Plan Review Stops For Permit 03032330
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-06-03 Cont ID  
Sent By jwitmer Date 2003-06-03 Time 09:36 Rev Time 0.50
Received By jwitmer Date 2003-06-03 Time 09:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-04-29 Cont ID  
Sent By jwitmer Date 2003-04-29 Time 06:36 Rev Time 0.50
Received By jwitmer Date 2003-04-29 Time 06:36 Sent To  
Notes
2003-04-29 00:00:00 
  
 BUILDING PLAN REVIEW
 PERMIT: 030323230
 ADD: 3619 S DIXIE
 CONT: FRANKLIN CONST
 TEL: (561)793-5098
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 2ND REVIEW
 ACTION : DENIED
  
 1)1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
 THE STRUCTURAL ENGINEER IS CALLING
 OUT FOR 3/16" TAPCONS @ NO SPACING,
 THE PRODUCT TESTING REPORT HAS ANCHORING
 SCHEDULE AOR B USING 1/4" TAPCONS SEE
 SCHEDULE FOR SPACING!
  
 2) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 HIGHLIGHT THE DETAILS OF ANCORING THAT
 WILL BE USED, THE ANCHORS AND SPACING.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-09 Cont ID  
Sent By jwitmer Date 2003-04-09 Time 17:11 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2003-04-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03032330
 ADD: 3619 S DIXIE HWY
 CONT: FRANKLIN CONST
 TEL: (561)793-5098
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) SUBMIT SITE PLAN INDICATING WHAT WALL
 WILL BE ALTERED. TABLE 600 MAY BE AND
 ISSUE.
  
 2) PROVIDE ELEVATION OF WALL INDICATING
 THE TOTAL LENGHTAND HEIGHT, AGAIN
 TABLE 600.
  
 3)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE PRODUCT TESTING REPORT SUBMITTED IS
 FOR DOORS NOT WINDOWS. THE REPORT IS
 GOOD FOR A SINGLE DOR OR DOUBLE DOOR.
 THE DOUBLE DOOR WOULD STILL REQUIRE
 INFILL, HOW WILL THIS BE ACCOMPLISHED?
  
 4) EXISTING BUILDINGS: CHAPTER 34.
 3401.7.2 THE REPLACEMENT OF EXTERIOR
 DOORS, OPERATIVE AND INOPERATIVE WINDOWS
 SHALL BE DESIGNED AND CONSTRUCTED IN
 ACCORDANCE WITH CHAPTER 16 OF THIS CODE.
  
 5)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 6)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 7)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 7) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-04-25 Cont ID  
Sent By mcarsill Date 2003-04-25 Time 10:09 Rev Time 0.00
Received By mcarsill Date 2003-04-25 Time 10:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-04-10 Cont ID  
Sent By nmccray Date 2003-04-10 Time 15:59 Rev Time 0.00
Received By nmccray Date 2003-04-10 Time 15:59 Sent To  
Notes
2003-04-10 00:00:001) PERMIT APPLICATION DESCRIBE PROJECT
 FOR REPLACING A WINDOW.
  
 2) IS THIS AN EXIT DOOR OR INTERIOR DOOR
  
 3) WHAT TYPE OF OCCUPANT
  
 4) PLEASE SEE BUILDING PLAN REVIEW
 COMMENTS.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-28 Cont ID  
Sent By shernand Date 2003-05-28 Time 13:07 Rev Time 0.00
Received By shernand Date 2003-05-28 Time 13:07 Sent To  
Notes
2003-05-28 00:00:00COMM BOARD #30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-25 Cont ID  
Sent By shernand Date 2003-04-25 Time 09:38 Rev Time 0.00
Received By shernand Date 2003-04-25 Time 09:38 Sent To  
Notes
2003-04-25 00:00:00COMM BOARD #9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-31 Cont ID  
Sent By sthyng Date 2003-03-31 Time 13:45 Rev Time 0.00
Received By sthyng Date 2003-03-31 Time 13:45 Sent To  
Notes
2003-03-31 00:00:00COMM BOARD #27