| Plan Review Stops For Permit 03040754 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2004-07-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-07-20 |
Time |
09:03 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2004-07-20 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2004-07-20 00:00:00 | ****CORRECTIONS**** | | | PICNIC PAVILLION TRUSSES | | | MAIL KIOSK TRUSSES | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)SOME SHEETS ARE PHOTOCOPIES WITH | | | NO SEAL.ALL COPIES ARE REQUIRED | | | TO BE SIGNED, DATED, SEALED ORIGINALS | | | FAC61G15-23.002. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2004-06-02 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-06 |
Time |
14:07 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2004-06-02 |
Time |
14:54 |
Sent To |
|
|
| Notes |
| 2004-06-02 00:00:00 | REINFORCING STEEL SHOPS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2003-12-22 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2003-12-22 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2003-12-22 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2003-12-22 00:00:00 | BUILDING/ELECTRICAL/PLUBMING REVISION | | | SUBMITTED 11/10/03 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-09-05 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-09 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-09-05 |
Time |
10:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2003-04-29 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-04-29 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-04-29 |
Time |
09:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2003-11-17 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-11-17 |
Time |
16:08 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2003-11-17 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2003-11-17 00:00:00 | DENIED | | | ~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CHANGES TO | | | THE PLANS FOR CODE COMPLIANCE. | | | | | | 1} THE #4 KEYNOTE ON SHEET E16.10 | | | INDICATES A #4 ALUMINUM GROUND.ARTICLE | | | 310.2(B)(2),WEST PALM BEACH AMMENDMENTS | | | PROHIBITS THE USE OF ALUMINUM FOR | | | GROUNDING. | | | | | | 2} PLEASE INDICATE THE FEEDER SIZES ON | | | SHEET E16.10. | | | | | | 3} SMOKE DETECTORS AND FANS IN BEDROOMS | | | MUST BE ON AN ARC FAULT PROTECTED | | | CIRCUIT. SEE 212.12(B).ALSO PLEASE LOOK | | | AT THE DEFINITION OF "OUTLET" IN THE | | | NEC IF THERE ARE QUESTIONS TO THIS | | | REFERENCE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-09-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-09-09 |
Time |
19:52 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2003-09-09 |
Time |
19:09 |
Sent To |
|
|
| Notes |
| 2003-09-09 00:00:00 | ELECTRICAL PLANS OK, STAMPED AND SIGNED | | | OFF. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2003-06-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-06-24 |
Time |
08:23 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-06-24 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2003-06-24 00:00:00 | PLEASE SEE NOTES UNDER 03040756 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-04-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-04-29 |
Time |
18:12 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2003-04-29 |
Time |
18:12 |
Sent To |
|
|
| Notes |
| 2003-04-29 00:00:00 | ********* UNSAT ********* | | | | | | PLEASE SEE NOTES UNDER #03040756 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
P |
Date |
2003-11-24 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2003-11-24 |
Time |
08:42 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2003-11-24 |
Time |
08:41 |
Sent To |
|
|
| Notes |
| 2003-11-24 00:00:00 | PASSED: | | | 1. SEE PERMIT # 03111160 FOR UNDERGROUND | | | UTILITIES AND SITE WORK. | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2003-09-08 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2003-09-08 |
Time |
10:48 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2003-09-08 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2003-09-08 00:00:00 | PASSED WITH PROVISOS: | | | 1.UNDERGROUND UTILITIES /SITE WORK PLAN | | | IS APPROVED PROVIDED THAT ALL THE ISSUES | | | WITH PUBLIC UTILITIES AND ENGINEERING | | | ARE RESOLVED AND SITE PALN IS REVISED TO | | | THEIR SATISFACTIONS. UPON THE PUBLIC | | | UTILITIES AND ENGINEERING APPROVALS, THE | | | APPLICANT MUST APPLY SEPARATELY FOR | | | UNDERGROUND UTILITIES AND SITE WORK | | | PERMIT AND PAY THE APPROPRIATE FEES. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2003-06-05 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2003-06-05 |
Time |
14:15 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2003-06-05 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2003-06-05 00:00:00 | FAILED: | | | 1. PLEASE NOTE THAT A SEPARATE PERMIT | | | APPLICATION AND FEES FOR UNDERGROUND | | | UTILITIES AND SITE WORK IS REQUIRED, | | | PLEASE SUBMIT TWO SETS OF CIVIL DRAWING | | | ONLY APPROVED BY PUBLIC UTILITIES AND | | | SIGNED AND SEALED BY CIVIL ENGINEER OF | | | RECORD. | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2003-04-16 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2003-04-16 |
Time |
