Plan Review Details - Permit 03040477
Plan Review Stops For Permit 03040477
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2004-03-05 Cont ID  
Sent By shill Date 2004-03-05 Time 14:33 Rev Time 0.50
Received By shill Date 2004-03-05 Time 14:33 Sent To  
Notes
2004-03-05 00:00:00REVISION, 1A6.2.1 2/13/4

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2004-03-01 Cont ID  
Sent By shill Date 2004-02-28 Time 16:52 Rev Time 1.00
Received By shill Date 2004-02-28 Time 16:52 Sent To  
Notes
2004-02-28 00:00:00TRUSS SUBMITTALS, OK PER HP (RESOLVED
 ISSUES ON TELEPHONE)

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2004-01-28 Cont ID  
Sent By csiegber Date 2004-02-25 Time 12:21 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2004-01-28 00:00:00TRUSS ENGINEERING PREPARED BY THOMAS
 KELAHER, PE. DATED VARIOUSLY 11/25/03
 AND 12/12/03.
  
 THE REVIEW OF DELEGATED ENGINEERING
 SHOULD BE BY THE ENGINEER OF RECORD,
 NOT AN EIT.
  
 SHEETS DATED 12/12/03 LABELED SHOP
 DRAWING SK-01 AND OTHERS LABELED RT-01,
 H-02, ETC., SIGNED AND SEALED BY T.
 KELAHER DO NOT SHOW ANY LOADING OR
 CRITERIA USED FOR THE DESIGN.
  
 THE COMPUTER CALCULATIONS PROVIDED ARE
 NOT REFERENCED OR RECOGNIZED IN THE
 KELAHER COVER LETTER.THE COVER LETTER
 "METAL STUD ROOF FRAMING
 SPECIFICATIONS" DOES NOT REFENCE OR
 INDEX ANY OF THE OTHER TRUSS DESIGN
 INFORMATION.
  
 PLEASE REVISE AS NECESSARY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2003-10-23 Cont ID  
Sent By csiegber Date 2004-01-27 Time 14:53 Rev Time 0.00
Received By hpiskura Date 2003-10-23 Time 07:54 Sent To  
Notes
2003-10-23 00:00:00REVISONS DATED 9/2/03 AND 9/23/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-08-14 Cont ID  
Sent By csiegber Date 2003-10-21 Time 14:47 Rev Time 0.00
Received By hpiskura Date 2003-08-14 Time 09:58 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2003-08-01 Cont ID  
Sent By alange Date 2003-08-05 Time 13:10 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-08-01 00:00:00STH LETTER DATED 7/31/03 RE: FILLED
 MASONRY.
  
 THE ARCHITECT CITES FBC 709.3.2 AS A
 METHOD FOR CODE COMPLIANCE.THIS IS
 NOT VALID FOR THE CORE FILL 500 SINCE
 THE TEST STANDARDS ARE FOR MINERAL TYPE
 AGGREGATES AND THE FOAM BASED MATERIAL
 DOES NOT LEND ITSELF TO THOSE METHODS.
  
 BASED ON THE INFORMAION PROVIDED,
 PARTICULARLY THE SOUTHWEST RESEARCH
 INSTITUTE, DATA, IT MAY BE APPROVED FOR
 USE UNDER FBC 103.7 ALTERNATE MATERIALS
 AND METHODS.
  
 THERE ARE SOME CONFLICTS IN THE
 INFORMATION THAT MUST BE RESOLVED
 BEFORE THE BUILDING OFFICIAL MAY RENDER
 A DECISION TO ACCEPT THIS MATERIAL/METHO
  
 PAGE 30F5 IN REPORT 01-6740-711 DATED
 8/95 STATED THAT TEST ASSEMBLY HAD
 CELLS FILLED WITH MORTAR AS SHOWN IN
 FIGURE A-3 OF APPENDIX A.THIS APPENDIX
 AND FIGURE ARE NOT INCLUDED AND APPEAR
 TO BE A KEY ELEMENT IN THE TEST WHEN
 TAKEN IN THE CONTEXT OF THE
 INTRODUCTION TO THE REPORT.
  
 THE SWRI LETTER TO JACK TEMPLE DATED
 11/4/96 REFERENCES AN SWRI FINAL REPORT
 01-7522-607 WHICH IS DIFFERENT THAN THE
 01-6740-711 PROVIDED.
  
 PLEASE REVIEW FBC 103.7 AND PROVIDE
 COMPLETE AND COMPLEMENTARY DATA SO THAT
 EQUIVALENT CODE COMPLIANCE MAY BE
 DETERMINED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-07-16 Cont ID  
Sent By hpiskura Date 2003-07-16 Time 14:52 Rev Time 0.00
Received By hpiskura Date 2003-07-16 Time 14:52 Sent To  
Notes
2003-07-16 00:00:00THE STH LETTER DATED 6/24/03 RESPONDED
 TO THE REQUEST FOR INFORMATION AND/OR
 CODE DEFICIENCIES CONTAINED IN THE
 5/28/03 COMMENT LIST.
  
 THE THRESHOLD INSPECTION PLAN HAS BEEN
 RECEIVED, HOWEVER THE STATEMENT
 REQUIRED BY FS 553 TO APPEAR ON THE
 PLANS HAS NOT.THE ARCHITECT'S
 RESPONSE TO SEE THE ENCLOSED LETTER
 FROM ONMJ IS NOT SUFFICIENT, NOR WAS AN
 LETTER FOUND.PLEASE REVISE THE PLANS
 AS NECESSARY.
  
