| Plan Review Stops For Permit 03040100 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-05-30 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-24 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-05-30 |
Time |
12:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-04-22 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-04-22 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-04-21 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2003-04-22 00:00:00 | STAIR #3 IS SHOWN EXITING INTO THE | | | LOADING ZONE ON SHEET C-1.THE DOOR | | | MUST NOT BE BLOCKED.SEE FBC 1001.1.3 | | | AND 1010.1.1. | | | | | | DOORS SHOWN AS 107, 118 AND 109 WILL NOT | | | COMPLY WITH FBC 1003.2.3 FOR 32" CLEAR. | | | | | | THE PARKING GARAGE AS SHOWN MUST COMPLY | | | WITH THE VENTILATION REQUIREMENTS OF | | | FBC 411.4. | | | | | | SHEETS C-1 AND A4 APPEAR TO INDICATE A | | | STEP AT THE ENTRANCES OF THE BUILDING | | | THAT MAY NOT COMPLY WITH HANDICAP | | | ACCESSIBILITY.PLEASE CLARIFY.SEE | | | FBC 11- 4.1.3. | | | | | | THE ENERGY CODE MUST BE SIGNED BY THE | | | DESIGN PROFESSIONALS.FBC 13-103.1.1.1. | | | | | | BEFORE A PERMIT TO CONSTRUCT MAY BE | | | ISSUED IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, THE PERMIT PLANS STAMPED | | | BY THAT OFFICE AND A COPY OF THE PAID | | | RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION.CALL 561-233-5025 FOR | | | MORE INFORMATION. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2004-03-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2004-03-09 |
Time |
08:37 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2004-03-09 |
Time |
08:11 |
Sent To |
|
|
| Notes |
| 2004-03-09 00:00:00 | | | | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | ANY CHANGES TO THESE PLANS ARE REQUIRED | | | TO BE MADE BY THE ENGINEER OF RECORD, | | | THESE HAND DRAWN UNSIGNED COPIES ARE | | | UNACCEPTABLE FOR PUBLIC RECORD | | | RETENTION AND ARE ILLEGAL UNDER 471 OF | | | THE FLORIDA STATUTES. HAVE THE DESIGN | | | PROFESSIONAL MAKE ALL CHANGES. | | | ALSO NOTE THAT ADDITIONS TO THESE PLANS | | | ARE TO BE SUBMITTED AS A REVISION TO THE | | | ORIGINAL SCOPE OF WORK, NOT A | | | SUBMITTAL. HAVE PLANS REDRAWN AND | | | RESUBMIT FOR REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2003-12-02 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-03-08 |
Time |
11:42 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2003-12-02 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2003-12-02 00:00:00 | | | | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | NOTE: PLEASE NOTE THAT ALL PLANS | | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | | ING A TITLE BLOCK, MUST BE SIGNED, | | | DATED AND SEALED BY THE ARCH/ENGINEER OF | | | RECORD. PER FS/FAC 481.221 & 471.025 | | | ALSO HAND DRAWN CHANGES TO THE PLANS ARE | | | NOT ACCEPTABLE THE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-05-22 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-01 |
Time |
16:33 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2003-05-22 |
Time |
06:51 |
Sent To |
|
|
| Notes |
| 2003-05-22 00:00:00 | | | | REDLINED THE ELCTRICAL ROOM #117 ON "E-1 | | | " FOR 110-26(1,2 &3)./WRT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-04-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-04-11 |
Time |
05:52 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2003-04-11 |
Time |
05:52 |
Sent To |
|
|
| Notes |
| 2003-04-11 00:00:00 | ********** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE E-2, EXIT SIGNS SEEM | | | TO BE MISSING ON SECOND FLOOR. | | | PER LIFE SAFETY/NFPA-72 ETC. 700 NEC | | | | | | 2)NOTE: PLEASE CLARIFY PROVISIONS TO | | | MEET 110-26A-3. GUTTER MAY NOT PROTRUDE | | | 6" OUT FROM METER AND FUTURE DISC/? | | | | | | 3)NOTE: PLEASE CLARFIY/VERIFY ELECTRICAL | | | SERVICE LAYOUT. SHOWN DIFFERENTLY ON | | | E-1. PLEASE SEE CLEARENCE REQ`D. 110-26 | | | | | | 4)NOTE: PLEASE SEE E-2, SHOWS AHU-6 AS | | | 2-P60A AND PANEL SCHEDULE SHOWS AS 2P50A | | | PLEASE CORRELATE. | | | PLEASE ALSO SEE AMPERAGES FIGURED FOR | | | OCP OF AHU. PLEASE RE-FIGURE FOR 208V | | | AND SIZE OCP ACCORD TO 424-3B | | | PLEASE ADJUST AWG/CONDUIT. | | | | | | PLEASE SEE ANY OTHER COMMENTS FROM | | | OTHER REVIEWERS THAT MAY AFFECT ELEC. | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2003-06-06 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2003-06-06 |
Time |
