| 2003-04-09 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION MAKE NECESSARY CHANGES TO |
| | PLANS AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE PLANS SUBMITTED INCLUDE INTERIOR |
| | WIRING,BUT NONE IS DESCRIBED ON THE |
| | APPLICATION,PLEASE CLARIFY THE SCOPE OF |
| | WORK AND SUBMIT PLANS INDICATING SAME. |
| | |
| | 2} THE LAUNDRY CIRCUIT LISTED ON THE |
| | PANEL SCHEDULE AND THE LOAD CALC MUST |
| | COMPLY WITH 220-16(B). |
| | |
| | 3} THERE ARE 3 SMALL APPLIANCE CIRCUITS |
| | IN THE CALCS BUT ONLY 2 ON PANEL SCHED. |
| | PLEASE CORRELATE. |
| | |
| | 4} THE RISER DIAGRAM SHOWS THE 200 AMP |
| | PANEL AS BEING REMOVED? SHOW NEW PANEL |
| | LOCATION. |
| | |
| | 5} THE 3000 VA WATER HEATER WOULD APPEAR |
| | TO HAVE AN INCORRECT OCP @3O AMPS, |
| | PLEASE CLARIFY. |
| | |
| | 6} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 7} PLEASE LIST THE REQ'D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG,AND SHALL SERVE |
| | ONLY THE BATH,SCHEDULE SHOWS 1 CKT @ 30 |
| | AMPS AND KITCHEN ON SAME CIRCUIT. |
| | |
| | 8} THE DRYER CIRCUIT MUST COMPLY WITH |
| | 220-18.(5000 VA) |
| | |
| | 9} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE PER 210-12. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | 561/659-8096 EXT.8392 |