 THE REQUEST FOR THE LISTING OF THE
 RINKER T-14 BLOCK MEETING A THREE HOUR
 RATING WAS RESPONDED TO WITH A UL
 LISTING U905. RINKER WAS NOT FOUND AS
 AN "ELIGIBLE MANUFACTURER" AS CALLED FOR
 IN ITEM #1 OF THAT LISTING.PLEASE
 PROVIDE DATA DEMONSTRATING COMPLIANCE
 WITH FBC 701.5.
  
 THE HUSTON SEATING PLAN DATED 6/13/03
 DOES NOT APPEAR TO HAVE THE 19" CLEAR
 SPACE BETWEEN THE CHAIR AND TABLE IN
 ACCORDANCE WITH FBC 1019.10.3.5.1 FOR
 LECTURE ROOMS 1, 2 AND 3.
  
 THE EMERGENCY LIGHING REQUIRED BY FBC
 1016.2 IS NOT SHOWN ON THE PLANS.A
 SEPARATE RESPONSE BY THE ELECTRICAL
 ENGINEER AS NOTED IN THE ARCHITECT'S
 RESPONSE, HAS NOT BEEN FOUND.PLEASE
 REVISE AS NECESSARY.
  
 PANIC HARDWARE IS REQUIRED IN
 CLASSROOMS 1, 2 AND 3 AS DEPICTED ON
 SHEET A1.3.2 SINCE THE OCCUPANT LOAD IS
 > 100.SEE FBC 1021.3.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-05-28 Cont ID  
Sent By hpiskura Date 2003-05-28 Time 11:11 Rev Time 0.00
Received By hpiskura Date 2003-05-21 Time 13:25 Sent To  
Notes
2003-05-28 00:00:00PLANS DATED 5/3/03 NO REVISION DATE.
  
 PLEASE PROVIDE A RECENT PROPERTY SURVEY.
  
 THIS IS A THRESHOLD BUILDING AS DEFINED
 IN 553.71, FLORIDA STATUTES AND REQUIRES
 A THRESHOLD INSPECTION PLAN AND THE
 STATEMENT ON THE PLANS DECLARING
 COMPLIANCE WITH 553.
  
 PLEASE PROVIDE A LISTING OR
 SPECIFICATION THAT A RINKER T-14 BLOCK
 MEETS A THREE HOUR FIRE RATING WITH AN
 EQUIVALENT THICKNESS REQUIRED BY FBC
 709.3.
  
 SHEET A1.3.1, NOTE #1 ERRONEOUSLY
 DECLARES "UNLIMITED, UNPROTECTED
 OPENINGS FOR WALLS MORE THAN 15' ..."
 SEE FBC TABLE 600, FBC 705 SPEAKS TO
 FIRE PROTECTION OF OPENINGS, NOT AREA.
 PLEASE REVISE AS NECESSARY.
  
 SHEETS A1.3.1 AND 1.3.2.SHOW A
 SEATING PLAN AND AISLE WIDTHS.SEE FBC
 1003.1.2.
  
 SHEET A1.3.3, ROOM 307.THE
 MEASUREMENTOF THE DIAGONAL DISTANCE
 SEPARATION OF THE EXIT ACCESS DOORS IS
 INCORRECT AS SHOWN ON THE PLAN.A
 STRAIGHT LINE DISTANCE IS USED. SEE FBC
 1004.1.4 AND REVISE AS NECESSARY.
  
 SHEET A1.4.1 INCORRECTLY CALCULATES THE
 RATIO OF WALL OPENINGS TO WALL AREA.
 THE WALL AREA FOR TABLE 600 IS BASED ON
 A PER FLOOR AREA, AND AS MEASURED FROM
 FLOOR TO CEILING NEXT ABOVE.OPENINGS
 ARE TAKEN AS THE ROUGH OPENING SIZE.
 PLEASE REVISE AS NECESSARY.
  
 WHAT IS THE GATE AND HAND RAIL SHOWN IN
 SECTION 1 SHEET A5.2.1 USED FOR?
  
 SHEET A5.2.2 THE DELEGATION OF THE
 DESIGN OF THE STAIRS REQUIRES SPECIFIC
 INFORMATION NOT A CODE SECTION
 REFERENCE.SEE FBC 104.2.
  
 SHEET A6.1.1 HAS REFERENCE TO A GLAZING
 SCHEDULE AND SPECIFICATIONS NOT PROVIDED
 WITH THIS PERMIT APPLICATION.
  
 SHEET A6.2.1 SHOWS A SCREEN IN THE IN
 THE EMERGENCY OVERFLOW SCUPPER PIPE.
 WHATVOLUME OF WATER IS CALCULATED TO
 FLOW THROUGH THIS SCREEN AT WHAT RATES?
 SEE FBC 1503.4.
  
 SHEET A6.2.2, SECTION 6.SHOW A
 CONSTRUCTION DETAIL FOR THE SUSPENDED
 PLASTER SOFIT INCLUDING FRAMING AND
 FASTENERS. SEE FBC 104.2.
  
 SHEET A7.2.1 CALLS FOR THE UNDERCUTTING
 OF FIRE RATED DOORS.SEE NFPA 80 FOR
 LIMITATIONS.
  
 SHEET S1 SHOWS COLUMN FOOTINGS EXTENDING
 BEYOND THE APPARENT PROPERTY LINE.
 SEE FBC 3207.
  
