Plan Review Details - Permit 03032055
Plan Review Stops For Permit 03032055
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-08-05 Cont ID  
Sent By jwitmer Date 2003-08-05 Time 08:14 Rev Time 0.25
Received By jwitmer Date 2003-08-05 Time 08:14 Sent To  
Notes
2003-08-05 00:00:00REVISION 7/24/03 ADD KITHEN WINDOW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-05-19 Cont ID  
Sent By alange Date 2003-08-01 Time 15:43 Rev Time 0.11
Received By jwitmer Date 2003-05-19 Time 12:26 Sent To  
Notes
2003-05-19 00:00:00BUILDING PROVISO:
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 RE-EVALUATE TRUSS ANCHOR SCHEDULE BEFORE
 FOOR FRAMING INSPECTION.
 JIM WITMER
 (561)805-6715

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-05-18 Cont ID  
Sent By jwitmer Date 2003-05-18 Time 09:55 Rev Time 1.00
Received By jwitmer Date 2003-05-18 Time 09:55 Sent To  
Notes
2003-05-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03032055
 ADD: 10295 SANDY CAY LANE
 CONT: G.W. PURUCKER HOMES, INC
 TEL: (561)722-6141
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 PROVISO:
 1)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 RE-EVALUATE TRUSS ANCHOR SCHEDULE BEFORE
 FOOR FRAMING INSPECTION.
 JIM WITMER
 (561)805-6715
 ROOF TRUSS SCHEDULE RED LINED TO INDI-
 CATE CURRENT 2003 VALUESS / NO INCRESS
 TAKEN.
  
 2) STORM SHUTTERS UNDER SEPERATE PERMIT
 AS PER CONTRACTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-05-08 Time 14:55 Rev Time 2.25
Received By jwitmer Date 2003-04-30 Time 10:29 Sent To  
Notes
2003-04-30 00:00:00 
  
 BUILDING PLAN REVIEW
 PERMIT: 03032055
 ADD: 10295 SAND CAY LANE
 CONT: G W PURUCKER HOMES
 TEL: (561)775-1170
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION : DENIED
  
 *************NOTE*************
 FUTURE POOL
 1803.1.3 EXCAVATION FOR ANY PURPOSE
 SHALL NOT EXTEND WITHIN 1 FT OF THE
 ANGLE OF REPOSE OR NARURAL SLOPE OF THE
 SOIL UNDER ANY FOOTING OR FOUNDATION,
 UNLESS SUCH FOOTING OR FOUNDATION IS
 FIRST PROPERLY UNDERPINNED OR PROTECTED
 AGAINST SETTLEMENT.
  
  
 1) 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 2)SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.
  
 A) CASTLEGATE/ MASONITE DOOR SITE
 SPECIFIC ENGINEERING! CITY FORM ATTACHED
  
 3)STORM HUTTERS: HIGHLIGHT WHAT TYPE OF
 WALL ATTACHMENTS THAT ARE BEING USED TO
 ANCHOR THE STORM SHUTTERS, IN THE REPORT
 AS WELL AS THE TECHNICAL SHEETS.
  
 THE SECOND PROBLEM IS USING THE CONCRETE
 TABLES 12" VERSES THE MASONARY TABLES!!!
  
 INDICATE HOW EGRESS WILL BE MAINTAINED
 WITH STORM SHUTTERS ON FRONT DOORS.
  
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 4)TRUSSES:
 THE ENGINEERED TRUSS DRAWINGS & LAYOUT
 ARE NOT REQUIRED FOR PLAN REVIEWOF A
 SINGLE FAMILY HOUSE. THEY WILL BE
 REQUIRED AT TIME OF ROOF FRAMING INSPEC-
 TION. IF SUBMITTED THEY ARE TO BE
 REVIEWED FOR CODE COMPLIANCE!
  
 ANCHOR SCHEDULE:
 (TA22) USP LUGT C2 F1= 500
 (TA24) USP HC10 USP 2003 CATALOG
 USP ISSUED A PRODUCTS DELETED
 FROM THEIR 2003 CATALOG!
 SHEET A-5 (TA-13) USP TA20 R VALUE FOR
 ONE STRAP 1520 OK! 2003 CATOLOG
 TWO STRAPS ONLY GOOD FOR 2750
  
 THE ENGINEERED TRUSS INDEX SHEET, I'VE
 HIGHLIGHTED TRUSSES WITH PROBLEMS
  
 THE TRUSS PLACEMENT DIGRAM JOB # 10263
 INDICATES A TRUSS/TRUSS CONNECTORS
 I CAN NOT LOCATE EHUH26 IN EITHER USP OR
 SIMPSON.
  
 ON A-5.1 GIRDER GR-7 NO INFO ON PLANS
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-04-11 Cont ID  
Sent By btrobaug Date 2003-04-11 Time 12:07 Rev Time 0.50
Received By btrobaug Date 2003-04-11 Time 10:55 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-08-01 Cont ID  
Sent By alange Date 2003-08-01 Time 15:43 Rev Time 0.00
Received By alange Date 2003-08-01 Time 15:43 Sent To B
Notes
2003-08-01 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-07-01 Cont ID  
Sent By shernand Date 2003-07-01 Time 08:40 Rev Time 0.00
Received By shernand Date 2003-07-01 Time 08:40 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-13 Cont ID  
Sent By shernand Date 2003-06-13 Time 16:11 Rev Time 0.00
Received By shernand Date 2003-06-13 Time 16:11 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-08 Cont ID  
Sent By shernand Date 2003-05-08 Time 14:55 Rev Time 0.00
Received By shernand Date 2003-05-08 Time 14:55 Sent To B
Notes
2003-05-08 00:00:00JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-25 Cont ID  
Sent By sthyng Date 2003-03-25 Time 13:33 Rev Time 0.00
Received By sthyng Date 2003-03-25 Time 13:33 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-04-19 Cont ID  
Sent By jleech Date 2003-04-14 Time 19:52 Rev Time 0.50
Received By jleech Date 2003-04-19 Time 08:45 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-07-05 Cont ID  
Sent By kstevens Date 2003-07-05 Time 09:30 Rev Time 0.50
Received By kstevens Date 2003-07-05 Time 09:30 Sent To  
Notes
2003-07-05 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-06-21 Cont ID  
Sent By shernand Date 2003-07-01 Time 08:41 Rev Time 0.50
Received By kstevens Date 2003-06-21 Time 08:01 Sent To  
Notes
2003-06-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN. NO LAUNDRY SINK SHOWN
 ON FLOOR PLAN. NO SHOWER SHOWN ON RISER
 DIAGRAM. PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-04-14 Cont ID  
Sent By shernand Date 2003-06-13 Time 16:11 Rev Time 0.50
Received By jleech Date 2003-04-14 Time 19:52 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-05-19 Cont ID  
Sent By jwitmer Date 2003-05-19 Time 12:27 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2003-05-19 00:00:00OK PER S GRAHAM 05/19/03JW

Review Stop Z ZONING
Rev No 1 Status F Date 2003-03-27 Cont ID  
Sent By sthyng Date 2003-03-25 Time 13:33 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-03-27 00:00:00DENIED, ZERO LOT LINE COMMUNITY