Plan Review Details - Permit 03040657
Plan Review Stops For Permit 03040657
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-08-05 Cont ID  
Sent By csiegber Date 2003-12-04 Time 08:20 Rev Time 0.50
Received By jwitmer Date 2003-08-05 Time 14:26 Sent To  
Notes
2003-08-05 00:00:00FENCE

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-07-14 Cont ID  
Sent By jwitmer Date 2003-07-14 Time 09:32 Rev Time 0.25
Received By jwitmer Date 2003-07-14 Time 09:32 Sent To Z
Notes
2003-07-14 00:00:00REV# 4 FENCE, W.P.B. CITY AMENDMENT
 104.1.1. BARRIERS & SIGNS, TO ERECT OR
 REPLACE FENCES, WALLS, SIGNS OR SIGN
 STRUCTURES REQUIRES A PERMIT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-05-30 Cont ID  
Sent By shernand Date 2003-07-11 Time 16:46 Rev Time 0.75
Received By jwitmer Date 2003-05-30 Time 09:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-05-20 Cont ID  
Sent By shernand Date 2003-05-30 Time 08:46 Rev Time 0.55
Received By jwitmer Date 2003-05-20 Time 16:20 Sent To  
Notes
2003-05-20 00:00:00REQUIRES IMPACT FEES, J WITMER
 READY TO ISSUE AFTER IMPACT FEES PAID
 5/20/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-05-02 Cont ID  
Sent By kstevens Date 2003-05-20 Time 14:59 Rev Time 3.20
Received By jwitmer Date 2003-05-02 Time 08:29 Sent To  
Notes
2003-05-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03040657
 ADD: 6343 PARADISE COVE
 CONT: DOUBLE R BLDG
 TEL: (954)796-0777
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
  
 CONTRACTOR IS CONTINUEING AT OWN RISK!
 SOILS REPORT SUBMITTED TO THIS OFFICE,
 "A PRELIMINARY GEOTECHNICAL EVALUATION"
 FOR RENAISSANCE SECTION# 7 .UNDER LIMITA
 TIONS (5.0)"IT IS IMPORTANT TO REALIZE
 THAT THE INFORMATION PROVIDED IN THIS
 REPORT IS NOT SUFFICIENT FOR A FINAL
 DESIGN OF THE FOUNDATION SYSTEM".
  
 3) BEDROOM # 3, EGRESS WINDOW NOT ACCESS
 IBLE.SHEET A-2 WINDOW (R) IS LABELED A
 34+4 A EGRESS WINDOW. CLEAR HEIGHT FOR A
 34 WINDOW IS 20.0945 IF YOU ADD 4" IN
 HEIGHT TO THE OVERALL HEIGHT, YOU WILL
 ONLY GAIN 2" IN CLEAR HEIGHT, TOTALING
 22.0945".
  
 4)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 RE-EVALUATE TRUSS TABLES WITH THE LOWER
 VALUES IN THE 2003 USP CATALOG.
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-12 Cont ID  
Sent By btrobaug Date 2003-05-12 Time 05:59 Rev Time 0.50
Received By btrobaug Date 2003-05-12 Time 05:53 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-18 Cont ID  
Sent By shernand Date 2003-05-09 Time 17:07 Rev Time 0.75
Received By btrobaug Date 2003-04-18 Time 10:11 Sent To P
Notes
2003-04-18 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 TO THE PLAN FOR CODE COMPLIANCE.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR FOR
 A 400 AMP SERVICE MUST COMPLY WITH
 250-66.(1/0).
  
 2} THE FEEDERS FOR PANEL "B" MUST
 CONTAIN AN EQUIPMENT GROUND.
  
 3} THE LAUNDRY CIRCUIT ON THE PANEL
 SCHEDULE MUST COMPLY WITH
 220-16(B).1.5KW.
  
 4} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} SMOKE DETECTOR IN THE KITCHEN IS IN
 VIOLATION OF 8-4.1.2 NFPA-72,CHANGE TO A
 LISTED HEAT DETECTOR,OR REMOVE.
  
 6} THE SMOKE DETECTOR IN THE ENTRY TO
 THE MASTER SUITE SHOULD BE LOCATED IN
 THE VESTIBULE TO MEET THE INTENT OF
 ARTICLE 8-1.4.1.6.2(2) AS "OUTSIDE" THE
 SLEEPING AREA.
  
 7} BEDROOM #4 NEEDS A RECEPTACLE TO
 COMPLY WITH 210-52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-12-04 Cont ID  
Sent By csiegber Date 2003-12-04 Time 08:20 Rev Time 0.00
Received By csiegber Date 2003-12-04 Time 08:20 Sent To B
Notes
2003-12-04 00:00:00TO JW DESK/REV-REMOVE FENCE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-11 Time 16:46 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 16:46 Sent To B
Notes
2003-07-11 00:00:00JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-30 Cont ID  
Sent By shernand Date 2003-05-30 Time 08:46 Rev Time 0.00
Received By shernand Date 2003-05-30 Time 08:46 Sent To B
Notes
2003-05-30 00:00:00JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-09 Cont ID  
Sent By shernand Date 2003-05-09 Time 17:07 Rev Time 0.00
Received By shernand Date 2003-05-09 Time 17:07 Sent To E
Notes
2003-05-09 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-09 Cont ID  
Sent By shernand Date 2003-04-09 Time 09:09 Rev Time 0.00
Received By shernand Date 2003-04-09 Time 09:09 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-04-23 Cont ID  
Sent By alange Date 2003-04-21 Time 17:24 Rev Time 0.50
Received By hmoser Date 2003-04-23 Time 17:28 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-05-20 Cont ID  
Sent By kstevens Date 2003-05-20 Time 14:58 Rev Time 0.50
Received By kstevens Date 2003-05-20 Time 14:57 Sent To B
Notes
2003-05-20 00:00:00PASSED - PROVISO
  
 LAV AND SINK ON RISER DIAGRAM NOT SHOWN
 ON FLOOR PLAN. REVISION REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-21 Cont ID  
Sent By btrobaug Date 2003-05-12 Time 06:00 Rev Time 0.50
Received By alange Date 2003-04-21 Time 17:24 Sent To M
Notes
2003-04-21 00:00:00DENIED;
 PAGE A-1 PLUMBING RISER DIAGRAM NOT TO
 CODE. SEC.909.1. WET VENTS FOR BATHROOMS
 ARE PERMITTED TO VENT ONLY BATHROOM
 FIXTURES. WASHING MACHINE AND LAUNDRY
 TUB ARE REQUIRED TO DISCHARGE DOWN
 STREAM OF THE BATHROOM GROUP.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-09 Cont ID  
Sent By jwitmer Date 2003-07-14 Time 09:40 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***