| 2003-04-30 00:00:00 | |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 03032055 |
| | ADD: 10295 SAND CAY LANE |
| | CONT: G W PURUCKER HOMES |
| | TEL: (561)775-1170 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION : DENIED |
| | |
| | *************NOTE************* |
| | FUTURE POOL |
| | 1803.1.3 EXCAVATION FOR ANY PURPOSE |
| | SHALL NOT EXTEND WITHIN 1 FT OF THE |
| | ANGLE OF REPOSE OR NARURAL SLOPE OF THE |
| | SOIL UNDER ANY FOOTING OR FOUNDATION, |
| | UNLESS SUCH FOOTING OR FOUNDATION IS |
| | FIRST PROPERLY UNDERPINNED OR PROTECTED |
| | AGAINST SETTLEMENT. |
| | |
| | |
| | 1) 1707.4.4.2 TAPERED BUCKS: |
| | SHALL EXTEND BEYOND THE INTERIOR FACE |
| | OF THE WINDOW OR DOOR FRAME SUCH THAT |
| | FULL SUPPORT OF THE FRAME IS SUPPORTED. |
| | |
| | 2)SITE SPECIFIC ENGINEERING (PRODUCT |
| | APPROVAL) REQUIRES THE WET SIGNATURE, |
| | DATE AND EMBOSSED SEAL OF THE ENGINEER |
| | CERTIFYING THE PRODUCT AND SIGNATURE |
| | AND SEAL OF THE DESIGN PROFESSIONAL |
| | OF RECORD. |
| | |
| | A) CASTLEGATE/ MASONITE DOOR SITE |
| | SPECIFIC ENGINEERING! CITY FORM ATTACHED |
| | |
| | 3)STORM HUTTERS: HIGHLIGHT WHAT TYPE OF |
| | WALL ATTACHMENTS THAT ARE BEING USED TO |
| | ANCHOR THE STORM SHUTTERS, IN THE REPORT |
| | AS WELL AS THE TECHNICAL SHEETS. |
| | |
| | THE SECOND PROBLEM IS USING THE CONCRETE |
| | TABLES 12" VERSES THE MASONARY TABLES!!! |
| | |
| | INDICATE HOW EGRESS WILL BE MAINTAINED |
| | WITH STORM SHUTTERS ON FRONT DOORS. |
| | |
| | FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | 4)TRUSSES: |
| | THE ENGINEERED TRUSS DRAWINGS & LAYOUT |
| | ARE NOT REQUIRED FOR PLAN REVIEWOF A |
| | SINGLE FAMILY HOUSE. THEY WILL BE |
| | REQUIRED AT TIME OF ROOF FRAMING INSPEC- |
| | TION. IF SUBMITTED THEY ARE TO BE |
| | REVIEWED FOR CODE COMPLIANCE! |
| | |
| | ANCHOR SCHEDULE: |
| | (TA22) USP LUGT C2 F1= 500 |
| | (TA24) USP HC10 USP 2003 CATALOG |
| | USP ISSUED A PRODUCTS DELETED |
| | FROM THEIR 2003 CATALOG! |
| | SHEET A-5 (TA-13) USP TA20 R VALUE FOR |
| | ONE STRAP 1520 OK! 2003 CATOLOG |
| | TWO STRAPS ONLY GOOD FOR 2750 |
| | |
| | THE ENGINEERED TRUSS INDEX SHEET, I'VE |
| | HIGHLIGHTED TRUSSES WITH PROBLEMS |
| | |
| | THE TRUSS PLACEMENT DIGRAM JOB # 10263 |
| | INDICATES A TRUSS/TRUSS CONNECTORS |
| | I CAN NOT LOCATE EHUH26 IN EITHER USP OR |
| | SIMPSON. |
| | |
| | ON A-5.1 GIRDER GR-7 NO INFO ON PLANS |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)659-8096 X 8412 |
| | FAX: (561)659-8026 |