Plan Review Details - Permit 03040662
Plan Review Stops For Permit 03040662
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-05-14 Cont ID  
Sent By hpiskura Date 2003-04-25 Time 08:59 Rev Time 0.00
Received By hpiskura Date 2003-04-25 Time 11:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-06-05 Cont ID  
Sent By btrobaug Date 2003-06-05 Time 09:54 Rev Time 1.00
Received By btrobaug Date 2003-06-05 Time 08:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-24 Cont ID  
Sent By dpalmer Date 2003-04-24 Time 17:29 Rev Time 0.75
Received By dpalmer Date 2003-04-24 Time 17:29 Sent To  
Notes
2003-04-24 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE CLARIFY LOCATION FOR
 STORAGE AND USE OF OIL IN DRUMS AND/OR
 ANY HAZARDOUS LOCATION PER NEC ART 500.
  
  
 2)NOTE: PLEASE SHOW REQ`D SIGN CIRCUIT
 PER 600-5.
  
 3)NOTE: PLEASE PROVIDE "SHOW" WINDOW"
 RECEPTS PER 210-62
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2003-06-16 Cont ID  
Sent By shernand Date 2003-06-16 Time 16:57 Rev Time 0.00
Received By shernand Date 2003-06-16 Time 16:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-06-16 Cont ID  
Sent By nmccray Date 2003-06-16 Time 13:28 Rev Time 0.00
Received By nmccray Date 2003-06-16 Time 13:28 Sent To  
Notes
2003-06-16 00:00:00************PROVISO*********************
 FIRE ALARM SYSTEM TO BE CLASS "A" OR
 FULLY ADDRESSABLE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-05-15 Cont ID  
Sent By shernand Date 2003-05-14 Time 16:31 Rev Time 0.00
Received By nmccray Date 2003-05-15 Time 10:13 Sent To  
Notes
2003-05-15 00:00:00REF: NFPA 101 LIFE SAFETY 2000 EDITION
 CH.40 & CH.7
  
 1) PLEASE PROVIDE LOCATION OF STORED OIL
 DRUMS IN WAREHOUSE.
  
 2) THERE APPEARS TO BE AN EXIT SIGN OVER
 THE DOOR OF WAREHOUSE RESTROOM.
  
 3) PLEASE PROVIDE INTERIOR WALL AND
 CEILING FINISH CLASSIFICATION.
  
 4) SEPARATE PERMIT APPLICATIONS AND FEES
 FOR FIRE SPRINKLER AND FIRE ALARM SYSTEM
 WILL BE REQUIRED.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-09-29 Cont ID  
Sent By csiegber Date 2003-09-29 Time 08:37 Rev Time 0.00
Received By csiegber Date 2003-09-29 Time 08:37 Sent To P
Notes
2003-09-29 00:00:00TO KS DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-02 Cont ID  
Sent By shernand Date 2003-06-02 Time 09:37 Rev Time 0.00
Received By shernand Date 2003-06-02 Time 09:37 Sent To  
Notes
2003-06-02 00:00:00COMM BOARD #16

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-05-14 Time 16:13 Rev Time 0.00
Received By shernand Date 2003-05-14 Time 16:13 Sent To FIRE
Notes
2003-05-14 00:00:00COMM BOARD #
 REMOVED FROM COMM BOARD, NEEDS FIRE,
 THEN WILL CALL TO P/U FOR CORRECTIONS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-08 Cont ID  
Sent By shernand Date 2003-04-08 Time 16:48 Rev Time 0.00
Received By shernand Date 2003-04-08 Time 16:48 Sent To  
Notes
2003-04-08 00:00:00COMM BOARD #21 BOTH PERMIT#03040662 AND
 #03040660

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-03 Cont ID  
Sent By pkrauss Date 2003-05-03 Time 10:09 Rev Time 0.40
Received By pkrauss Date 2003-05-03 Time 10:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-09-30 Cont ID  
Sent By kstevens Date 2003-09-30 Time 08:47 Rev Time 0.50
Received By kstevens Date 2003-09-30 Time 08:47 Sent To  
Notes
2003-09-30 00:00:00REVISION OK - CHANGED ROUTING OF SANT.
 PIPING.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-04-23 Cont ID  
Sent By csiegber Date 2003-09-29 Time 08:37 Rev Time 1.00
Received By kstevens Date 2003-04-23 Time 17:43 Sent To  
Notes
2003-04-23 00:00:00PASSED PROVISO: 607.3.2 THERMAL EXPAN-
 SION CONTROL REQUIRED. - 410.1 WATER
 COOLER SHALL BE ARI-1010 COMPLIANT,
 MANUF. INFO. REQUIRED AT PLMB FINAL.

Review Stop Z ZONING
Rev No 1 Status N Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-05-14 Time 16:17 Rev Time 0.00
Received By shernand Date 2003-05-14 Time 16:17 Sent To  
Notes
2003-05-14 00:00:00NO ZONING NEEDED.