10:48 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2003-04-16 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2003-04-16 00:00:00 | FAILED: | | | 1. PLEASE NOTE THAT A SEPARATE PERMIT | | | APPLICATION AND FEES FOR UNDERGROUND | | | UTILITIES AND SITE WORK WILL BE REQUIRED | | | 2. A DDCV FOR ALL PRIVATE FIRE HYDRANT | | | WILL BE REQUIRED. | | | 3. A SEPARATE BACKFLOW PREVENTER FOR | | | EACH BUILDING IN DOMESTIC WATER LINE | | | AND ONE FOR THE PROPOSED POOL IS | | | REQUIRED. | | | 4. METER BANK 10-5/8" METERS AS PROPOSED | | | MUST BE APPROVED BY PUBLIC UTILITIES | | | 659-8040. | | | 5. PLEASE SUBMIT TWO SETS OF CIVIL PLANS | | | TO PUBLIC UTILITIES FOR THEIR REVIEW | | | AND APPROVAL PRIOR TO SUBMITTING TO THE | | | BUILDING DEPARTMENT. | | | 6. DUMPSTER ENCLOSURE MUST BE SIZED PER | | | CITY REQUIREMENTS IF TO BE PICKED UP BY | | | THE CITY. | | | 7. ANY WORK WITHIN PUBLIC ROW WILL | | | REQUIRES PERMIT FROMCITY ENGINEER | | | OFFICE, 659-8040. | | | 8. POLLUTION/EROSION PLAN MUST BE ADDED | | | TO THE PLANS, PLAN MUST BE INSTALLED IN | | | FIELD PRIOR TO ANY EARTH/ CONSTRUCTION | | | WORK AND MUST BE IN WORKING CONDITION | | | THROUGHOUT THE CONSTRUCTION DURATION. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2003-12-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-12-11 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-12-11 |
Time |
14:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-09-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-09-10 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-09-10 |
Time |
16:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-07-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-07-01 |
Time |
07:48 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-07-01 |
Time |
07:48 |
Sent To |
|
|
| Notes |
| 2003-07-01 00:00:00 | 1) CLUBHOUSE FIRE PUMP ROOM MISSING | | | REQUIRED EMERGENCY LIGHTING. | | | | | | 2) LETTER NEEDS TO BE NOTORIZED THAT | | | WAS SIGNED BY FRANCISCO ROJO. | | | | | | 3) EMERGENCY LIGHTS SEEM CONFUSING. | | | PLEASE INDICATE ALL EMERGENCY LIGHTS | | | IN CORRIDORS AND STAIRWELLS. | | | | | | 4) SIAMESE CONNECTION APPEARS TO FACE | | | THE WRONG DIRECTION. HOSE WILL KINK | | | WHEN CONNECTED TO BUILDING 1. | | | | | | 5) ON JUNE 30, 2003, WRITER MET WITH | | | ALEX BARROSO AT FIRE STATION # 4. IT | | | WAS EXPLAINED THAT ANOTHER FIRE HYDRANT | | | IS NEEDED IMMEDIATELY UPON ENTERING THE | | | NEW APARTMENT COMPLEX. | | | | | | WE ALSO DISCUSSED THAT SINCE YOU | | | CANNOT SEE THE NEW BUILDINGS FROM | | | EXECUTIVE CENTER DRIVE AND THAT YOU | | | MUST ENTER VIA LAKE PLACE THEN | | | PROPER SIGNAGE WILL BE REQUIRED ON | | | THE ROADWAY. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-07-06 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-06 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-06 |
Time |
14:07 |
Sent To |
B |
|
| Notes |
| 2004-07-06 00:00:00 | TO SH DESK/SUBMITTAL/PICNIC PAVILLION | | | TRUSSES |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-12-09 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-09 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-12-09 |
Time |
10:55 |
Sent To |
B |
|
| Notes |
| 2003-12-09 00:00:00 | TO HP DESK/21 MISC SHOP DRAWINGS- | | | SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-11-10 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-10 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-11-10 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2003-11-10 00:00:00 | TO COMM BD#41 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-06-05 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-05 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-05 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2003-06-05 00:00:00 | COMM BOARD #39 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
N |
Date |
2003-12-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-12-05 |
Time |
16:54 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2003-12-05 |
Time |
10:38 |
Sent To |
|
|
| Notes |
| 2003-12-05 00:00:00 | NO MECHANICAL REVISIONS SUBMITTED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2003-09-10 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2003-09-10 |
Time |
16:50 |
Rev Time |
1.50 |
| Received By |
hmoser |
Date |
2003-09-10 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2003-09-10 00:00:00 | PASS/PRIVISO | | | SEE PROVISO ON PERMIT # 03040755 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2003-06-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-06-24 |
Time |
12:44 |
Rev Time |
0.10 |
| Received By |
pkrauss |
Date |
2003-06-24 |
Time |
12:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-12-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-12-09 |
Time |
12:37 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-12-09 |
Time |
12:37 |
Sent To |
|
|
| Notes |
| 2003-12-09 00:00:00 | REVISION OK - SHTS AP/P14.01, AP/P14.03 | | | AP/P14.07, AP/P14.08, & AP/P14.2 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2003-09-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-09-04 |
Time |
16:53 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2003-09-04 |
Time |
16:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2003-04-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-04-30 |
Time |
12:46 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2003-04-30 |
Time |
12:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2003-09-12 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2003-09-12 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-09-12 00:00:00 | 9/12/03 OK PER GRACE GIVEN PERMIT & | | | OTHER TO LUIS MARTINEZ TO ISSUE PERMIT | | | MM |
|
|