16:16 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2003-06-06 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2003-06-06 00:00:00 | PASSED; | | | 1. SEE PERMIT # 03060494 FOR UNDERGROUND | | | UTILITIES AND SITE WORK. | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2003-05-21 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2003-05-21 |
Time |
13:24 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2003-05-21 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2003-05-21 00:00:00 | FAILED: | | | 1. PLEASE NOTE THAT A SEPARATE PERMIT | | | APPLICATIN AND FEES FOR UNDERGROUND | | | UTILITIES AND SITE WORK IS REQUIRED. | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2003-04-14 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2003-04-14 |
Time |
15:32 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2003-04-14 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2003-04-14 00:00:00 | FAILED: | | | 1. A RPZ BACKFLOW PREVENTER WILL NEED TO | | | TO BE INSTALLED, IF NOT ALREADY IN PLACE | | | AT THE WATER METER ON PRIVATE PROPERTY. | | | ALL BACKFLOWS SHALL BE COMPLETELY HIDDEN | | | FROM VIEW WITH SHRUBS PRIOR TO | | | ACTIVATION. | | | 2. A CLEAN OUT WILL NEED TO BE INSTALLED | | | IN SANITARY SEWER LATERAL, ON THE | | | PROPERTY, AT THE BACK OF THE SIDEWALK,IF | | | NOT ALREADY INSTALLED. | | | 3. A SEPARATE IRRIGATION METER IS | | | SUGGESTED TO SAVE ON THE MONTHLY WATER | | | BILL, A PROPER BACKFLOW NEED TO BE | | | INSTALLED ON THIS LINE. | | | 4. PLEASE NOTE THAT A SEPARATE PERMITT | | | APPLICATION AND FEES FOR UNDERGROUND | | | UTILITIES AND SITE WORK WILL BE REQUIRED | | | | | | IF ANY QUESTION PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-05-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-05-30 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-05-30 |
Time |
09:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-04-04 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-04-04 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-04-04 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2003-04-04 00:00:00 | 1) HOW IS EXITING ACCOMPLISHED FROM | | | THE FIRST LEVEL OF THE GARAGE WITH THE | | | GATES,FENCES AND WALLS BEING PRESENT. | | | | | | 2) THE PROPOSED BUILDING MAY BE | | | LOCATED IN THE CITY FIRE LIMITS. | | | PLEASE SEE APPENDIX F OF THE LOCAL | | | AMENDMENTS OF THE FLORIDA BUILDING | | | CODE. | | | | | | 3) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. | | | | | | 4) PLEASE INDICATE EXIT DISCHARGE | | | WIDTH AND HEIGHTS FROM ANY ADJACENT | | | ONSTRUCTIONS,EQUIPMENT,OR PROPERTIES. | | | | | | 5) TACTILE SIGNAGE REQUIRED AT STAIRWELL | | | DOORS. | | | | | | 6) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENTS FOR ALL HANDRAILS | | | AND OR GAURDRAILS. | | | | | | 7) A MINIMUM OF AT LEAST TWO HOUR | | | FIRE SEPARATION IS REQUIRED BETWEEN THE | | | PARKING AREA AND OTHER PORTIONS OF | | | THE BUILDING. | | | | | | 8) HOW DOES EXITING OCCUR FROM STAIR | | | # 3 WHEN IT EMPTIES INTO A PARKING | | | AREA WITH GATES AND OTHER OBSTRUCTIONS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2004-03-25 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-03-25 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-03-25 |
Time |
14:49 |
Sent To |
M |
|
| Notes |
| 2004-03-25 00:00:00 | TO PK BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2004-03-08 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-03-08 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-03-08 |
Time |
11:42 |
Sent To |
E |
|
| Notes |
| 2004-03-08 00:00:00 | TO BT DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-12-01 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-01 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-12-01 |
Time |
16:33 |
Sent To |
E |
|
| Notes |
| 2003-12-01 00:00:00 | TO BT DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-09-24 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-24 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-24 |
Time |
16:22 |
Sent To |
B |
|
| Notes |
| 2003-09-24 00:00:00 | TO HP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-05-20 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-20 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-20 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2003-05-20 00:00:00 | COMM BOARD #56 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-04-04 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2003-05-06 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-03 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2003-04-03 00:00:00 | COMM BOARD #62 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2004-04-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-04-07 |