 SHEET S6 CITES SSTD 12-97.SSTD 12-99
 IS INVOKED BY THE FBC, PLEASE REVISE
 AND INSURE COMPLIANCE AS NECESSARY.
  
 SHEET S4, SHOW THE METHOD OF FIRE
 PROTECTION FOR THE COLUMNS SHOWN AS SC2.
 AND THE STEEL COLUMNS SHOWN IN SECTION
 3/6.1.2.
  
 SHEET S7, SHOW THE FIRE PROTECION FOR
 THE STRUCTURE SHOWN IN SECTION AS
 TYPICAL HANGING PARTITION DETAIL.
  
 SHOW HOW COMPLIANCE WITH FBC 1405 WILL
 BE ACCOMPLISHED, (FIRE DEPARTMENT
 ACCESS), WITH REGARDS TO THE HURRICANE
 MISSILE IMPACT GLAZING.SEE FBC 903.5
 #2 FOR PERSPECTIVE.
  
 SHOW THE PANIC HARDWARE FOR THE DOORS IN
 ACCORDANCE WITH FBC 1021.3.1.
  
 SHOW THE STAIR IDENTIFICATION AS
 PROVIDED FOR IN FBC 1016.4.
  
 SHOW THE EMERGENCY LIGHTING FOR THE
 COVERED WALKWAYS ON THE SOUTH AND WEST
 SIDES OF THE FIRST FLOOR. SEE FBC 1016.2
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFIEC AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-21 Cont ID  
Sent By shernand Date 2003-05-19 Time 14:04 Rev Time 0.00
Received By hpiskura Date 2003-04-22 Time 10:11 Sent To  
Notes
2003-04-23 00:00:00PAID PLAN REVIEW NOT A PERMIT
 APPLICATION.
  
 THE PLANS PROVIDED WERE INCOMPLETE AND
 WITHOUT SPECIFICATIONS SO A CLOSE AND
 CRITICAL PLAN REVIEW WAS NOT POSSIBLE.
  
 AT TIME OF PERMIT APPLICATION ADHERENCE
 TO THE ITEMS IN FBC 104.3.1.1 WILL
 ENSURE AN EXPEDITIOUS PLAN REVUE.
  
 THE PROPOSED BUILDING WILL BE A
 THRESHOLD BUILDING AND MUST COMPLY WITH
 FBC 105.13.
  
 SHEET A2.5.1, ROOF PLAN.THE AREA
 DECLARED AS "UOCCUPIED SPACE" WILL BE
 COUNTED AS A STORY SINCE IT DOES NOT
 COMPLY WITH FBC 1511.1.1.3, FURTHER THE
 TOTAL AREA OF ROOF STRUCTURES EXCEEDS
 THE 1/3 ALLOTTED BY FBC 1511.1.1.2.
 (THIS INCLUDES THE MANSARD LIKE
 STRUCTURES)
  
 CONSEQUENTLY, THE PROPOSED BUILDING
 WILL EXCEED THE ALLOWABLE HEIGHT OF 65'
 IN TABLE 500 FOR TYPE IV 1 HOUR
 PROTECTED CONSTRUTION. PLEASE REVISE AS
 NECESSARY PRIOR TO PERMIT APPLICATION.
  
 SHEET S6 THE MASONRY COLUMN SCHEDULE
 INDICATES 6 #7'S IN AN 8X16 BLOCK.
 WHAT IS THE ANTICIPATED CLEAR CELL
 SPACE FOR GROUT?

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2004-06-25 Cont ID  
Sent By dpalmer Date 2004-06-25 Time 13:28 Rev Time 0.25
Received By dpalmer Date 2004-06-25 Time 13:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-06-25 Time 12:26 Rev Time 0.33
Received By dpalmer Date 2004-06-23 Time 14:14 Sent To  
Notes
2004-06-23 00:00:00******** UNSAT ******
  
 1)NOTE: PLEASE REVISED TITLE BLOCK
 WITH CORRECT CA#.
 FAC 61G15-23.002/ FS 471.023
  
 2)NOTE: PLEASE SEE THAT ALL THREE SETS
 MUST BE SIGNED, DATED AND SEALED.
 ONE SET MISSING.
 THIS JOB REQUIRES THREE SETS FOR THRES-
 -HOLD JOB.
 FAC 61G15-23.002
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2004-05-21 Cont ID  
Sent By csiegber Date 2004-06-18 Time 16:28 Rev Time 1.00
Received By dpalmer Date 2004-05-21 Time 11:22 Sent To  
Notes
2004-05-21 00:00:00REVISED CHILLER RISER DIAGRAM.

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2004-04-03 Cont ID  
Sent By csiegber Date 2004-05-18 Time 15:14 Rev Time 0.50
Received By btrobaug Date 2004-04-03 Time 11:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2004-03-08 Cont ID  
Sent By dpalmer Date 2004-03-08 Time 16:35 Rev Time 1.50
Received By dpalmer Date 2004-03-08 Time 16:35 Sent To FIRE
Notes
2004-03-08 00:00:00FIRE ALARM OK IN MOVR INTO FRON ENTRANCE
 COLUMN. OK PER MIKE C.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2004-03-08 Cont ID  
Sent By dpalmer Date 2004-03-08 Time 12:10 Rev Time 0.50
Received By dpalmer Date 2004-03-08 Time 11:39 Sent To  
Notes
2004-03-08 00:00:00******** UNSAT ***************
  
