Plan Review Details - Permit 03040313
| Plan Review Stops For Permit 03040313 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-08-05 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-08-05 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-08-05 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2003-08-05 00:00:00 | REVISION DATED 7-18-03 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2003-04-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-07-28 |
Time |
07:49 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-04-21 |
Time |
15:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-07-21 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-21 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-21 |
Time |
10:54 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-04-03 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-03 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-03 |
Time |
15:10 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-07-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-07-28 |
Time |
07:39 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2003-07-28 |
Time |
07:31 |
Sent To |
FIRE |
|
| Notes |
| 2003-07-28 00:00:00 | PROVISO: | | | | | | 1. PROVIDE MANUFACTURERS INSTALLATION | | | INSTRUCTIONS ON THE 3M FASTWRAP+ ON THE | | | JOBSITE AT THE TIME OF INSPECTION. | | | PLEASE NOTE WELDS TO BE INSPECTED | | | PRIOR TO COVERING WITH WRAP. | | | | | | 2. GREASE DUCT SHALL HAVE A MINIMUM | | | SLOPE OF 1/4" PER FOOT TOWARD THE HOOD. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2003-04-09 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-21 |
Time |
10:55 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2003-04-09 |
Time |
14:26 |
Sent To |
FIRE |
|
| Notes |
| 2003-04-09 00:00:00 | PROVISO: | | | | | | EXHAUST OUTLETS SHALL BE LOCATED NOT | | | LESS THAN 10 FT HORIZONTALLY FROM PARTS | | | OF THE SAME OR CONTIGUOUSBUILDINGS, | | | ADJACENT PROPERTY LINES & AIR INTAKES. | | | 2001 FBC(M) 506.3.14.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719 |
|
|
|