Plan Review Details - Permit 03032015
Plan Review Stops For Permit 03032015
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-04-03 Cont ID  
Sent By dpalmer Date 2003-04-02 Time 17:27 Rev Time 0.75
Received By lsmith Date 2003-04-03 Time 14:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-04-29 Cont ID  
Sent By dpalmer Date 2003-04-29 Time 19:36 Rev Time 0.33
Received By dpalmer Date 2003-04-29 Time 19:36 Sent To P
Notes
2003-04-29 00:00:00********* NOTE *********
  
 PLEASE SEE POSSIBLE NOTES FROM PLUMB
 PLAN REVIEW.
 PLUMB PLANS/SUBMITTALS DO NOT CONTAIN
 ORIG SIGNATURE BY ENGINEER OF RECORD
 ON ALL SHEETS AND SETS. ONLY ONE COPY
 OF ONE SUBMITTAL CONTAINS ORIG "WET'
 SIGNATURE.
 PLEASE SEE FS/ FAC 471.025 AND FAC
 61G15-23.002 ALL SETS/SHEETS/DOCUMNETS
 ETC MUST CONTAIN ORIG "WET" SIGNATURE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-04-09 Cont ID  
Sent By shernand Date 2003-04-28 Time 13:56 Rev Time 0.33
Received By dpalmer Date 2003-04-09 Time 06:23 Sent To P
Notes
2003-04-09 00:00:00************** UNSAT ***************
  
 PLEASE SEE NOTES FROM FIRST REVIEW
  
 1)NOTE: PLEASE SEE PLANS, WIRING DIAGRAM
 DOES NOT SHOW 3-PUMPS AS SHOWN ON PLUMB
 AND SUBMITTED PANEL SCHEDULE.
  
 2)NOTE: PLEASE SUBMIT PLANS AND SPECS
 FOR ONE HEATER OR THE OTHER. SUBMITTED
 BOTH ELECTRICAL AND GAS??
 ELECTRICAL WIRING DIAGRAM DOES NOTE SHOW
 EITHER? IF ELECTRIC, SUBMIT LOAD
 CALCULATIONS THAT INCLUDE NEW PUMPS AND
 HEAT PUMP. PANEL SCHEDULE SUBMITTED
 ONLY LIST ON PANEL SCHEDULE AND DOES NOT
 REVISE LOAD CALC. PLEASE ALSO SEE LOAD/
 KW LISTED ON PANEL SCHEDULE FOR HEAT
 PUMP. KW RATING DOES NOT CORRELATE
 W/ SPECS SUBMITTED.??
  
 PLEASE SEE ATTACHED LETTER FOR PLANS
 BEING REVIEW. FS 553.80(2)(B).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT8372
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-02 Cont ID  
Sent By shernand Date 2003-04-04 Time 14:16 Rev Time 0.33
Received By dpalmer Date 2003-04-02 Time 17:27 Sent To B
Notes
2003-04-02 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS, SHOWS THREE
 PUMPS AND ONLY ONE SHOWN ON RISER DIA-
 -GRAM?
  
 2)NOTE: PLEASE SEE POOL DATA, MENTIONS,
 GAS AND ELECTRIC HEATERS? PLEASE SEE
 PERMIT APPLICATION, SHOWS NO HEATERS?
 PLEASE ADJUST.
 IF HEATERES ARE INSTALLED, PLEASE ALSO
 SUBMIT SPECS FOR HEATER. IF ELECTRICAL
 HEATER IS INSTALLED, PLEASE SUBMIT LOAD
 CALCULATIONS FOR EXISTING SERVICE AND
 NEW ADDED LOADS.
 215-5/220
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-28 Cont ID  
Sent By shernand Date 2003-04-28 Time 13:56 Rev Time 0.00
Received By shernand Date 2003-04-28 Time 13:56 Sent To E
Notes
2003-04-28 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-04 Cont ID  
Sent By shernand Date 2003-04-04 Time 14:16 Rev Time 0.00
Received By shernand Date 2003-04-04 Time 14:16 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-25 Cont ID  
Sent By sthyng Date 2003-03-25 Time 13:29 Rev Time 0.00
Received By sthyng Date 2003-03-25 Time 13:29 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-05-01 Cont ID  
Sent By bstaples Date 2003-05-01 Time 10:34 Rev Time 0.00
Received By bstaples Date   Time   Sent To  
Notes
2003-05-01 00:00:00PLANS WITH SEAL AND SIGNATURE SUBMITTED.
 5/1/03 WRS.

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-04-30 Cont ID  
Sent By kstevens Date 2003-04-30 Time 15:52 Rev Time 0.25
Received By kstevens Date 2003-04-30 Time 15:51 Sent To  
Notes
2003-04-30 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FS61G15-23.002 SEAL SIGNATURE
 AND DATE.
  
 1) PLUMBING PLANS/SUBMITTALS DO NOT CON-
 TAIN ORIGANAL SIGNATURE OF ENGINEER OF
 RECORD SHEETS AND SETS. DATE MISSING ON
 ALL SEALS. SEE ATTACHED SHEET FOR REFER-
 ENCE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-04-15 Cont ID  
Sent By dpalmer Date 2003-04-29 Time 19:36 Rev Time 1.50
Received By kstevens Date 2003-04-15 Time 10:29 Sent To  
Notes
2003-04-15 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) HAND DRAWN CORRECTIONS ON SIGNED AND
 SEALED PLANS SHALL BE INITALED AND DATED
 BY ENGINEER OF RECORD.
 2) TWO COPIES REQUIRED FOR ALL INFOR-
 MATION SUBMITTED.
 3) NEW PIPING SCHEMATIC, ONLY ONE HEATER
 IS SHOWN. POOL LAYOUT SHOWS 2 HEATERS,
 ONE GAS AND ONE ELECTRIC. PLEASE SHOW
 BOTH HEATERS ON SCHEMATIC.
 4) NOTE #1 STATES CPVC FLANGES WITH PVC
 BEING GLUED TO THE CPVC. THIS IS NOT
 APPROVED. PLEASE SEE MANUFACTURES INFOR-
 MATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-01 Cont ID  
Sent By dpalmer Date 2003-04-09 Time 06:23 Rev Time 0.50
Received By kstevens Date 2003-04-01 Time 16:34 Sent To E
Notes
2003-04-01 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 2) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. - POOL DATA SHOWS AUTO VAC
 CLEANER, BUT PIPING DIAGRAM AND PIPING
 SCHEMATIC SHOWS NONE. PLEASE CLAIRFY
 3) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 4) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 5) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
 6) PIPING SCHEMATIC DOES NOT REFLECT THE
 PIPING DIAGRAM. ONLY ONE PUMP IS SHOWN,
 NO POOL HEATERS ARE SHOWN. IF THERE IS
 A VACUMM LINE IT SHALL BE SHOWN. THERE
 IS NO PIPING SHOWN FOR THE SPA ON THE
 SCHEMATIC. PLEASE SUBMIT A PIPING SCHEM-
 ATIC THAT REFLECTS THE POOL PIPING WITH
 ALL PUMPS, FILTERS, HEATERS, MAIN DRAINS
 VALVES ECT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-31 Cont ID  
Sent By sthyng Date 2003-03-25 Time 13:29 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***