Plan Review Details - Permit 03040098
Plan Review Stops For Permit 03040098
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-08-25 Cont ID  
Sent By dpalmer Date 2003-09-22 Time 12:32 Rev Time 0.00
Received By hpiskura Date 2003-08-25 Time 14:28 Sent To  
Notes
2003-08-25 00:00:00SEE ATTACHED PROVISO

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-12 Cont ID  
Sent By hpiskura Date 2003-07-12 Time 12:05 Rev Time 0.00
Received By hpiskura Date 2003-07-12 Time 11:18 Sent To  
Notes
2003-07-12 00:00:00!!PROVISO!!
  
 STH PLANS SHEET A-8.PLEASE PROVIDE A
 FIRE DESIGN NUMBER FOR THE BEAM/GIRDER
 PROTECTION AS SHOWN IN DETAILS 12 AND
 13 BEFORE CONSTRUCTION.SEE FBC 701.5.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-18 Cont ID  
Sent By hpiskura Date 2003-06-18 Time 09:55 Rev Time 0.00
Received By hpiskura Date 2003-06-18 Time 07:42 Sent To  
Notes
2003-06-18 00:00:00SHEET S1 OF THE STH PLANS.SECTIONS 1 &
 2, PLEASE NOTE THE EMBEDMENT DEPTH
 OF THE #4 REBAR AND THE 5/8" EXPANSION
 BOLTS.
  
 WILL THERE BE OTHER REINFORCEMENT STEEL
 THEN #4 X 2' @ 12" OC?
  
 SHOW THE METHOD OF TWO HOUR FIRE RATED
 PROTECTION FOR THE NEW STEEL BEAMS.
 SEE FBC T-600, TYPE I CONSTRUCTION,
 BEAMS, GIRDERS AND ARCHES.
  
 WORK SHOP + PLANS.
  
 PROVIDE SPECIFIC DETAILS FOR THE STAIRS
 HANDRAILS.SEE FBC 1007.5 AND 1608.2.
  
 THE STAIRS AS SHOWN COMMUNICATING WITH
 MORE THAN TWO FLOORS DO NOT COMPLY WITH
 FBC 705.2.2.PLEASE REVISE AS
 NECESSARY.
  
 PLEASE SHOW OR NOTE A SPECIFIC METHOD
 FOR ATTACHMENT OF THE WOOD VENEER AS
 SHOWNIN SECTION 1/A3.1.
  
 THE PLANS ARE REQUIRED TO BE SIGNED,
 SEALED AND DATED BY A FLORIDA
 REGISTERED ARCHITECT OR ENGINEER.
  
 PLEASE DESCRIBE FURTHER AND/OR INCLUDE
 PLANS FOR THE ELEVATOR MODIFICATIONS
 CALLED OUT ON THE PERMIT APPLICATION.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-09-22 Cont ID  
Sent By dpalmer Date 2003-09-22 Time 12:20 Rev Time 1.50
Received By dpalmer Date 2003-09-22 Time 12:20 Sent To B
Notes
2003-09-22 00:00:00**** REDLINED NOTES****
 AHU OCP, MAX 150%
 WROTE CA# ON E-SHEEST ONLY.
 ARCH SHEETS DO NOT CONTAIN ANY LICENSE
 # INFORMATION PER 61G1-16.004/ FS 481

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2003-09-18 Cont ID  
Sent By csiegber Date 2003-09-19 Time 11:31 Rev Time 0.25
Received By dpalmer Date 2003-09-18 Time 12:16 Sent To  
Notes
2003-09-18 00:00:00SEPARATE PLANS AND PERMIT APPLICATION
 FEES TO BE BE SUBMITTED FOR ANY
 ELECTRICAL PERMIT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-08-26 Cont ID  
Sent By dpalmer Date 2003-08-26 Time 08:00 Rev Time 1.00
Received By dpalmer Date 2003-08-26 Time 08:00 Sent To  
Notes
2003-08-26 00:00:00*********** UNSAT *****************
  
 PLEASE SEE THAT PLANS SUBMITTED NOW BY
 STH SHOW ALL NEW WORK BEING PERFORMED
 FOR ELECTRICAL, THAT WAS NOT ON ORIG
 PLANS SUBMITTED. PLEASE SEE THE FOLLOW-
 -ING COMMENTS.
  
 1)NOTE: PLEASE CLARIFY NEW OCP TO FEED
 NEW GUTTER WHICH FEEDS A&B PANELS.
 215.5/240.3/310.16/250.122
  
 2)NOTE: PLEASE CLARIFY CONDUCTOR SIZE
 PANEL "B" FEED. SHOWN FOR NEW "A" BUT
 NOT FOR "B"?
  
 3)NOTE: PLEASE CORRELATE CIRCUITING ON
 PLANS WITH #'S ON PANEL SCHEDULE.
 A/C? WATER HEATER? ETC.
  
 4)NOTE: PLEASE VERFIY OCP FOR A/C SYS.?
 \\MAX 150%?
 PLEASE ALSO SIZE MAX OCP FOR WATER HEAT
 AT OR BELOW 150%. MIN 125% 422.13,422.11
 E-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REIVEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-19 Cont ID  
Sent By dpalmer Date 2003-05-19 Time 17:33 Rev Time 0.25
Received By dpalmer Date 2003-05-19 Time 17:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-09-02 Cont ID  
Sent By nmccray Date 2003-09-02 Time 14:26 Rev Time 0.00
Received By nmccray Date 2003-09-02 Time 14:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-06-12 Cont ID  
Sent By nmccray Date 2003-06-12 Time 13:47 Rev Time 0.00
Received By nmccray Date 2003-06-12 Time 13:46 Sent To  
Notes
2003-06-12 00:00:00**************PROVISO*******************
 1) SEPARATE PLAN AND PERMIT APPLICATION
 ARE REQUIRED FOR FIRE SPRINKLER REMODEL.
  
