Plan Review Details - Permit 03040100
Plan Review Stops For Permit 03040100
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-05-30 Cont ID  
Sent By csiegber Date 2003-09-24 Time 16:22 Rev Time 0.00
Received By hpiskura Date 2003-05-30 Time 12:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-22 Cont ID  
Sent By hpiskura Date 2003-04-22 Time 09:42 Rev Time 0.00
Received By hpiskura Date 2003-04-21 Time 14:46 Sent To  
Notes
2003-04-22 00:00:00STAIR #3 IS SHOWN EXITING INTO THE
 LOADING ZONE ON SHEET C-1.THE DOOR
 MUST NOT BE BLOCKED.SEE FBC 1001.1.3
 AND 1010.1.1.
  
 DOORS SHOWN AS 107, 118 AND 109 WILL NOT
 COMPLY WITH FBC 1003.2.3 FOR 32" CLEAR.
  
 THE PARKING GARAGE AS SHOWN MUST COMPLY
 WITH THE VENTILATION REQUIREMENTS OF
 FBC 411.4.
  
 SHEETS C-1 AND A4 APPEAR TO INDICATE A
 STEP AT THE ENTRANCES OF THE BUILDING
 THAT MAY NOT COMPLY WITH HANDICAP
 ACCESSIBILITY.PLEASE CLARIFY.SEE
 FBC 11- 4.1.3.
  
 THE ENERGY CODE MUST BE SIGNED BY THE
 DESIGN PROFESSIONALS.FBC 13-103.1.1.1.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-03-09 Cont ID  
Sent By btrobaug Date 2004-03-09 Time 08:37 Rev Time 0.75
Received By btrobaug Date 2004-03-09 Time 08:11 Sent To  
Notes
2004-03-09 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 ANY CHANGES TO THESE PLANS ARE REQUIRED
 TO BE MADE BY THE ENGINEER OF RECORD,
 THESE HAND DRAWN UNSIGNED COPIES ARE
 UNACCEPTABLE FOR PUBLIC RECORD
 RETENTION AND ARE ILLEGAL UNDER 471 OF
 THE FLORIDA STATUTES. HAVE THE DESIGN
 PROFESSIONAL MAKE ALL CHANGES.
 ALSO NOTE THAT ADDITIONS TO THESE PLANS
 ARE TO BE SUBMITTED AS A REVISION TO THE
 ORIGINAL SCOPE OF WORK, NOT A
 SUBMITTAL. HAVE PLANS REDRAWN AND
 RESUBMIT FOR REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-12-02 Cont ID  
Sent By csiegber Date 2004-03-08 Time 11:42 Rev Time 0.75
Received By btrobaug Date 2003-12-02 Time 12:24 Sent To  
Notes
2003-12-02 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOTE: PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
 ALSO HAND DRAWN CHANGES TO THE PLANS ARE
 NOT ACCEPTABLE THE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-22 Cont ID  
Sent By csiegber Date 2003-12-01 Time 16:33 Rev Time 0.75
Received By btrobaug Date 2003-05-22 Time 06:51 Sent To  
Notes
2003-05-22 00:00:00 
 REDLINED THE ELCTRICAL ROOM #117 ON "E-1
 " FOR 110-26(1,2 &3)./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-11 Cont ID  
Sent By dpalmer Date 2003-04-11 Time 05:52 Rev Time 1.00
Received By dpalmer Date 2003-04-11 Time 05:52 Sent To  
Notes
2003-04-11 00:00:00********** UNSAT **************
  
 1)NOTE: PLEASE SEE E-2, EXIT SIGNS SEEM
 TO BE MISSING ON SECOND FLOOR.
 PER LIFE SAFETY/NFPA-72 ETC. 700 NEC
  
 2)NOTE: PLEASE CLARIFY PROVISIONS TO
 MEET 110-26A-3. GUTTER MAY NOT PROTRUDE
 6" OUT FROM METER AND FUTURE DISC/?
  
 3)NOTE: PLEASE CLARFIY/VERIFY ELECTRICAL
 SERVICE LAYOUT. SHOWN DIFFERENTLY ON
 E-1. PLEASE SEE CLEARENCE REQ`D. 110-26
  
 4)NOTE: PLEASE SEE E-2, SHOWS AHU-6 AS
 2-P60A AND PANEL SCHEDULE SHOWS AS 2P50A
 PLEASE CORRELATE.
 PLEASE ALSO SEE AMPERAGES FIGURED FOR
 OCP OF AHU. PLEASE RE-FIGURE FOR 208V
 AND SIZE OCP ACCORD TO 424-3B
 PLEASE ADJUST AWG/CONDUIT.
  
 PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER REVIEWERS THAT MAY AFFECT ELEC.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2003-06-06 Cont ID  
Sent By mamini Date 2003-06-06 Time 16:16 Rev Time 1.00
Received By mamini Date 2003-06-06 Time 16:16 Sent To  
Notes
2003-06-06 00:00:00PASSED;
 1. SEE PERMIT # 03060494 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2003-05-21 Cont ID  
Sent By mamini Date 2003-05-21 Time 13:24 Rev Time 1.00
Received By mamini Date 2003-05-21 Time 13:24 Sent To  
Notes
2003-05-21 00:00:00FAILED:
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATIN AND FEES FOR UNDERGROUND
 UTILITIES AND SITE WORK IS REQUIRED.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-04-14 Cont ID  
Sent By mamini Date 2003-04-14 Time 15:32 Rev Time 1.00
Received By mamini Date 2003-04-14 Time 15:32 Sent To  
Notes
2003-04-14 00:00:00FAILED:
 1. A RPZ BACKFLOW PREVENTER WILL NEED TO
 TO BE INSTALLED, IF NOT ALREADY IN PLACE
 AT THE WATER METER ON PRIVATE PROPERTY.
 ALL BACKFLOWS SHALL BE COMPLETELY HIDDEN
 FROM VIEW WITH SHRUBS PRIOR TO
 ACTIVATION.
 2. A CLEAN OUT WILL NEED TO BE INSTALLED
 IN SANITARY SEWER LATERAL, ON THE
 PROPERTY, AT THE BACK OF THE SIDEWALK,IF
 NOT ALREADY INSTALLED.
 3. A SEPARATE IRRIGATION METER IS
 SUGGESTED TO SAVE ON THE MONTHLY WATER
 BILL, A PROPER BACKFLOW NEED TO BE
 INSTALLED ON THIS LINE.
 4. PLEASE NOTE THAT A SEPARATE PERMITT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND SITE WORK WILL BE REQUIRED
  
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-05-30 Cont ID  
Sent By mcarsill Date 2003-05-30 Time 09:45 Rev Time 0.00
Received By mcarsill Date 2003-05-30 Time 09:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-04-04 Cont ID  
Sent By mcarsill Date 2003-04-04 Time 16:22 Rev Time 0.00
Received By mcarsill Date 2003-04-04 Time 16:22 Sent To  
Notes
2003-04-04 00:00:001) HOW IS EXITING ACCOMPLISHED FROM
 THE FIRST LEVEL OF THE GARAGE WITH THE
 GATES,FENCES AND WALLS BEING PRESENT.
  
 2) THE PROPOSED BUILDING MAY BE
 LOCATED IN THE CITY FIRE LIMITS.
 PLEASE SEE APPENDIX F OF THE LOCAL
 AMENDMENTS OF THE FLORIDA BUILDING
 CODE.
  
 3) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS.
  
 4) PLEASE INDICATE EXIT DISCHARGE
 WIDTH AND HEIGHTS FROM ANY ADJACENT
 ONSTRUCTIONS,EQUIPMENT,OR PROPERTIES.
  
 5) TACTILE SIGNAGE REQUIRED AT STAIRWELL
 DOORS.
  
 6) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS
 AND OR GAURDRAILS.
  
 7) A MINIMUM OF AT LEAST TWO HOUR
 FIRE SEPARATION IS REQUIRED BETWEEN THE
 PARKING AREA AND OTHER PORTIONS OF
 THE BUILDING.
  
 8) HOW DOES EXITING OCCUR FROM STAIR
 # 3 WHEN IT EMPTIES INTO A PARKING
 AREA WITH GATES AND OTHER OBSTRUCTIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-03-25 Cont ID  
Sent By csiegber Date 2004-03-25 Time 14:49 Rev Time 0.00
Received By csiegber Date 2004-03-25 Time 14:49 Sent To M
Notes
2004-03-25 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-03-08 Cont ID  
Sent By csiegber Date 2004-03-08 Time 11:42 Rev Time 0.00
Received By csiegber Date 2004-03-08 Time 11:42 Sent To E
Notes
2004-03-08 00:00:00TO BT DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-01 Cont ID  
Sent By csiegber Date 2003-12-01 Time 16:33 Rev Time 0.00
Received By csiegber Date 2003-12-01 Time 16:33 Sent To E
Notes
2003-12-01 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-24 Cont ID  
Sent By csiegber Date 2003-09-24 Time 16:22 Rev Time 0.00
Received By csiegber Date 2003-09-24 Time 16:22 Sent To B
Notes
2003-09-24 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-20 Cont ID  
Sent By shernand Date 2003-05-20 Time 16:03 Rev Time 0.00
Received By shernand Date 2003-05-20 Time 16:03 Sent To  
Notes
2003-05-20 00:00:00COMM BOARD #56

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-04 Cont ID  
Sent By sgraham Date 2003-05-06 Time 16:19 Rev Time 0.00
Received By shernand Date 2003-04-03 Time 10:31 Sent To  
Notes
2003-04-03 00:00:00COMM BOARD #62

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-04-07 Cont ID  
Sent By pkrauss Date 2004-04-07 Time 11:37 Rev Time 0.20
Received By pkrauss Date 2004-04-07 Time 11:37 Sent To  
Notes
2004-04-07 00:00:00PROVISO:
 PLEASE NOTE, PLAN SHEET M-1, DUCT
 PENETRATING THE WALL BETWEEN THE STORAGE
 AND CONF #2 SHALL COMPLY WITH 2001
 FBC(M) 607.1.2 #3 ITEMS 1 THROUGH 4,
 OTHERWISE FIRE DAMPERS WILL BE REQUIRED
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-04-02 Cont ID  
Sent By pkrauss Date 2004-04-02 Time 06:44 Rev Time 0.40
Received By pkrauss Date 2004-04-02 Time 06:38 Sent To  
Notes
2004-04-02 00:00:00DENIED:
 PLANS SUBMITTED ARE NOT BY THE ENGINEER
 OF RECORD (A. CHANE).PLEASE PROVIDE A
 SIGNED, SEALED & DATED LETTER FROM MR.
 CHANE RESCINDING FROM THIS PROJECT.
  
