Plan Review Details - Permit 03040753
Plan Review Stops For Permit 03040753
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-06-11 Cont ID  
Sent By hpiskura Date 2003-06-11 Time 11:14 Rev Time 0.00
Received By hpiskura Date 2003-06-11 Time 10:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-23 Cont ID  
Sent By hpiskura Date 2003-04-23 Time 15:26 Rev Time 0.00
Received By hpiskura Date 2003-04-23 Time 13:32 Sent To  
Notes
2003-04-23 00:00:00THE PLYWOOD SHEATHING SHOWN ON
 SHEETA2-3AND IN NOTES #17 AND #18 IS
 PROHIBITTED IN TYPE II CONSTRUCTION, BY
 THE CURRENT BUILDING CODE (FBC) AS WELL
 AS THE CODE THE BUILDING WAS
 CONSTRUCTED UNDER (SBC). SEE FBC 609.2.1
  
 SHEET A3-1 NOTE #9 THE SUSPENDED
 UMBRELLAS AND OTHER OBSTRUCTIONS MUST
 BE COORDINATED WITH THE FIRE SPRINKLER
 SYSTEM.PLEASE PROVIDE NOTES OR
 DIRECTION TO ENSURE COMPLIANCE.
  
 SHOW THE WIND PRESSURES FOR THE NEW
 EXTERIOR DOOR.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-11-17 Cont ID  
Sent By btrobaug Date 2003-11-17 Time 10:11 Rev Time 0.50
Received By btrobaug Date 2003-11-17 Time 10:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-08-06 Cont ID  
Sent By csiegber Date 2003-11-14 Time 11:55 Rev Time 1.00
Received By dpalmer Date 2003-08-06 Time 15:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-06-11 Cont ID  
Sent By dpalmer Date 2003-06-11 Time 12:48 Rev Time 0.50
Received By dpalmer Date 2003-06-11 Time 12:48 Sent To  
Notes
2003-06-11 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST
 REVIEW. PLEASE SEE PLANS SUBMITTED AND
 DATED 5/23/03, NOTES NOT ADDRESSED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION AND
 INFORMATION REQUESTED ON FIRST REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-16 Cont ID  
Sent By dpalmer Date 2003-04-16 Time 12:56 Rev Time 0.75
Received By dpalmer Date 2003-04-16 Time 12:56 Sent To  
Notes
2003-04-16 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING AND
 CONTROLS FOR NEW ITEMS . PLEASE ALSO
 CORRELATE W/ A SUBMITTED PANEL SCHEDULE
 (S).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-08-11 Cont ID  
Sent By nmccray Date 2003-08-11 Time 14:47 Rev Time 0.00
Received By nmccray Date 2003-08-11 Time 14:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-06-26 Cont ID  
Sent By nmccray Date 2003-06-26 Time 10:50 Rev Time 0.00
Received By nmccray Date 2003-06-26 Time 10:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-04-11 Cont ID  
Sent By mcarsill Date 2003-04-11 Time 14:43 Rev Time 0.00
Received By mcarsill Date 2003-04-11 Time 14:43 Sent To  
Notes
2003-04-11 00:00:001) NO CITY PLACE STAMP COULD BE
 LOCATED ON THE PLANS.
  
 2) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION FOR WALLS AND CEILINGS.
  
 3) PLEASE INDICATE FURNITURE LOCATIONS.
  
 4) PLEASE INDICATE ANY PROPOSED WAITING
 AREAS.
  
 5) PLEASE INDICATE LOCATIONS OF
 REQUIRED HANDICAPPED SEATING.
  
 6) PLEASE INDICATE LOCATIONS OF FIRE
 ALARM EQUIPMENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-11-14 Cont ID  
Sent By csiegber Date 2003-11-14 Time 11:55 Rev Time 0.00
Received By csiegber Date 2003-11-14 Time 11:55 Sent To E
Notes
2003-11-14 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-30 Time 14:09 Rev Time 0.00
Received By alange Date 2003-07-30 Time 14:09 Sent To  
Notes
2003-07-30 00:00:00TO COMM BD #3

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-20 Cont ID  
Sent By shernand Date 2003-06-20 Time 15:42 Rev Time 0.00
Received By shernand Date 2003-06-20 Time 15:42 Sent To  
Notes
2003-06-20 00:00:00COMM BOARD #50

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-05 Cont ID  
Sent By shernand Date 2003-06-05 Time 15:03 Rev Time 0.00
Received By shernand Date 2003-06-05 Time 15:03 Sent To  
Notes
2003-06-05 00:00:00COMM BOARD #50