 2) SEPARATE PLAN AND PERMIT APPLICATION
 ARE REQUIRED FOR FIRE ALARM SYSTEM
 REMODEL.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-09-19 Cont ID  
Sent By csiegber Date 2003-09-19 Time 11:31 Rev Time 0.00
Received By csiegber Date 2003-09-19 Time 11:31 Sent To E
Notes
2003-09-19 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-08-25 Cont ID  
Sent By csiegber Date 2003-08-25 Time 11:18 Rev Time 0.00
Received By csiegber Date 2003-08-25 Time 11:18 Sent To  
Notes
2003-08-25 00:00:00COMM BD #25

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-20 Cont ID  
Sent By csiegber Date 2003-08-20 Time 16:37 Rev Time 0.00
Received By csiegber Date 2003-08-20 Time 16:37 Sent To P
Notes
2003-08-20 00:00:00TO KS DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-20 Cont ID  
Sent By csiegber Date 2003-08-20 Time 15:25 Rev Time 0.00
Received By csiegber Date 2003-08-20 Time 15:25 Sent To  
Notes
2003-08-20 00:00:00TO KS DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-09 Cont ID  
Sent By shernand Date 2003-07-09 Time 16:19 Rev Time 0.00
Received By shernand Date 2003-07-09 Time 16:19 Sent To  
Notes
2003-07-09 00:00:00COMM BOARD #48

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-05-14 Time 16:00 Rev Time 0.00
Received By shernand Date 2003-05-14 Time 16:00 Sent To  
Notes
2003-05-14 00:00:00COMM BOARD #27

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-09-02 Cont ID  
Sent By pkrauss Date 2003-09-02 Time 12:43 Rev Time 0.40
Received By pkrauss Date 2003-09-02 Time 12:43 Sent To  
Notes
2003-09-02 00:00:00PROVISO:
  
 NO COMBUSTIBLES ABOVE THE CEILING IN THE
 RETURN AIR PLENUM.2001 FBC(M) 602.2.1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-05-27 Cont ID  
Sent By pkrauss Date 2003-05-27 Time 13:56 Rev Time 0.45
Received By pkrauss Date 2003-05-27 Time 13:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-08-25 Cont ID  
Sent By kstevens Date 2003-08-25 Time 11:15 Rev Time 1.00
Received By kstevens Date 2003-08-23 Time 16:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-07-22 Cont ID  
Sent By csiegber Date 2003-08-20 Time 16:37 Rev Time 1.00
Received By kstevens Date 2003-07-22 Time 10:48 Sent To  
Notes
2003-07-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW, SUBMIT A DETAIL
 SHOWING HEIGHT OF BACKING FOR SHOWER,
 SECTION 11-4.21.4, CONTROLS FOR SHOWER,
 SECTION 11-4.21.5, CURB FOR SHOWER, SEC-
 TION 11-4.21.7, (CURB SHOWN AS 4" AND
 THAT IS NOT APPROVED).
 2) SUBMIT A DETAIL FOR DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15
 AND ALL SUBSECTIONS. ALSO PROVISIONS
 SHALL BE MADE FOR THOSE WHO HAVE DIFFI-
 CULTY BENDING OR STOOPING. SECTION 11-4.
 1.3(10)(A).-A CUP DISPENSER AFFIXED
 ON THE WALL NEXT TO THE DRINKING FOUNT-
 AIN WILL MEET THIS REQUIREMENT, OR A
 HIGH/LOW DRINKING FOUNTAIN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-11 Cont ID  
Sent By kstevens Date 2003-06-11 Time 17:38 Rev Time 1.00
Received By kstevens Date 2003-06-11 Time 17:38 Sent To  
Notes
2003-06-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-2 OTHER TOILET ROOMS PROVIDED
 FOR THE USE OF OCCUPANTS OF SPECIFIC
 SPACES (I.E., A PRIVATE TOILET ROOM FOR
 THE OCCUPANT OF A PRIVATE OFFICE) SHALL
 BE ADAPTABLE. SUBMIT DETAILS FOR THE
 PRIVATE BATHROOM. SHOW TURNING RADIUS,
 CENTER LINE OF WATER CLOSET TO WALL,
 BACKING FOR ALL GRAB BARS, (W/C & SHWR),
 CURB FOR SHOWER, CONTROLS FOR SHOWER ECT
 SECTIONS 11-4.22.3, FIGURE 28, 11-4.16.4
 11-4.21.7, 11-4.21.5, 11-4.21.4 ECT.
 2) SHT A-2 TABLE 403.1 A DRINKING FOUNT-
 AIN IS REQUIRED. (ALSO SEE SEC 410.1)
 3) SHTS A-5/A-6 PLEASE SHOW CLEAR FLOOR
 SPACE FOR URNAL. 11-4.18.3.
 4) SHT P-2 GENERAL NOTES #16 AIR CHAMB-
 ERS ARE NOT APPROVED. PLEASE DELETE REF-
 ERENCE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692