Plan Review Details - Permit 03040652
Plan Review Stops For Permit 03040652
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-05-13 Cont ID  
Sent By hpiskura Date 2003-05-13 Time 13:20 Rev Time 0.00
Received By hpiskura Date 2003-05-13 Time 13:15 Sent To  
Notes
2003-05-13 00:00:00PROVISO:ONLY WORK SHOWN ON PLANS
 PREPARED BY KIMLEY - HORN DATED 4/30/03
 WILL BE PERMITTED.ANTENNAS AND
 CONNECTIONS WILL REQUIRE A SEPARATE
 PERMIT, PLANS AND FEES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-16 Cont ID  
Sent By shernand Date 2003-04-16 Time 09:07 Rev Time 0.00
Received By hpiskura Date 2003-04-16 Time 13:38 Sent To  
Notes
2003-04-16 00:00:00THERE IS NO INFORMATION FOR THE ACTUAL
 ANTENNA ITSELF AND ITS CONNECTION
 DETAILS.
  
 THE WORK SHOWN IS CODE COMPLIANT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-12 Cont ID  
Sent By dpalmer Date 2003-05-12 Time 07:28 Rev Time 0.50
Received By dpalmer Date 2003-05-12 Time 07:28 Sent To  
Notes
2003-05-12 00:00:00************ NOTE *****************
  
 PLEASE SEE THAT NO PERMIT APPLICATION
 CAME BACK IN W/ PLANS.
 UNABLE TO VERIFY VALUE OF WORK BEING
 DONE. 104.6.5
 ONLY UNDER PLAN REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-22 Cont ID  
Sent By shernand Date 2003-04-16 Time 10:04 Rev Time 0.75
Received By dpalmer Date 2003-04-22 Time 10:28 Sent To  
Notes
2003-04-22 00:00:00************* UNSAT ***********
  
 1)NOTE: PLEASE CORRECT ADDRESS ON PLANS.
 ACTUAL ADDRESS IS 255 EVERNIA. ELECTRIC-
 AL PLANS SEEM TO HAVE CORRECT ADDRESS.
  
 2)NOTE: PLEASE PROVIDE COPY OF CONTRACT
 FOR COMPLETE SCOPE OF WORK, TO INCLUDE
 LABOR AND MATERIALS EVEN IF OWNER SUPPL-
 IED. 104.6.5 CITY-WIDE ADMIN CODE.
 APPL SHOWS 19,450.
  
 3)NOTE: PLEASE CLARIFY AWG AND OCP FOR
 SURGE ARRESTOR ON PANEL. PLEASE ALSO
 SEE MAX # OF #2`S IN 2" CONDUIT. PER
 NEC TABLES.
  
 PLEASE APPLY FOR PERMIT APPLICATION AND
 PAY PERMIT FEES.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-08 Cont ID  
Sent By shernand Date 2003-05-08 Time 14:16 Rev Time 0.00
Received By shernand Date 2003-05-08 Time 14:16 Sent To  
Notes
2003-05-08 00:00:00COMM BOARD #46

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-16 Cont ID  
Sent By shernand Date 2003-04-16 Time 09:07 Rev Time 0.00
Received By shernand Date 2003-04-16 Time 09:07 Sent To  
Notes
2003-04-16 00:00:00COMM BOARD #23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-08 Cont ID  
Sent By shernand Date 2003-04-08 Time 16:29 Rev Time 0.00
Received By shernand Date 2003-04-08 Time 16:29 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-04-15 Cont ID  
Sent By shernand Date 2003-04-08 Time 16:32 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***