Plan Review Details - Permit 03031958
Plan Review Stops For Permit 03031958
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-08 Cont ID  
Sent By shernand Date 2003-04-08 Time 15:43 Rev Time 0.00
Received By shernand Date 2003-04-08 Time 15:43 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-25 Cont ID  
Sent By dpalmer Date 2003-03-25 Time 09:42 Rev Time 0.00
Received By dpalmer Date 2003-03-25 Time 09:42 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-04-15 Cont ID  
Sent By pkrauss Date 2003-04-15 Time 09:44 Rev Time 0.40
Received By pkrauss Date 2003-04-15 Time 09:44 Sent To  
Notes
2003-04-15 00:00:00CALLED CONTRACTOR - RESUBMITTAL DOES
 NOT GIVE SIZE OF O.A. DUCT, NEED LOUVER
 THAT IS SCREENED. IS O.A. DUCT IN
 CLOSE PROXIMITY OF R/A?

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-03-31 Cont ID  
Sent By shernand Date 2003-04-08 Time 15:43 Rev Time 0.35
Received By pkrauss Date 2003-03-31 Time 08:32 Sent To  
Notes
2003-03-31 00:00:00PLEASE PROVIDE THE FOLLOWING INFORMATION
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 2001 FBC(M) TABLE 403.3 & ASHRAE
 62-89.
  
 2.INDICATE EXHAUST (NEW OR EXISTING)
  
 3.PLEASE CLARIFY THE LOCATION OF THE
 CONDENSER UNIT, IT APPEARS TO BE AGAINST
 THE BUILDING.INDICATE WHERE THE
 PROPERTY LINE - 3 FT SETBACK REQUIRED.
  
 4.IS THIS A HAIR SALON OR WILL NAILS
 & PEDICURES BE DONE AT THIS LOCATION?
 IF SO, COMPLY WITH ASHRAE 62-89 SECTION
 5.7.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.