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-09 Cont ID  
Sent By shernand Date 2003-04-09 Time 16:50 Rev Time 0.00
Received By shernand Date 2003-04-09 Time 16:50 Sent To  
Notes
2003-04-09 00:00:00COMM BOARD #16

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-08-11 Cont ID  
Sent By pkrauss Date 2003-08-11 Time 12:44 Rev Time 0.55
Received By pkrauss Date 2003-08-11 Time 12:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2003-06-24 Cont ID  
Sent By pkrauss Date 2003-06-24 Time 08:39 Rev Time 0.30
Received By pkrauss Date 2003-06-24 Time 08:31 Sent To  
Notes
2003-06-24 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
 PLEASE PROVIDE PLANS WITH PERMIT
 APPLICATION.
  
 SEPARATE PERMITS REQUIRED FOR HOOD, FIRE
 SUPPRESSION, AND WALK-IN COOLERS. PLEASE
 PROVIDE PLANS & MANUFACTURER SUBMITTAL
 DATA WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-05-03 Cont ID  
Sent By pkrauss Date 2003-05-03 Time 09:34 Rev Time 0.30
Received By pkrauss Date 2003-05-03 Time 09:25 Sent To  
Notes
2003-05-03 00:00:00 
 NO MECHANICAL PLANS SUBMITTED FOR REVIEW
  
 PROVIDE PLANS INDICATING ANY CHANGES TO
 THE EXISTING HVAC SYSTEM.
  
 PROVIDE REVISED OUTSIDE AIR CALCS AS PER
 2001 FBC(M) TABLE 403.3.
  
 INDICATE IF ANY MODIFICATION TO HOOD
 OR SUPPRESSION SYSTEM IS PLANNED.SHOW
 ANY NEW WORK TO BE DONE.PLEASE NOTE,
 SEPARATE PERMITS REQUIRED FOR HOOD, FIRE
 SUPPRESSION, OR WALK-IN COOLERS/FREEZERS
 PROVIDE PLANS & MANUFACTURERS SUBMITTAL
 DATA WITH PERMIT APPLICATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-08-15 Cont ID  
Sent By kstevens Date 2003-08-15 Time 13:07 Rev Time 2.50
Received By kstevens Date 2003-08-11 Time 17:59 Sent To  
Notes
2003-08-15 00:00:00PASSED - PROVISO-
 GAS APPLIANCES EXISTING - MOVING LOCAT-
 ION. INSPECTORS SHALL FIELD VERIFY BTU'S
 AND LISTING. KITCHEN PIPING TO STAY -
 MOVING LOCATIONS OF SOME KIT. FIXTURES
 NEW PIPING FOR NEW BAR & EXISTING BAR
 ONLY. - EXISTING GREASE INTERCEPTOR

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-06-23 Cont ID  
Sent By kstevens Date 2003-06-23 Time 16:29 Rev Time 0.50
Received By kstevens Date 2003-06-23 Time 16:29 Sent To  
Notes
2003-06-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) COMMENTS FROM PREVIOUS REVIEW NOT
 ADDRESSED. SEE ATTACHED SHEET FOR COMM-
 ENTS FROM 1ST REVIEW.
 2) SEE ATTACHED SHEET CONCERNING FLORIDA
 STATUTE 553.80(2)(B)
 ********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-25 Cont ID  
Sent By kstevens Date 2003-04-25 Time 08:45 Rev Time 1.50
Received By kstevens Date 2003-04-25 Time 08:45 Sent To  
Notes
2003-04-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) PLEASE PROVIDE A SANITARY RISER DIA-
 GRAM AND A WATER RISER DIAGRAM SHOWING
 ALL CHANGES TO EXISTING SYSTEMS.
 2) PLEASE CONTACT RODNEY COMPO, ENVIRON-
 MENTAL COMPLIANCE TO CHECK SIZE OF THE
 GREASE TRAP FOR THE NEW RESTURANT.
 WASTE ORD #2938-96. (561) 837-4074
 3) PLANS SHALL BE ROUTED TO DBPR, HOTEL
 AND RESTAURANT DIVISION FOR REVIEW.
 PLEASE RETURN FOR REVIEW WITH STAMPED
 SETS WITH WORK SHEETS ATTACHED TO PLANS.
 (954) 958-5520
 4) PLANS SHALL BE STAMPED BY CITY PLACE
 PRIOR TO RESUBMITTING.
 5) FOLLOWING INFORMATION REQUIRED FOR
 GAS APPLICATION. (SEPARATE PERMIT REQD.)
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692