 1)NOTE: PLEASE SEE SHEET E3.4 THIS SHEET
 IS REQUIRED TO BE SIGNED BY THE ENGINEER
 OF RECORD. THIS HAS BEEN NOTED AND
 REQUESTED ON PREVIOUS REVIEWS.
 FS 471.025
 PLEASE PROVIDE ONE NEW SET AS ONE SET
 IS BEING RETAINED FOR ABOVE COMMENT FOR
 FILE.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW, IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2004-02-24 Cont ID  
Sent By csiegber Date 2004-03-02 Time 09:50 Rev Time 0.50
Received By dpalmer Date 2004-02-24 Time 16:03 Sent To FIRE
Notes
2004-02-24 00:00:00************** UNSAT **********
  
 1)NOTE: PLEASE HAVE ALL SHEETS SIGNED
 DATED AND SEALED. PLEASE SEE SOME
 SHEETS ARE INITIALED.
 FS 471.025
  
 2)NOTE: PLEASE SUBMIT LIGHTNING PROTECT-
 -ION SYSTEM UNDER SEPARATE ELECTRICAL
 PERMIT APPLICATION.
  
 INSTALLATION TO ALSO MEET NFPA-780.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-08-18 Cont ID  
Sent By csiegber Date 2004-02-20 Time 16:07 Rev Time 1.00
Received By dpalmer Date 2003-08-18 Time 10:44 Sent To  
Notes
2003-08-18 00:00:00STAMPED ELECTRICAL SHEETS.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-08-12 Cont ID  
Sent By dpalmer Date 2003-08-12 Time 06:29 Rev Time 1.00
Received By dpalmer Date 2003-08-12 Time 14:21 Sent To  
Notes
2003-08-12 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE E,3.3,3.4,6.1 ARE
 MISSING BEING SIGNED, DATED AND SEALED
 BY ENGINEER.
 CALLED JEFF SOBLE, WAITING FOR NEW
 SHEETS BEFORE STAMPING ELECTRICAL.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-07-17 Cont ID  
Sent By dpalmer Date 2003-07-17 Time 11:37 Rev Time 1.00
Received By dpalmer Date 2003-07-17 Time 11:37 Sent To  
Notes
2003-07-17 00:00:00************* UNSAT ****************
  
 1)NOTE: RESPOND LETTER DATED 6/26/03
 FROM BRICE BLDG, MENTIONS TO SEE SHEET
 AC-8 AND 9 FOR CONTROL VOLTAGE BUT NO
 RESPONSE OR CORRECTIONS WERE MADE FOR
 MEANS OF DISC OF WIRING COMING INTO BLDG
 FROM ANOTHER SERVICE. 225-31,230-2 ETC
 SIGNAGE 230-2
  
 2)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FOR ELECTRICAL FIXTURES MISSING.
 PLEASE SEE THAT THIS WILL HAVE A DIRECT
 AFFECT ON ELECTRICAL PLANS AND WILL
 NEED TO BE REVISED FOR ELECTRICAL AND
 FIRE REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-05-19 Cont ID  
Sent By dpalmer Date 2003-05-19 Time 19:20 Rev Time 1.00
Received By dpalmer Date 2003-05-19 Time 19:20 Sent To  
Notes
2003-05-19 00:00:00************** UNSAT **********
  
 1)NOTE: PLEASE CLARIFY CONTROL VOLTAGE
 OF CHILLER PLANT CONTROL WIRING?
 PLEASE CLARIFY MEANS OF DISC IN MAIN
 ELECTRICAL ROOM FOR ALL CONTROL WIRING
 FEEDING ANOTHER BLDG FROM A SEPARATE
 SERVICE? 225-31
 ALL DISC SHALL HAVE SIGNAGE AS REQ`D PER
 NEC. 230-2
  
 2)NOTE: PLEASE SEE 384-16 FOR MAIN
 REQ`D ON SECONDARY SIDE OF TRANSFORMER
 FOR PANEL "4LA".
  
 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 230-42,215-3 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-15 Cont ID  
Sent By dpalmer Date 2003-04-15 Time 14:15 Rev Time 1.50
Received By dpalmer Date 2003-04-15 Time 13:56 Sent To  
Notes
2003-04-15 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT COMPLETED PLANS
 FOR REVIEW. PLEASE SEE BLANK PANEL
 SCHEDULES, NO CIRCUITING, LOAD CALCS
 ETC ETC.
  
