Plan Review Details - Permit 03040236
Plan Review Stops For Permit 03040236
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-17 Cont ID  
Sent By btrobaug Date 2003-04-17 Time 07:02 Rev Time 1.00
Received By sthyng Date 2003-04-17 Time 17:13 Sent To  
Notes
2003-04-17 00:00:00**********CORRECTIONS************
  
 1.)PROVIDE PRODUCT APPROVALS, TWO
 COPIES, FOR THE EXTERIOR DOOR,
 GLASS BLOCK, WINDOWS AND HURRICANE
 PROTECTION.
  
 2.)PROVIDE A WALL SECTION DETAIL OF
 THE WALL YOU ARE BUILDING.
  
 3.)INDICATE ON THE PLAN THAT YOU ARE
 ENCLOSING AN EXISTING PORCH.GIVE
 STRUCTURAL INFORMATION ABOUT THE PORCH;
 COLUMN SUPPORTS, MATERIALS, ATTACHMENTS,
 ROOF.THIS CAN BE DONE AS AN EXISTING
 WALL SECTION.
  
 4.)WHAT IS AT THE LOCATION OF THE
 2868 DOOR ON THE EXISTING HOUSE WALL
 (DINING TO NEW ENCLOSED AREA).IS THIS
 A WALL TO BE CUT OPEN (NEED DETAIL)?
 IS THE DOOR EXISTING (SHOW ON PLAN)?
  
 5.)GIVE AREA CALCULATIONS ON THE PLAN-
 SQUARE FOOTAGE OF EXISTING HOUSE, NEW
 A/C AREA, NEW TOTAL.
  
 6.)SHOW ALL WINDOWS, INCLUDING GLASS
 BLOCK AREA, ON THE FLOOR PLAN.GIVE
 DIMENSIONS.
  
 7.)BEFORE A PERMIT TO CONSTRUCT MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8.)A NOTICE OF COMMENCEMENT MUST BE
 RECORDED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED.
  
 9.)GIVE A WALL SECTION OF THE INTERIOR
 PARTITION WALL.ALSO SHOW REINFORCEMENT
 AROUND THE WINDOWS AND DOORS.
  
 10.)ENERGY CALCS REQUIRED PER FBC
 13-101.2.2.
  
 11.)ADDITIONAL FEES REQUIRED.THIS
 MUST BE PAID BEFORE A PERMIT CAN BE
 ISSUED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-17 Cont ID  
Sent By pkrauss Date 2003-04-16 Time 12:42 Rev Time 0.50
Received By btrobaug Date 2003-04-17 Time 06:43 Sent To B
Notes
2003-04-17 00:00:00DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 AN ELECTRICAL PERMIT WAS APPLIED FOR
 AND NO DRAWINGS FOR SAME WAS SUBMITTED
 PER ARTICLE 104.1.3 FBC.ALSO NOTE ALL
 INSTALLATIONS MUST COMPLY WITH THE
 APPLICABLE ARTICLES OF NFPA-70.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-10 Cont ID  
Sent By shernand Date 2003-04-10 Time 13:19 Rev Time 0.00
Received By shernand Date 2003-04-10 Time 13:19 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-03 Time 16:14 Rev Time 0.00
Received By shernand Date 2003-04-03 Time 16:14 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-04-16 Cont ID  
Sent By kstevens Date 2003-04-15 Time 09:12 Rev Time 0.10
Received By pkrauss Date 2003-04-16 Time 12:38 Sent To E
Notes
2003-04-16 00:00:00NO MECHANICAL INFORMATION SUBMITTED -
 ADDING NEW DOWNSTAIRS BATHROOM - EXHAUST
 FAN REQUIRED AS PER 2001 FBC(M) TABLE
 403.3.
  
 PLAN REVIEW BY:
 PATTY KRAUSS, (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-04-15 Cont ID  
Sent By shernand Date 2003-04-10 Time 13:19 Rev Time 0.25
Received By kstevens Date 2003-04-15 Time 09:12 Sent To M
Notes
2003-04-15 00:00:00NO PLUMBING PLANS SUBMITTED

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***