Plan Review Details - Permit 03032207
Plan Review Stops For Permit 03032207
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-07-17 Cont ID  
Sent By sthyng Date 2003-07-17 Time 09:14 Rev Time 0.25
Received By sthyng Date 2003-07-17 Time 09:14 Sent To  
Notes
2003-07-17 00:00:00HOLDS OK PER E GARCED, NOTE IN PERMIT
 PACKAGE

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-07-16 Cont ID  
Sent By sthyng Date 2003-07-16 Time 14:35 Rev Time 1.50
Received By sthyng Date 2003-07-16 Time 14:35 Sent To  
Notes
2003-07-16 00:00:00*******CORRECTIONS*******
  
 1.)SEE ATTACHED IN REGARDS TO HOLDS
 PLACED ON THIS PROPERTY. THESE HOLDS
 MUST BE ADDRESSED BEFORE A PERMIT CAN
 BE ISSUED.
  
 2.)REFER TO NOTE 8.) ON THE ORIGINAL
 CORRECTION LIST AND NOTE 2.) ON THE
 CORRECTION LIST DATED 4/25/03.A
 TITLE BLOCK AND SEAL, DATED AND SIGNED,
 ARE REQUIRED ON ALL DOCUMENTS SUBMITTED
 FOR PUBLIC RECORD.A TITLE BLOCK IS
 REQUIRED TO INCLUDE THE LICENSE NUMBER.
 FS471, FAC61G1-16.004.
  
 INCLUDE YOUR LICENSE NUMBER ON BOTH
 SHEETS.
  
 SEAL THE FIRST PAGE
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-04-28 Cont ID  
Sent By shernand Date 2003-07-16 Time 10:05 Rev Time 1.50
Received By sthyng Date 2003-04-28 Time 14:02 Sent To  
Notes
2003-04-28 00:00:00**********CORRECTIONS************
  
 1.)FLORIDA STATUTE 471.031(1)(E), A
 PERSON MAY NOT USE OR ATTEMPT TO USE A
 LICENSE THAT HAS BEEN SUSPENDED,REVOKED,
 OR PLACED ON INACTIVE OR DELINQUENT
 STATUS.FLORIDA STATUTE 471.003(1) NO
 PERSON OTHER THAN A DULY LICENSED
 ENGINEER SHALL PRACTICE ENGINEERING OR
 USE THE NAME OR TITLE OF "PROFESSIONAL
 ENGINEER" TO INDICATE THAT SUCH PERSON
 HOLDS AN ACTIVE LICENSE AS AN ENGINEER
 IN THIS STATE.FLORIDA STATUTE 471.033
 (I), THE FOLLOWING ACTS CONSTITUTE
 GROUNDS FOR WHICH THE DISCIPLINARY
 ACTIONS IN SUBSECTION (3) MAY BE TAKEN:
 (I) PRACTICING ON A REVOKED, SUSPENDED,
 INACTIVE, OR DELINQUENT LICENSE.
  
 BE ADVISED THAT A COMPLAINT
 MAY BE FILED WITH THE FLORIDA BOARD
 OF PROFESSIONAL ENGINEERS AGAINST
 MOHAMMAD HOSSEIN ARSALI.
  
 2.)SUBMIT NEW ENGINEERED PLANS,
 SIGNED AND SEALED BY A LICENSED
 ENGINEER.
  
 3.)CALL TOM MOORE, 805-6669, IN
 REGARDS TO THE DEMO HOLDS ON THIS
 PROPERTY.
  
 4.)ADVISE AS TO THE STATUS OF THE
 HOLD DATED 7/20/02, LIENED CASE HOLD.
 MIKE MALONEY, X8940
  
 5.)ONLY ONE OWNER/BUILDER PERMIT IS
 ALLOWED IN A 12 MONTH PERIOD.DUE TO
 THE OWNER/BUILDER PERMIT ISSUED FOR
 517 ARDMORE ROAD, THIS PERMIT IS BEING
 VOIDED.APPLY FOR A NEW PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-04-25 Cont ID  
Sent By sthyng Date 2003-04-25 Time 13:27 Rev Time 2.00
Received By sthyng Date 2003-04-25 Time 13:27 Sent To  
Notes
2003-04-25 00:00:00**********CORRECTIONS************
  
 1.)REFER TO NOTE 1.) ON THE ORIGINAL
 CORRECTION LIST.SHOW BEDROOM WINDOWS
 WITH SIZES AND TYPE OF WINDOW TO SHOW
 COMPLIANCE WITH FBC 1004.5.
  
 2.)REFER TO NOTE 8.) ON THE ORIGINAL
 CORRECTION LIST.A TITLE BLOCK IS
 REQUIRED ON ALL SEALED SHEETS.SEALS
 SHOULD BE DATED AS WELL AS SIGNED.
 ADDITIONALLY, WHEN STRUCTURAL SHEETS
 ARE SUBMITTED, HAVE A TITLE BLOCK AND
 SEAL ON EVERY PAGE.
  