Time |
11:37 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2004-04-07 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2004-04-07 00:00:00 | PROVISO: | | | PLEASE NOTE, PLAN SHEET M-1, DUCT | | | PENETRATING THE WALL BETWEEN THE STORAGE | | | AND CONF #2 SHALL COMPLY WITH 2001 | | | FBC(M) 607.1.2 #3 ITEMS 1 THROUGH 4, | | | OTHERWISE FIRE DAMPERS WILL BE REQUIRED | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2004-04-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-04-02 |
Time |
06:44 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2004-04-02 |
Time |
06:38 |
Sent To |
|
|
| Notes |
| 2004-04-02 00:00:00 | DENIED: | | | PLANS SUBMITTED ARE NOT BY THE ENGINEER | | | OF RECORD (A. CHANE).PLEASE PROVIDE A | | | SIGNED, SEALED & DATED LETTER FROM MR. | | | CHANE RESCINDING FROM THIS PROJECT. | | | | | | PROVISO: | | | PLEASE NOTE PLAN SHEET M-1, DUCT | | | PENETRATING THE WALL BETWEEN THE STORAGE | | | AND CONF #2 SHALL COMPLY WITH 2001 | | | FBC(M) 607.1.3 #3 ITEMS 1 THROUGH 4 | | | OTHERWISE FIRE DAMPERS WILL BE REQUIRED. | | | | | | PLANS ARE OTHERWISE CODE COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-06-16 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-03-25 |
Time |
14:49 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2003-06-16 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2003-06-16 00:00:00 | MECHANICAL PERMIT 03040105 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-04-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-04-24 |
Time |
10:16 |
Rev Time |
2.15 |
| Received By |
pkrauss |
Date |
2003-04-24 |
Time |
10:05 |
Sent To |
Z |
|
| Notes |
| 2003-04-24 00:00:00 | DENIED: | | | PLEASE CLARIFY THE FOLLOWING INFORMATION | | | | | | 1.PLAN SHEET A-1 INDICATES ROOM #104 | | | AS A RATED ROOM.PLEASE NOTE 14" X 22" | | | SUPPLY DUCT RUNS THROUGH ROOM, NO FIRE | | | DAMPERS ARE INDICATED. | | | | | | 2.PLAN DOES NOT INDICATE A SEPARATION | | | BETWEEN PARKING GARAGE AND OFFICE SPACE. | | | AS PER 2001 FBC TABLE 704 A 1 HOUR | | | SEPARATION IS REQUIRED. | | | | | | 3.PLAN SHEET M-3 CLOSET #203, 14" X | | | 14" DUCT PENETRATES RATED PARTITION, | | | DAMPER NOT INDICATED.PLEASE CLARIFY. | | | | | | 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | OR SMOKE DETECTOR SHALL ACTIVATE A | | | VISIBLE & AUDIBLE SUPERVISORY SIGNAL | | | AT A CONSTANTLY ATTENDED LOCATION. | | | | | | 5.SEE BUILDING PLAN REVIEW COMMENTS | | | ON VENTILATION FOR PARKING GARAGE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-06-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-06-14 |
Time |
13:24 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-06-14 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2003-06-14 00:00:00 | PASSED/PROVISO | | | | | | | | | CLEANOUTS REQUIRED PER SECTIONS 708.3.1 | | | AND 708.3.3 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-04-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-04-19 |
Time |
07:36 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2003-04-19 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2003-04-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A-1 RM 102A SINK SHALL COMPLY | | | WITH SECTION 11-4.24 AND ALL ALL SUB- | | | SECTIONS. PLEASE PROVIDE DETAILS. | | | 2) SHT A-1 SHOW 5' TURNING RADIUS IN ALL | | | TOILET ROOMS. 11-4.22.3 | | | 3) SHT A2 TOILET ROOM #221 TO BE ACCESS- | | | IBLE PER 11-4.1.3(11). PLEASE SHOW DE- | | | TAILS PER 11-4.23 AND ALL SUBSECTIONS. | | | 4) SHT M-2 WATER ISOMETRIC, | | | A) SHUT OFF VALVE REQUIRED ON WATER | | | HEATER. SEC 606.1(7). | | | B) SHUT OFF VALVES REQUIRED FOR RE- | | | CIRCULATING PUMP. SEC 606.2(3) | | | C) THERMAL EXPANSION CONTROL REQUIRED | | | PER SECTION 607.3.2 | | | D) A WATER HAMMER ARRESTOR SHALL BE IN- | | | STALLED WHERE QUICK CLOSING VALVES ARE | | | UTILIZED. (WASH MACHINES - DISH WASHERS | | | AND ICE MAKERS) FBC-2001 SEC 604.9 | | | LOCATED NEAR THE FIXTURE IN AN "EFFECT- | | | IVE RANGE" PER PDI-WH 201 AND MANUF. IN- | | | STALLATION INSTRUCTIONS. NOT AT THE TOP | | | OF THE DROPS IN THE CEILING. | | | 5) AN RPZ BACKFLOW IS REQUIRED ON WATER | | | SERVICE. | | | 6) SHT M-1 CONDENSATE LINE SHALL HAVE A | | | RELIEF VENT, (OVERFLOW), AS IT EXITS THE | | | BLDG. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2003-05-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-04-24 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
I |
|
| Notes |
|
|