 PROVISO:
 PLEASE NOTE PLAN SHEET M-1, DUCT
 PENETRATING THE WALL BETWEEN THE STORAGE
 AND CONF #2 SHALL COMPLY WITH 2001
 FBC(M) 607.1.3 #3 ITEMS 1 THROUGH 4
 OTHERWISE FIRE DAMPERS WILL BE REQUIRED.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-06-16 Cont ID  
Sent By csiegber Date 2004-03-25 Time 14:49 Rev Time 0.35
Received By pkrauss Date 2003-06-16 Time 08:54 Sent To  
Notes
2003-06-16 00:00:00MECHANICAL PERMIT 03040105

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-04-24 Cont ID  
Sent By pkrauss Date 2003-04-24 Time 10:16 Rev Time 2.15
Received By pkrauss Date 2003-04-24 Time 10:05 Sent To Z
Notes
2003-04-24 00:00:00DENIED:
 PLEASE CLARIFY THE FOLLOWING INFORMATION
  
 1.PLAN SHEET A-1 INDICATES ROOM #104
 AS A RATED ROOM.PLEASE NOTE 14" X 22"
 SUPPLY DUCT RUNS THROUGH ROOM, NO FIRE
 DAMPERS ARE INDICATED.
  
 2.PLAN DOES NOT INDICATE A SEPARATION
 BETWEEN PARKING GARAGE AND OFFICE SPACE.
 AS PER 2001 FBC TABLE 704 A 1 HOUR
 SEPARATION IS REQUIRED.
  
 3.PLAN SHEET M-3 CLOSET #203, 14" X
 14" DUCT PENETRATES RATED PARTITION,
 DAMPER NOT INDICATED.PLEASE CLARIFY.
  
 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 OR SMOKE DETECTOR SHALL ACTIVATE A
 VISIBLE & AUDIBLE SUPERVISORY SIGNAL
 AT A CONSTANTLY ATTENDED LOCATION.
  
 5.SEE BUILDING PLAN REVIEW COMMENTS
 ON VENTILATION FOR PARKING GARAGE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-06-14 Cont ID  
Sent By kstevens Date 2003-06-14 Time 13:24 Rev Time 0.50
Received By kstevens Date 2003-06-14 Time 13:24 Sent To  
Notes
2003-06-14 00:00:00PASSED/PROVISO
  
  
 CLEANOUTS REQUIRED PER SECTIONS 708.3.1
 AND 708.3.3

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-19 Cont ID  
Sent By kstevens Date 2003-04-19 Time 07:36 Rev Time 1.25
Received By kstevens Date 2003-04-19 Time 07:36 Sent To  
Notes
2003-04-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 RM 102A SINK SHALL COMPLY
 WITH SECTION 11-4.24 AND ALL ALL SUB-
 SECTIONS. PLEASE PROVIDE DETAILS.
 2) SHT A-1 SHOW 5' TURNING RADIUS IN ALL
 TOILET ROOMS. 11-4.22.3
 3) SHT A2 TOILET ROOM #221 TO BE ACCESS-
 IBLE PER 11-4.1.3(11). PLEASE SHOW DE-
 TAILS PER 11-4.23 AND ALL SUBSECTIONS.
 4) SHT M-2 WATER ISOMETRIC,
 A) SHUT OFF VALVE REQUIRED ON WATER
 HEATER. SEC 606.1(7).
 B) SHUT OFF VALVES REQUIRED FOR RE-
 CIRCULATING PUMP. SEC 606.2(3)
 C) THERMAL EXPANSION CONTROL REQUIRED
 PER SECTION 607.3.2
 D) A WATER HAMMER ARRESTOR SHALL BE IN-
 STALLED WHERE QUICK CLOSING VALVES ARE
 UTILIZED. (WASH MACHINES - DISH WASHERS
 AND ICE MAKERS) FBC-2001 SEC 604.9
 LOCATED NEAR THE FIXTURE IN AN "EFFECT-
 IVE RANGE" PER PDI-WH 201 AND MANUF. IN-
 STALLATION INSTRUCTIONS. NOT AT THE TOP
 OF THE DROPS IN THE CEILING.
 5) AN RPZ BACKFLOW IS REQUIRED ON WATER
 SERVICE.
 6) SHT M-1 CONDENSATE LINE SHALL HAVE A
 RELIEF VENT, (OVERFLOW), AS IT EXITS THE
 BLDG.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-05-06 Cont ID  
Sent By pkrauss Date 2003-04-24 Time 13:46 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***