 3.)FOR THE ATTACHMENT OF THE BOTTOM
 PLATE, SPECIFY SPACING OF ATTACHMENTS
 AND LENGTH OF BOLTS.
  
 4.)THE DOCUMENT SUBMITTED FOR THE
 EXTERIOR DOORS IS NOT A PRODUCT
 APPROVAL.PLEASE SUBMIT TWO COPIES
 OF THE PRODUCT APPROVAL FOR THE DOOR.
  
 5.)REFER TO NOTE #9 ON THE ORIGINAL
 CORRECTION LIST, NAMELY LIEN HOLD AND
 ABAS HOLD.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-21 Cont ID  
Sent By shernand Date 2003-04-23 Time 10:41 Rev Time 2.00
Received By sthyng Date 2003-04-21 Time 11:08 Sent To  
Notes
2003-04-21 00:00:00**********CORRECTIONS************
  
 1.)PROVIDE A FOOTPRINT OF THE HOUSE
 SHOWING WINDOWS TO BE REPLACED (NOT
 WINDOWS BEING REGLAZED).INDICATE
 BEDROOM WINDOWS, IF ANY.FBC 1004.5.
  
 2.)WINDOWS BEING REPLACED (NOT
 REGLAZED) ARE TO HAVE HURRICANE
 PROTECTION, FBC1606.1.4, FBC 3401.7.2.4.
  
 3.)SUBMIT 2 COPIES OF PRODUCT
 APPROVALS FOR THE FOLLOWING:
 WINDOWS (REPLACEMENT ONLY, NOT
 WINDOWS TO BE REGLAZED)
 HURRICANE SHUTTERS
 EXTERIOR DOORS BEING REPLACED
  
 4.)WHEN SUBMITTING PERMITTING
 PAPERWORK, PLEASE ALWAYS SUBMIT TWO
 COPIES.ONE COPY REMAINS IN OUR RECORDS
 AND ONE IS FOR YOUR PERMIT SET.ONLY
 ONE SEALED SET OF STRUCTURE INSPECTION
 RESULTS WAS SUBMITTED; 2ND COPY OF
 REPAIR DETAILS WAS NOT SEALED.
  
 5.)WHEN INDICATING AN ATTACHMENT,
 EITHER SPECIFY BRAND AND TYPE, OR GIVE
 UPLIFT REQUIREMENTS.DETAILS SHOULD
 INCLUDE TYPE OF LUMBER, SIZE, AND
 SPECIFIC ATTACHMENTS.
  
 6.)FOR CLARITY, LABEL THE VARIOUS
 ATTACHMENT DETAILS (A, B, C, ETC.) AND
 ON THE STRUCTURE INSPECTION RESULTS AND
 REPAIR DETAILS SHEET, REFER TO THE
 SPECIFIC DETAIL FOR THE VARIOUS ITEMS.
  
 7.)THE WALL FRAMING/WALL SHEATHING
 DETAIL SHEETS ARE NOT LEGIBLE.PLEASE
 SUPPLY LEGIBLE COPIES.ALSO IT REFERS
 TO AN ATTACHMENT SCHEDULE FOR THE BOTTOM
 PLATE WHICH IS NOT ON THE SHEET.THE
 NAILING SCHEDULE AT THE TOP OF THE PAGE
 CONFLICTS WITH THE NAILING IN THE TEXT
 OF THE DIAGRAM.
  
 8.)PROVIDE A TITLE BLOCK FOR ALL
 SEALED SHEETS.SEALS SHOULD BE DATED
 AS WELL AS SIGNED.
  
 9.)BEFORE A PERMIT CAN BE ISSUED,
 THE HOLDS ON THIS PROPERTY MUST BE
 ADDRESSED.SEE ATTACHED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-07-16 Cont ID  
Sent By shernand Date 2003-07-16 Time 10:05 Rev Time 0.00
Received By shernand Date 2003-07-16 Time 10:05 Sent To B
Notes
2003-07-16 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-04-28 Cont ID  
Sent By shernand Date 2003-04-28 Time 11:01 Rev Time 0.00
Received By shernand Date 2003-04-28 Time 11:01 Sent To  
Notes
2003-04-28 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-23 Cont ID  
Sent By shernand Date 2003-04-23 Time 10:41 Rev Time 0.00
Received By shernand Date 2003-04-23 Time 10:41 Sent To B
Notes
2003-04-23 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-21 Cont ID  
Sent By shernand Date 2003-04-21 Time 09:32 Rev Time 0.00
Received By shernand Date 2003-04-21 Time 09:32 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-01 Cont ID  
Sent By shernand Date 2003-04-01 Time 16:56 Rev Time 0.00
Received By shernand Date 2003-04-01 Time 16:56 Sent To B
Notes
2003-04-01 00:00:00PREINSPECT,LOU HATTEN TO REVIEW.