 PLEASE NOTE, PLANS MAY HAVE ADDITIONAL
 COMMENTS ONCE COMPLETED AND SUBMITTED
 FOR REVIEW.
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2003-07-23 Cont ID  
Sent By mamini Date 2003-07-23 Time 11:46 Rev Time 0.50
Received By mamini Date 2003-07-23 Time 11:45 Sent To  
Notes
2003-07-23 00:00:00PASSED:
 1. SEE PERMIT # 03071236 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2003-07-03 Cont ID  
Sent By shernand Date 2003-07-09 Time 16:55 Rev Time 1.00
Received By mamini Date 2003-07-03 Time 09:22 Sent To  
Notes
2003-07-03 00:00:00FAILED:
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND SITE WORK IS REQUIRED.
 PLEASE SUBMIT TWO SETS CIVIL PLANS ONLY
 (SIGNED & SEALED).PLANS MUST BE
 APPROVED BY PUBLIC UTILITIES PRIOR TO
 ISSUANCE OF UNDERGROUND UTILITIES AND
 SITE WORK PERMIT BY BUILDING DEPARTMENT.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2003-05-15 Cont ID  
Sent By mamini Date 2003-05-15 Time 08:53 Rev Time 1.00
Received By mamini Date 2003-05-15 Time 08:47 Sent To  
Notes
2003-05-15 00:00:00FAILED:
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND SITE WORK WILL BE REQUIRED
 2. A SEPARATE BACKFLOW PREVENTER IN
 2 1/2" WATER SERVICE TO THE BUILDING IS
 REQUIRED.
 3. IS THERE ANY EXSITING DDCV ON 8" FIRE
 LINE ON SITE?, IF SO PLEASE SHOW.
 4. BROKEN/ DAMAGED SIDEWALK, CURB &
 GUTTERS AT ALL SIDE OF PROPERTY MUST BE
 RESTORED/REPALCED.
 5. CIVIL /SITE PLANS MUST BE APPROVED
 BY PUBLIC UTILITIES PRIOR TO ISSUANCE OF
 CIVIL/SITE PERMIT BY BUILDING DEPARTMENT
 6. ANY CONSTRUCTION IN DIXIE HWY WILL
 REQUIRE A SEPARATE PERMIT FROM FDOT.
 7. PLEASE PROVIDE EASEMENT FOR FOOTING,
 AREAL ENCROACHMENT INTO THE PUBLIC ROW
 TO PUBLIC UTILITIES, ATT: VINCE NOEL,
 659-8040 EXT. 8440
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-04-16 Cont ID  
Sent By mamini Date 2003-04-16 Time 13:57 Rev Time 1.00
Received By mamini Date 2003-04-16 Time 13:57 Sent To  
Notes
2003-04-16 00:00:00FAILED :
 1. PLEASE PROVIDE CIVIL/SITE PLAN FOR
 OUR REVIEW AND APPROVAL.PLAN SHOULD
 INCLUDE PERVIOUS AND IMPERVIOUS CALC.
 FOR THE ENTIRE SITE DUE TO THE PROPOSED
 STRUCTURE, THE DRAINAGE FOR THE SITE,
 POLLUTION PREVENTION PLANS AND
 CONNECTION TO THE SERVICES.
 2. PLEASE SUBMIT TWO SETS OF CIVIL PLANS
 TO PUBLIC UTILITIES FOR THIER REVIEW AND
 APPROVAL, 659-8040.
 3. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND SITE WORK WILL BE REQUIRED
  
 IF ANY QUESTION PLEASE CONTACT 659-8086
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2004-03-09 Cont ID  
Sent By nmccray Date 2004-03-09 Time 11:13 Rev Time 0.00
Received By nmccray Date 2004-03-09 Time 11:13 Sent To  
Notes
2004-03-09 00:00:00REVISION DATED FOR 2-18-04 & 3-08-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-08-19 Cont ID  
Sent By dpalmer Date 2004-03-08 Time 16:36 Rev Time 0.00
Received By nmccray Date 2003-08-19 Time 15:17 Sent To  
Notes
2003-08-19 00:00:00***********PROVISO**********************
 A LETTER FROM JEFF SOBLE INDICATING THAT
 COMMENTS DATED JUNE 13, 2003,(NOTES 1
 THRU 3) BE ADDRESSED. PER ASST. FIRE
 MARSHAL MIKE CARSILLO.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-06-13 Cont ID  
Sent By hpiskura Date 2003-08-14 Time 10:00 Rev Time 0.00
Received By mcarsill Date 2003-06-13 Time 09:05 Sent To  
Notes
2003-06-13 00:00:001) COULD NOT LOCATE INTERIOR FINISH
 CLASSIFCATION FOR WALLS AND CEILINGS.
  
 2) NOTE ON DOOR SCHEDULE STILL INDICATES
 UNDERCUTTING FIRE RATED DOORS. PLEASE
 EXPLAIN.
  
 3) WHY IS THE EXHAUST DUCT FOR HOOD 1
 AND HOOD 2 NOT ENCLOSED IN A RATED
 SHAFT.
  
 4) WHERE IS THE FDC. PLEASE SHOW ITS
 RELATIONSHIP TO A FIRE HYDRANT WITHIN
 150 FEET.
  
 5) NO EXIT SIGNS SHOWN ON ELECTRICAL
 DRAWINGS NEAR LECTURE HALL DOORS
 WITHIN PARTITIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-04-11 Cont ID  
Sent By hpiskura Date 2003-05-28 Time 13:00 Rev Time 0.00
Received By mcarsill Date 2003-04-11 Time 09:12 Sent To  
Notes
2003-04-11 00:00:001) BUILDING LOCATED IN CITY FIRE LIMITS.
 CERTAIN RESTRICTIONS APPLY.
  
 2) A KNOX-BOX IS REQUIRED.
  
 3) PANIC HARDWARE REQUIRED ON EXIT DOORS
 WITH OCCUPANT LOADS OF 100 OR MORE
 PERSONS.
  
 4) TACTILE SIGNAGE REQUIRED AT STAIRWELL
 DOORS.
  
 5) ALL SHAFTWAYS THAT PERSONS CAN FALL
 INTO MUST BE MARKED "SHAFTWAY" IN
 RED LETTERS.
  
 6) PLEASE PROVIDE FLAMESPREAD CRITERIA
 ON MOVABLE PARTITIONS IN LECTURE HALLS.
  
 7) PLEASE SHOW EXISTING AND OR NEW FIRE
 HYDRANTS ON SITE PLAN.
  
 8) PLEASE EXPLAIN GATES IN STAIRTOWERS.
  
