Plan Review Details - Permit 03040476
Plan Review Stops For Permit 03040476
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-04-23 Cont ID  
Sent By hpiskura Date 2003-04-23 Time 16:19 Rev Time 0.00
Received By hpiskura Date 2003-04-23 Time 16:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-21 Cont ID  
Sent By dpalmer Date 2003-05-21 Time 16:15 Rev Time 0.25
Received By dpalmer Date 2003-05-21 Time 16:15 Sent To  
Notes
2003-05-21 00:00:00NOTES REDLINED

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-15 Cont ID  
Sent By dpalmer Date 2003-04-15 Time 06:36 Rev Time 0.50
Received By dpalmer Date 2003-04-15 Time 06:36 Sent To  
Notes
2003-04-15 00:00:00************** UNSAT ********
  
 1)NOTE: PLEASE SEE 250-24/ AN EQUIPMENT
 GROUNDING CONDUCTOR IS SHOWN ON RISER
 AND FROM METER TO MAIN BRK PANEL.
 AN EQUIPMENT GRND IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 2)NOTE: PLEASE SEE 600-5 FOR MISSING
 REQ`D SIGN CIRCUIT.
  
 3)NOTE: PLEASE SEE 210-62 FOR MISSING
 SHOW WINDOW RECEPTS REQ`D. SHOWN ON
 LOAD CALCS.
 4)NOTE: PLEASE SEE 700-12E FOR CIRCUIT-
 -ING OF EXT/EM LTS. ON SAME BRANCH
 CIRCUIT AS GEN LT IN SAME AREAS.
  
 5)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 AND LOAD CALCULATIONS. WATER HEATER
 SHOWN AS 3500W ON PANEL AND 3000W ON
 LOAD CALCS?
  
 6)NOTE; PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215-3/230-42 ETC.
  
 7)NOTE: PLEASE SHOW/CLARIFY HOW FEED
 IS GETTING FROM METER TO PANEL. AS PER
 LOCAL AMENDMENTS, NO MORE THAN 8' OF
 UNPROTECTED CONDUCTORS INSIDETHE BLDG.
 230-70
 A MAIN DISC/OCP MAY BE REQ`D OUTSIDE
 OR PANEL LOCATION MAY NEED TO BE MOVED?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-05-28 Cont ID  
Sent By nmccray Date 2003-05-28 Time 10:28 Rev Time 0.00
Received By nmccray Date 2003-05-28 Time 10:28 Sent To  
Notes
2003-05-28 00:00:00PASSED ON 4-25-03 BY MIKE CARSILLO
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-04-25 Cont ID  
Sent By mcarsill Date 2003-04-25 Time 12:02 Rev Time 0.00
Received By mcarsill Date 2003-04-25 Time 12:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-21 Cont ID  
Sent By shernand Date 2003-05-21 Time 15:04 Rev Time 0.00
Received By shernand Date 2003-05-21 Time 15:04 Sent To  
Notes
2003-05-21 00:00:00COMM BOARD #31, RESTAMPED PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-04 Cont ID  
Sent By shernand Date 2003-04-04 Time 16:15 Rev Time 0.00
Received By shernand Date 2003-04-04 Time 15:56 Sent To  
Notes
2003-04-04 00:00:00COMM BOARD #36

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-04-28 Cont ID  
Sent By pkrauss Date 2003-04-28 Time 14:08 Rev Time 0.35
Received By pkrauss Date 2003-04-28 Time 13:28 Sent To  
Notes
2003-04-28 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
  
 PLEASE PROVIDE PLANS, AND OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2001
 FBC(M) TABLE 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-05-29 Cont ID  
Sent By kstevens Date 2003-05-29 Time 17:11 Rev Time 0.50
Received By kstevens Date 2003-05-29 Time 17:11 Sent To  
Notes
2003-05-29 00:00:00PASSED PROVISO - 607.3.2 THERMAL EXPAN-
 SION REQUIRED - 909.1 ONLY FIXTURES FROM
 THE BATHROOM GROUP SHALL BE WET VENTED -
 WATER COOLER SHALL BE ARI-1010 COMPLIANT
 410.1

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-22 Cont ID  
Sent By kstevens Date 2003-04-22 Time 10:48 Rev Time 0.50
Received By kstevens Date 2003-04-22 Time 10:48 Sent To  
Notes
2003-04-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) A DRINKING FOUNTAIN IS REQUIRED AND
 A SERVICE SINK IS REQUIRED PER TABLE
 403.1. (ALSO SEE SECTION 410.1)
 2) PLUMBING RISER SHOWS THREE SINKS, BUT
 FLOOR PLAN SHOW TWO SINKS. PLEASE
 CLAIRFY.
 3) PLEASE SUBMIT A WATER RISER DIAGRAM.
 4) RPZ BACKFLOW REQUIRED ON WATER SERV.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692