Plan Review Details - Permit 03032080
Plan Review Stops For Permit 03032080
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-05-13 Cont ID  
Sent By hpiskura Date 2003-05-13 Time 09:15 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-05-12 Time 09:20 Rev Time 0.00
Received By hpiskura Date 2003-04-30 Time 12:15 Sent To  
Notes
2003-04-30 00:00:00PLEASE NOTE WHICH MULLION THICKNESS AND
 LENGTH WILL BE USED IN THE FAMILY ROOM
 AND LIVING ROOM EXTERIOR DOOR AND FIXED
 LIGHT SYSTEM.
  
 PAGE 8 OF 8 IS MISSING FROM THE 02-0701.
 07 NOA (PGT FIXED WINDOW)
  
 THE WAYNE DALTON SHEETS, (GARAGE DOORS)
 ARE NOT NOTICE OF ACCEPTANCE OR TEST
 REPORTS.FURTHER, THE DESIGN PRESSURES
 ON THEM ARE LOWER THAN THOSE DECLARED
 ON THE PERMIT PLANS.
  
 SAFETY GLASS IS REQUIRED AT THE EXTERIOR
 WINDOW IN THE MASTER BATH BY THE
 WHIRLPOOL TUB.FBC 2405.2.1 #2.
  
 PLEASE PROVIDE A COPY OF THE PAID
 RECEIPT FROM PALM BEACH COUNTY FOR THE
 IMPACT FEES.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-04-09 Cont ID  
Sent By sgraham Date 2003-03-27 Time 15:24 Rev Time 0.33
Received By dpalmer Date 2003-04-09 Time 02:55 Sent To P
Notes
2003-04-09 00:00:00********** NOTES REDLINED **********
  
 MISSING BATH CIRCUIT(S) PER 210-52D/
 210-11-C-3. MUST BE 20A /#12
  
 SIZING OF KW FOR WASHER TO BE 1.5KW PER
 220-16
  
 ITEMS NOTED ON PLAN.
  
 IF THERE ARE ANY QUESTIONS, PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-12 Cont ID  
Sent By shernand Date 2003-05-12 Time 09:20 Rev Time 0.00
Received By shernand Date 2003-05-12 Time 09:20 Sent To B
Notes
2003-05-12 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-03 Time 10:38 Rev Time 0.00
Received By shernand Date 2003-04-03 Time 10:56 Sent To  
Notes
2003-04-03 00:00:00FOUND PLANS IN ELECTRICAL, ADDED SOIL RE
 PORT TO PACKET

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-25 Cont ID  
Sent By sthyng Date 2003-03-25 Time 16:51 Rev Time 0.00
Received By sthyng Date 2003-03-25 Time 16:51 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-04-19 Cont ID  
Sent By jleech Date 2003-04-19 Time 06:54 Rev Time 0.33
Received By jleech Date 2003-04-19 Time 06:54 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-04-14 Cont ID  
Sent By dpalmer Date 2003-04-09 Time 02:55 Rev Time 0.33
Received By kstevens Date 2003-04-14 Time 18:14 Sent To  
Notes
2003-04-14 00:00:00OK PER JOHN LEECH
  
  
 GAS APPLICATION REQUIRED - FOLLOWING
 INFORMATION REQUIRED WHEN APPLYING FOR
 GAS PERMIT.
 1. TYPE OF GAS, (LP OR NATURAL)
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 4. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304. DRYER ROOM IS A
 CONFINED SPACE. OPENINGS/OPENING REQUIR-
 ED PER 304.3.1/304.3.2
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 6. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 7. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-27 Cont ID  
Sent By sthyng Date 2003-03-25 Time 16:51 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***