 9) PLEASE PROVIDE FLAMSPREAD DETAILS
 ON MOVABLE PARTITIONS FOR CLASSROOMS
 1&2.
  
 10) WHAT WILL THE UNFINISHED EXPANSION
 AREA BE USED FOR.
  
 11) BUILDING ADDRESS REQUIRED ON
 PROPER ELEVATION. MINIMUM 6" NUMBERS
 REQUIRED.
  
 12) PLEASE INDICATE HANDICAPPED SEATING.
  
 13) ELEVATOR REQUIRED TO BE STRETCHER
 ACCESSIBLE.
  
 14) PLEASE EXPLAIN UNOCCUPIED SPACE
 ON ROOF PLAN.
  
 15) PLEASE EXPLAIN 8" HIGH CONCRETE STEP
  
 16) PLEASE PROVIDE FLAMSPREAD DETAILS
 ON ACOUSTICAL PANELS.
  
 17) NO HANDRAILS SHOWN AT 8" STEP.
  
 18) PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR HANDRAILS.
  
 19) EXIT SIGNS NOT SHOWN AT MOVEABLE
 PARTION WALL LOCATIONS.
  
 20) NO EXIT MARKINGS IN CLASSROOMS.
  
 21) NO EXIT MARKINGS IN DRUG INFORMATION
 CENTER.
  
 22) DUCT SMOKE DETECTORS ARE TO ACTIVATE
 THE FIRE ALARM SYSTEM.

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2004-06-25 Cont ID  
Sent By csiegber Date 2004-06-25 Time 12:26 Rev Time 0.00
Received By csiegber Date 2004-06-25 Time 12:26 Sent To E
Notes
2004-06-25 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2004-06-18 Cont ID  
Sent By csiegber Date 2004-06-18 Time 16:28 Rev Time 0.00
Received By csiegber Date 2004-06-18 Time 16:28 Sent To E
Notes
2004-06-18 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2004-05-18 Cont ID  
Sent By csiegber Date 2004-05-18 Time 15:14 Rev Time 0.00
Received By csiegber Date 2004-05-18 Time 15:14 Sent To E
Notes
2004-05-18 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2004-03-02 Cont ID  
Sent By csiegber Date 2004-03-02 Time 09:50 Rev Time 0.00
Received By csiegber Date 2004-03-02 Time 09:50 Sent To E
Notes
2004-03-02 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 12:21 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 12:21 Sent To B
Notes
2004-02-25 00:00:00TO SH/HP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2004-02-20 Cont ID  
Sent By csiegber Date 2004-02-20 Time 16:07 Rev Time 0.00
Received By csiegber Date 2004-02-20 Time 16:07 Sent To E
Notes
2004-02-20 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2004-02-12 Cont ID  
Sent By csiegber Date 2004-02-12 Time 10:18 Rev Time 0.00
Received By csiegber Date 2004-02-12 Time 10:18 Sent To B
Notes
2004-02-12 00:00:00TO SH DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-01-27 Time 14:53 Rev Time 0.00
Received By csiegber Date 2004-01-27 Time 14:53 Sent To B
Notes
2004-01-27 00:00:00TO HP DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2003-10-21 Cont ID  
Sent By csiegber Date 2003-10-21 Time 14:46 Rev Time 0.00
Received By csiegber Date 2003-10-21 Time 14:46 Sent To B
Notes
2003-10-21 00:00:00TO HP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-10-09 Time 10:07 Rev Time 0.00
Received By csiegber Date 2003-10-09 Time 10:06 Sent To B
Notes
2003-10-09 00:00:00TO HP DESK/SCAFFOLD & SHORING

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2003-10-02 Cont ID  
Sent By csiegber Date 2003-10-02 Time 11:33 Rev Time 0.00
Received By csiegber Date 2003-10-02 Time 11:33 Sent To B
Notes
2003-10-02 00:00:00TO HP DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2003-09-12 Cont ID  
Sent By csiegber Date 2003-09-12 Time 11:50 Rev Time 0.00
Received By csiegber Date 2003-09-12 Time 11:50 Sent To B
Notes
2003-09-12 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2003-09-03 Cont ID  
Sent By csiegber Date 2003-09-03 Time 16:42 Rev Time 0.00
Received By csiegber Date 2003-09-03 Time 16:41 Sent To B
Notes
2003-09-03 00:00:00TO HP DESK
 TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-08-05 Cont ID  
Sent By alange Date 2003-08-05 Time 13:10 Rev Time 0.00
Received By alange Date 2003-08-05 Time 13:09 Sent To B
Notes
2003-08-05 00:00:00TO H.P. DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-07-31 Cont ID  
Sent By alange Date 2003-07-31 Time 13:15 Rev Time 0.00
Received By alange Date 2003-07-31 Time 13:14 Sent To  
Notes
2003-07-31 00:00:00TO COMM BD #59

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-07-09 Cont ID  
Sent By shernand Date 2003-07-09 Time 16:55 Rev Time 0.00
Received By shernand Date 2003-07-09 Time 16:55 Sent To ENG
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-06-27 Cont ID  
Sent By shernand Date 2003-06-27 Time 11:35 Rev Time 0.00
Received By shernand Date 2003-06-27 Time 11:35 Sent To  
Notes
2003-06-27 00:00:00COMM BOARD #38

