Plan Review Details - Permit 03031898
Plan Review Stops For Permit 03031898
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-29 Cont ID  
Sent By jwitmer Date 2003-04-29 Time 11:22 Rev Time 0.50
Received By jwitmer Date 2003-04-29 Time 11:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-10 Cont ID  
Sent By jwitmer Date 2003-04-10 Time 09:31 Rev Time 1.33
Received By jwitmer Date 2003-04-10 Time 09:31 Sent To  
Notes
2003-04-10 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03031898
 ADD: 1601 BELVEDERE RD400/402
 CONT: INTEGRAL CONSTRUCTION
 TEL: (954)485-1110
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 PLEASE REVIEW OFFICE # 4 & 9 ENTRY
 DOORS, FOR THE REQUIRED 18" ON THE PULL
 SIDE OF THE DOOR.
  
 OFFICE # 9 IS"AS IS" SEE 20% DISPROP
 ORTIONATE COST. THIS IS THE ONLY "AS IS"
 ITEM SHOWN ON THE PLAN, THERE IS A POR-
 TION OF VTHIS FLOOR NOT INDICATED ON THE
 PLAN THAT MAY STILL REQUIRE ADDITIONAL
 INFORMATION, OR INSPECTOR MAY SEE IN THE
 FIELD AFTER THE PERMIT IS ISSUED!
  
 2) PLEASE PROVIDE INFORMATION FOR ENTRY
 DOORS TABLE 705.1.2 TENANT SEPERATION
 1 HR./ OPENING PROTECTIVE 45 MIN. (BUILD
 INGS NOT SPRINKLERED)
  
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-08-04 Cont ID  
Sent By dpalmer Date 2003-08-04 Time 11:44 Rev Time 0.33
Received By dpalmer Date 2003-08-04 Time 11:44 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-29 Cont ID  
Sent By alange Date 2003-07-31 Time 10:31 Rev Time 0.50
Received By dpalmer Date 2003-04-29 Time 12:22 Sent To  
Notes
2003-04-29 00:00:00************* PROVISO/NOTES ************
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEWS.
  
 1)NOTE: PLEASE CIRCUIT PLANS AND REVISE
 SHEETS BEFORE FINAL.
 PLANS MUST BE REVISED/SIGNED, DATED AND
 SEALED BY THE ARCH OF RECORD. FS481
 PLEASE CORRELATE WITH SUBMITTED PANEL
 SCHEDULE AND REVISE LOAD CALCAULTIONS TO
 SHOW ALL CONTINUOUS LOADS AT 125%,
 215-5/215-3/230-42 ETC.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-07 Cont ID  
Sent By dpalmer Date 2003-04-07 Time 07:07 Rev Time 0.25
Received By dpalmer Date 2003-04-07 Time 07:07 Sent To  
Notes
2003-04-07 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 THAT WILL AFFECT ELECTRICAL PLANS.
 PLEASE NOTE, AS PER FIRE REVIEW/
 CIRCUITING FOR EM/EXT LTS PER 700-12E
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-08-06 Cont ID  
Sent By nmccray Date 2003-08-06 Time 15:24 Rev Time 0.00
Received By nmccray Date 2003-08-06 Time 15:24 Sent To  
Notes
2003-08-06 00:00:00REVISION DATED 7-31-03 OK SUB# 03051522

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-05-02 Cont ID  
Sent By dpalmer Date 2003-08-04 Time 11:44 Rev Time 0.00
Received By mcarsill Date 2003-05-02 Time 10:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-04-04 Cont ID  
Sent By mcarsill Date 2003-04-04 Time 10:07 Rev Time 0.00
Received By mcarsill Date 2003-04-04 Time 10:07 Sent To  
Notes
2003-04-04 00:00:001) PLEASE INDICATE INTERIOR FINISH FOR
 WALLS AND CEILINGS.
  
 2) COULD NOT LOCATE ANY FIRE ALARM
 EQUIPMENT WITHIN SUITE 402.
  
 3) PLEASE INDICATE LOCATIONS OF
 EMERGENCY LIGHTING EQUIPMENT IN AREAS
 OF CONSTRUCTION OF SUITE 400.
  
 4) ARE THE EXISTING ENTRY DOORS TO
 SUITES 400 AND 402 FIRE RATED AS
 REQUIRED BY FIRE CODE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-31 Cont ID  
Sent By alange Date 2003-07-31 Time 10:31 Rev Time 0.00
Received By alange Date 2003-07-31 Time 10:31 Sent To E
Notes
2003-07-31 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-28 Cont ID  
Sent By shernand Date 2003-04-28 Time 13:43 Rev Time 0.00
Received By shernand Date 2003-04-28 Time 13:43 Sent To  
Notes
2003-04-28 00:00:00COMM BOARD #24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-24 Time 13:32 Rev Time 0.00
Received By sthyng Date 2003-03-24 Time 13:32 Sent To  
Notes
2003-03-24 00:00:00TO COMM BOARD #20

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-04-10 Cont ID  
Sent By pkrauss Date 2003-04-10 Time 14:26 Rev Time 0.20
Received By pkrauss Date 2003-04-10 Time 14:26 Sent To  
Notes
2003-04-10 00:00:00MECHANICAL PLANS NOT SUBMITTED -
 SHOULD RENOVATION REQUIRE RELOCATING OR
 OF DUCT & GRILLES PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719