Plan Review Details - Permit 03040099
Plan Review Stops For Permit 03040099
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-21 Cont ID  
Sent By hpiskura Date 2003-07-21 Time 09:55 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-07-21 00:00:00REVISIONS DATED 7/7/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-04-16 Cont ID  
Sent By shernand Date 2003-04-02 Time 13:10 Rev Time 0.00
Received By hpiskura Date 2003-04-16 Time 11:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-09-16 Cont ID  
Sent By dpalmer Date 2003-09-16 Time 12:03 Rev Time 0.50
Received By dpalmer Date 2003-09-16 Time 12:03 Sent To  
Notes
2003-09-16 00:00:00**** NOTES ****
 CHANGED FROM EM LTS TO LAY-IN 2X4 W/BATT
 BACK UP.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-21 Cont ID  
Sent By nmccray Date 2003-09-15 Time 15:16 Rev Time 0.33
Received By dpalmer Date 2003-07-21 Time 13:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-04-10 Cont ID  
Sent By dpalmer Date 2003-04-10 Time 11:18 Rev Time 0.50
Received By dpalmer Date 2003-04-10 Time 11:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-09-15 Cont ID  
Sent By nmccray Date 2003-09-15 Time 15:16 Rev Time 0.00
Received By nmccray Date 2003-09-15 Time 15:16 Sent To E
Notes
2003-09-15 00:00:00REVISION LETTER DATED 9-11-03

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-07-23 Cont ID  
Sent By nmccray Date 2003-07-23 Time 10:53 Rev Time 0.00
Received By nmccray Date 2003-07-23 Time 10:53 Sent To  
Notes
2003-07-23 00:00:00REVISION DATED 7-09-03

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-06-05 Cont ID  
Sent By nmccray Date 2003-06-05 Time 14:53 Rev Time 0.00
Received By nmccray Date 2003-06-05 Time 14:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-04-25 Cont ID  
Sent By shernand Date 2003-04-16 Time 10:29 Rev Time 0.00
Received By mcarsill Date 2003-04-25 Time 10:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shernand Date 2003-07-15 Time 09:57 Sent To  
Notes
2003-07-15 00:00:00COMM BOARD #18

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-06-25 Cont ID  
Sent By shernand Date 2003-06-25 Time 14:37 Rev Time 0.00
Received By shernand Date 2003-06-25 Time 14:37 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-08 Cont ID  
Sent By shernand Date 2003-05-08 Time 14:48 Rev Time 0.00
Received By shernand Date 2003-05-08 Time 14:48 Sent To  
Notes
2003-05-08 00:00:00COMM BOARD #47

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-16 Cont ID  
Sent By shernand Date 2003-04-16 Time 10:29 Rev Time 0.00
Received By shernand Date 2003-04-16 Time 10:25 Sent To FIRE
Notes
2003-04-16 00:00:00REV. FIRE ALARM DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-02 Cont ID  
Sent By shernand Date 2003-04-02 Time 12:29 Rev Time 0.00
Received By shernand Date 2003-04-02 Time 12:28 Sent To B
Notes
2003-04-02 00:00:00COMM BOARD #26

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-07-16 Cont ID  
Sent By pkrauss Date 2003-07-16 Time 12:56 Rev Time 0.40
Received By pkrauss Date 2003-07-16 Time 12:07 Sent To  
Notes
2003-07-16 00:00:00PROVISO:
  
 DUCT SMOKE DETECTOR TO BE INSTALLED IN
 THE SUPPLY AIR DUCT NOT THE RETURN AS
 INDICATED ON PLAN M-1 AS PER 2001 FBC(M)
 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-04-16 Cont ID  
Sent By pkrauss Date 2003-04-16 Time 15:47 Rev Time 0.45
Received By pkrauss Date 2003-04-16 Time 15:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2003-09-15 Cont ID  
Sent By kstevens Date 2003-09-15 Time 17:33 Rev Time 0.50
Received By kstevens Date 2003-09-15 Time 17:33 Sent To  
Notes
2003-09-15 00:00:00REVISION OK - LETTER FROM ENGINEER -
 DELETE FLOOR DRAINS IN TOILET ROOMS -
 CHANGE VENTS AT SHAMPOO SINKS TO AAV.

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-07-21 Cont ID  
Sent By kstevens Date 2003-07-21 Time 17:57 Rev Time 0.75
Received By kstevens Date 2003-07-21 Time 17:57 Sent To  
Notes
2003-07-21 00:00:00REVISION OK - CHANGED FLOOR PLAN, WATER
 RISER DIAGRAM - SANT. RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-06-30 Cont ID  
Sent By kstevens Date 2003-06-30 Time 11:07 Rev Time 1.00
Received By kstevens Date 2003-06-30 Time 11:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-05-29 Cont ID  
Sent By shernand Date 2003-06-25 Time 14:37 Rev Time 0.50
Received By kstevens Date 2003-05-29 Time 10:38 Sent To  
Notes
2003-05-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 A) FROM PREVIOUS REVIEW:
 1) SHT F1 EQUIPMENT SCHEDULE, #27 NOT
 LOCATED ON PLANS. PLEASE CLAIRFY.
 2) PLEASE SUBMIT DETAILS FOR TOILET ROOM
 PER SECTION 11-4.22, 11-4.16 & 11-4.19
 AND ALL SUBSECTIONS.
 3) PLEASE SUBMIT DETAIL FOR DRINKING
 FOUNTAIN PER SECTION 11-4.15 AND ALL
 SUBSECTIONS. ALSO PROVISIONS SHALL BE
 MADE FOR THOSE WHO HAVE DIFFICULTY BEND-
 ING OR STOOPING. SECTION 11-4.1.3(10)(A)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-12 Cont ID  
Sent By kstevens Date 2003-04-12 Time 14:29 Rev Time 1.00
Received By kstevens Date 2003-04-12 Time 14:29 Sent To  
Notes
2003-04-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT F1 EQUIPMENT SCHEDULE, #'S 27 &
 48 NOT FOUND. PLEASE CLAIRFY
 2) SHT F1 EQUIPMENT SCHENULE #28 IN
 TOILET ROOM. PLEASE CLAIRFY
 3) SHT P-1 PLUMBING PLAN NOTES: #10 VENT
 OFFSET, EVERY DRY VENT SHALL RISE VERTI-
 CALLY TO A MINIMUM OF 6" ABOVE TH FLOOD
 LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED
 FIXTURE BEING VENTED. SECTION 905.4 &
 905.5
 4) SHT P-1 OCCUPANCY CALCULATIONS SHALL
 BE FIGURED BY FBC-2001 BLDG TABLE 1003.1
 & PLUMBING TABLE 403.1, NOT SFBC. PLEASE
 CHANGE REFERENCE.
 5) RPZ BACKFLOW REQUIRED ON WATER SERV-
 ICE.
 6) SHT P-2 WATER HEATER DETAIL, DIELECT-
 RIC UNIONS NOT APPROVED FOR WATER.
 PLEASE REMOVE REFERENCE.
 7) PLEASE SUBMIT DETAILS FOR TOILET ROOM
 PER SECTION 11-4.22, 11-4.16, & 11-4.19
 AND ALL SUBSECTIONS.
 8) PLEASE SUBMIT DETAIL FOR DRINKING
 FOUNTAIN PER SECTION 11-4.15 AND ALL
 SUBSECTIONS. ALSO PROVISIONS SHALL BE
 MADE FOR THOSE WHO HAVE DIFFICULTY BEND-
 ING OR STOOPING. SECTION 11-4.1.3(10)(A)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692