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-05-19 Cont ID  
Sent By shernand Date 2003-05-19 Time 14:04 Rev Time 0.00
Received By shernand Date 2003-05-19 Time 14:04 Sent To B
Notes
2003-05-19 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-15 Cont ID  
Sent By shernand Date 2003-05-15 Time 16:53 Rev Time 0.00
Received By shernand Date 2003-05-15 Time 16:53 Sent To  
Notes
2003-05-15 00:00:00ADDED TO BOX #37, SUBMITTAL OF 3 SOIL
 TESTING PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-15 Cont ID  
Sent By shernand Date 2003-05-14 Time 16:52 Rev Time 0.00
Received By shernand Date 2003-05-14 Time 16:52 Sent To  
Notes
2003-05-14 00:00:00COMM BOARD #37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-07 Cont ID  
Sent By shernand Date 2003-04-07 Time 09:44 Rev Time 0.00
Received By shernand Date 2003-04-07 Time 09:44 Sent To  
Notes
2003-04-07 00:00:00COMM BOARD #13

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-07-08 Cont ID  
Sent By pkrauss Date 2003-07-08 Time 06:54 Rev Time 0.50
Received By pkrauss Date 2003-07-08 Time 06:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-05-23 Cont ID  
Sent By pkrauss Date 2003-05-23 Time 14:13 Rev Time 1.20
Received By pkrauss Date 2003-05-23 Time 14:12 Sent To  
Notes
2003-05-23 00:00:00DENIED:
  
 THE FOLLOWING ITEMS NOT ADDRESSED FROM
 PREVIOUS REVIEW DATED 4-30-03.
 ITEM #
 2.PLAN SHEET AC-2 STORAGE RM 117,
 EXHAUST TERMINATES OVER THE DOOR.2001
 FBC(M) 401.5.2 EXHAUST SHALL NOT BE
 DIRECTED ONTO WALKWAYS.FRESH AIR
 INTAKE SHALL BE A MINIMUM OF 10 FT FROM
 EXHAUST AS PER 2001 FBC(M) 401.5.1.
 ITEM #
 3. PLAN SHEET AC-7 WAS REVISED TO SHOW
 RESTROOM EXHAUST RISER IN A RATED SHAFT.
 DUCTWORK FROM HOOD THAT ALSO PENTRATES
 THROUGH MORE THAN ONE FLOOR SHALL ALSO
 BE IN FIRE RATED SHAFT. 2001 FBC(M)
 607.4. SEE ALSO 510.6.1.
 ITEM #
 5.PLEASE REFER TO 2001 FBC(M) 510 FOR
 HAZARDOUS EXHAUST SYSTEMS CONCERNING THE
 THE FUME HOODS EXHAUST AND MAKE-UP AIR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-05-03 Cont ID  
Sent By pkrauss Date 2003-04-30 Time 15:56 Rev Time 3.00
Received By pkrauss Date 2003-04-30 Time 15:28 Sent To  
Notes
2003-04-30 00:00:00DENIED:
  
 1.AS PER F.S. 471.025, ALL DRAWINGS,
 SPECIFICATION AND PLANS SHALL BE HAVE
 AN IMPRESSION-TYPE SEAL AND BE SIGNED,
 SEALED, AND DATED.
  
 2.PLAN SHEET AC-2 STORAGE RM 117,
 EXHAUST TERMINATES OVER THE DOOR.2001
 FBC(M) 401.5.2 EXHAUST SHALL NOT BE
 DIRECTED ONTO WALKWAYS.FRESH AIR
 INTAKE SHALL BE A MINIMUM OF 10 FT FROM
 EXHAUST AS PER 2001 FBC(M) 401.5.1.
  
 3.PLAN SHEET AC-7 DETAIL FOR THE
 RESTROOM EXHAUST RISER, AS PER 2001
 FBC(M) 607.4, DUCTS EXTENDING THROUGH
 MORE THAN ONE FLOOR SHALL BE PROTECTED
 BY A SHAFT ENCLOSURE.BUILDINGS LESS
 THAN 4 STORIES IN HEIGHT, ENCLOSURE
 SHALL HAVE A FIRE RESISTANCE RATING OF
 NOT LESS THAN 1 HR.BUILDINGS GREATER
 THAN 4 STORIES IN HEIGHT, ENCLOSURE
 SHALL BE NOT LESS THAN 2 HR RATING.
 THE ABOVE SHALL BE FOR ALL DUCTS
 PENETRATING MORE THAN ONE FLOOR.
  
 4.PLEASE CLARIFY MAKE-UP AIR FOR THE
 FUME HOODS.AIR BALANCE SCHEDULE
 INDICATES "N/A".MANUFACTURERS SPECS
 IN THE ACCESSORIES SHOWS A AUXILLARY
 AIR PLENUM KIT.WILL THIS BE UTILIZED?
  
 5.PLEASE REFER TO 2001 FBC(M) 510 FOR
 HAZARDOUS EXHAUST SYSTEMS CONCERNING THE
 FUME HOODS EXHAUST AND MAKE-UP AIR.
  
 6.PLEASE PROVIDE ENERGY CALCS.
  
 7.NO COMBUSTIBLES ABOVE THE CEILING IN
 THE RETURN AIR PLENUM. 2001 FBC(M)
 602.2.1.
  
 8.SEE PLUMBING COMMENT #10 ON
 CONDENSATE.
  
