| Plan Review Stops For Permit 03040659 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-04-08 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-08 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-08 |
Time |
16:56 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2003-04-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-04-15 |
Time |
10:56 |
Rev Time |
4.00 |
| Received By |
pkrauss |
Date |
2003-04-15 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2003-04-15 00:00:00 | CALLED (503) 703-0322, PIPING IS OKAY, | | | SEE BUILDING PERMIT 01121500 FOR | | | VENTILATION IN THE ENGINE ROOM - FANS | | | RUN CONTINUOUSLY, SENSORS ARE TO BE | | | INSTALLED AS PER PLAN SHEET M-4.2. | | | | | | PROVISO:ENGINE ROOM TO COMPLY WITH | | | 1997 SMC CHAPTER 11.PLANS DO NOT | | | INDICATE A BREATHING APPARATUS AS | | | DICTATED IN SECTION 1105.8.TERMINATION | | | OF RELIEF DEVICES SHALL BE OUTSIDE OF | | | STRUCTURE NOT LESS THAN 15 FT ABOVE THE | | | ADJOINING GROUND AND NOT LESS THAN 20 FT | | | FROM ANY WINDOW, VENTILATION OPENING OR | | | EXIT TO ANY BUILDING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|