 9.SEE FIRE DEPARMENT COMMENT #22 DUCT
 SMOKE DETECTORS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-07-28 Cont ID  
Sent By kstevens Date 2003-07-28 Time 13:41 Rev Time 1.00
Received By kstevens Date 2003-07-28 Time 13:41 Sent To  
Notes
2003-07-28 00:00:00PASSED/PROVISO
  
 SHT P6.1 VALVE REQUIRED FOR HOT DOWN-
 FEED LINE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-06-11 Cont ID  
Sent By kstevens Date 2003-06-11 Time 11:26 Rev Time 2.50
Received By kstevens Date 2003-06-11 Time 11:26 Sent To  
Notes
2003-06-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHTS P2.1 & P5.1 CLEANOUTS REQUIRED
 BY SECTION 708.3.3 REQUIRED. PLEASE SHOW
 ON FLAT LAYOUT AND SANT. RISER DIAGRAM.
 "CLEANOUTS SHALL BE INSTALLED AT EACH
 CHANGE OF DIRECTION OF THE BIILDING
 DRAIN OR HORIZONTAL WASTE OF SOIL LINES
 GREATER THAN 45 DEGREES. WHERE MORE THAN
 ONE CHANGEOF DIRECTION OCCURS IN A RUN
 OF PIPING, ONLY ONE CLEANOUT SHALL BE
 REQUIRED FOR EACH 40 FEET OF DEVELOPED
 LENGTH OF THE DRAINAGE PIPING."
 2) SHT P5.2 A RELIEF VENT IS REQUIRED AS
 THE CONDENSATE DRAIN EXITS THE BLDG. IN
 CASE OF BACKUP IN THE STORM SYSTEM,
 (CATCH BASIN), THE RELIEF VENT SHALL
 KEEP THE STORM WATER FROM BACKING UP IN-
 TO THE BLDG.
 3) SHT P6.1 FULL OPEN VALVES REQUIRED AT
 THE BASE OF EACH RISER. SEC 606.1(3).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-14 Cont ID  
Sent By kstevens Date 2003-04-14 Time 16:34 Rev Time 5.00
Received By kstevens Date 2003-04-14 Time 16:33 Sent To  
Notes
2003-04-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHTS A2.1.1, A2.2.1, A2.3.1, & A2.4.1
 PLEASE PROVIDE CALCULATIONS FOR MINIMUM
 FACILITIES PER BLDG CODE TABLE 1003.1 &
 PLUMBING CODE TABLE 403.1.
 2) SHTS A2.2.1 & A4.2.1, STUDENT LOUNGE
 ROOM #206 SHALL COMPLY WITH SEC. 11-4.24
 DETAIL #1, PLEASE SHOW COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 3) PLEASE SUBMIT RISER DIAGRAMS FOR DWV,
 STORM, ACID WASTE, AND WATER. PLEASE
 SHOW ALL PIPE SIZES, TYPE OF MATERIAL.
 SHOW DFU'S AS THEY ACCUMULATE IN SANIT-
 ARY SYSTEM. SHOW SQUARE FEET AS THEY
 ACCUMULATE IN THE STORM SYSTEM. SHOW
 WATER HAMMER ARRESTORS REQUIRED IN SEC.
 604.9 LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT AT THE TOP OF THE
 DROPS IN THE CEILING. PDI-WH 201, AND
 MANUF. INSTALLATION INSTRUCTIONS.
 4) SHT A2.2.1 PLEASE PROVIDE MANUF. INFO
 FOR DISTILLED WATER SYSTEM.
 5) SHTS A2.3.1, A2.4.1, A4.2.1 DETAIL
 #5, SINKS SHALL COMPLY WITH 11-4.24 AND
 ALL SUBSECTIONS. PLEASE SHOW ON DETAIL
 AND SUBMIT DETAIL FOR FACULITY LOUNGE ON
 4TH FLOOR.
 6) SHT A4.1.1 DETAIL #1, PLEASE SHOW
 CLEAR FLOOR SPACE FOR ALL HDCP FIXTURES.
 SHOW 5' TURNING CIRCLE FOR TOILET ROOMS.
 7) SHT A4.1.1 HDCP DETAILS, W/C TO BE
 18" OFF WALL TO CENTER OF FIXTURE. SHOW
 ON DETAIL. - NOTE #12 DRAIN TO BE INSUL-
 ATED ALSO.
 8) SHT P0.1 WATER HEATER DETAIL #4,
 THERMAL EXPANSION CONTROL REQUIRED. SEC.
 607.3.2- DIELECTRIC UNIONS NOT APPROV-
 ED FOR USE IN WATER SYSTEM. PLEASE DE-
 LETE REFERENCE.
 9) SHT PO.1 DILUTION TANK FOR ACID WASTE
 SYSTEM SHALL BE SIZED BY RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE. (561) 837-4074
 WASTE ORD: 2938-96
 10) SHT P0.1 DETAIL #1, CONDENSATE TRAP,
 VENT LINE WITH PERFORATED CAP SHALL NOT
 TERMINATE IN A/C ROOM IF ROOM IS USED AS
 A PLENUM. VENT THRU ROOF REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 2 Status P Date 2003-08-20 Cont ID  
Sent By mmclean Date 2003-08-20 Time 15:45 Rev Time 0.25
Received By mmclean Date   Time   Sent To  
Notes
2003-08-20 00:00:008/20/03 PASS PER ANGELLA JONES-VANN MM

Review Stop Z ZONING
Rev No 1 Status F Date 2003-05-23 Cont ID  
Sent By sgraham Date 2003-04-15 Time 15:19 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-05-23 00:00:00NEED CITY COMMISSION APPROVAL
2003-04-15 00:00:00DENIED,SAFE SITE TRIANGLE ISSUES
 CALL RANDALL GRANBERRY AT 659-3031