Plan Review Details - Permit 03031795
Plan Review Stops For Permit 03031795
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-03-09 Cont ID  
Sent By shill Date 2004-03-09 Time 12:11 Rev Time 0.50
Received By shill Date 2004-03-09 Time 12:11 Sent To  
Notes
2004-03-09 00:00:00REVISION OK - LETTER FROM ARCH +-37 FOR
 GARAGE DOOR, GAR DOOR PROD APP AND
 SHUTTER PROD APP

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-03-05 Cont ID  
Sent By shill Date 2004-03-05 Time 12:26 Rev Time 1.00
Received By shill Date 2004-03-05 Time 12:26 Sent To  
Notes
2004-03-05 00:00:00****CORRECTIONS****
  
 REVISION - GARAGE DOOR, SHUTTERS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)DESIGNER OF RECORD IS TO PROVIDE
 DESIGN PRESSURES FOR THE GARAGE DOOR.
 THE ORIGINAL PRODUCT SELECTED HAD A
 DESIGN LIMITATION OF +62/-70.THE
 NEW PROPOSED PRODUCT SUBMITTED HAS A
 LIMITATION OF +-37.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-12-17 Cont ID  
Sent By shill Date 2003-12-17 Time 16:36 Rev Time 0.50
Received By shill Date 2003-12-17 Time 16:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-17 Time 10:34 Rev Time 0.50
Received By shill Date 2003-12-16 Time 16:29 Sent To  
Notes
2003-12-16 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE FS 481.221 AND FAC61G1-16:
 THE SHEETS MUST BE SEALED BY THE
 DESIGNER OF RECORD
  
 THE SIGNATURE IS TO BE A WET SIGNATURE
 NOT A PHOTOCOPY
  
 THE FIRM LICENSE NUMBER IS TO BE ON
 THE PLAN
  
 THE PRINTED NAME OF THE PERSON SEALING
 THE PLAN IS TO BE ON THE TITLE BLOCK.
  
 2.)HAVE THE NEW SHEETS STAMPED BY
 THE HISTORIC PRESERVATION DIVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-05-15 Cont ID  
Sent By csiegber Date 2003-12-11 Time 09:54 Rev Time 0.00
Received By hpiskura Date 2003-05-15 Time 10:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-29 Cont ID  
Sent By hmoser Date 2003-04-12 Time 13:21 Rev Time 0.00
Received By hpiskura Date 2003-04-29 Time 11:53 Sent To  
Notes
2003-04-29 00:00:00THE GARAGE SHOWN ON SHEET A1 DOES NOT
 INDICATE A RIDGE BOARD OR COLLAR BEAMS
 FOR THE ROOF FRAMING.SEE FBC 2309.1.2
 AND 2309.1.7.
  
 PLEASE SHOW A CONSTRUCTION DETAIL FOR
 THE SHED ROOF AND ITS CONNECTION TO THE
 GARAGE.SEE FBC 104.2.
  
 NOTE A SEPARATE PERMIT IS REQUIRED FOR
 THE GARAGE CONSTRUCTION.
  
 PLEASE PROVIDE A CONSTRUCTION DETAIL FOR
 THE FIRE PLACE CHIMNEY.FBC 104.2.
  
 PROVIDE CONSTRUCTION DETAILS FOR THE
 STAIRS.SEE FBC 104.2.
  
 PROVIDE A CONSTRUCTION DETAIL FOR THE
 FRAMED BUMP OUT AT THE STAIRS ON THE
 EAST SIDE.
  
 SHOW A CONNECTION DETAIL FOR THE DORMER
 TO THE TRUSSES.
  
 PLEASE PROVIDE A CALCULATION FOR THE
 ATTIC VENTILATION IN ACCORDANCE WITH
 FBC2309.7.1, INCLUDE THE FREE AREA OF
 THE SCREENED VENTS.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPTATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-12-08 Cont ID  
Sent By dpalmer Date 2003-12-08 Time 07:10 Rev Time 0.75
Received By dpalmer Date 2003-12-08 Time 07:10 Sent To  
Notes
2003-12-08 00:00:00REDLINED FOOTER STEEL REQ'D PER 250.50

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-13 Cont ID  
Sent By csiegber Date 2003-12-01 Time 11:21 Rev Time 1.00
Received By dpalmer Date 2003-05-13 Time 11:08 Sent To P
Notes
2003-05-13 00:00:00REDLINED GFI PROTECTION FOR GARAGE 210-8
 REDLINED GROUNDING ELECTRODE SYSTEM AT
 MAIN SERVICE. 250-50

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-05-12 Time 11:16 Rev Time 0.75
Received By dpalmer Date 2003-04-03 Time 19:48 Sent To P
Notes
2003-04-03 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SHOWING GROUNDING ELEC-
 -TRODE SYSTEM TO FOOTER STEEL AND COLD
 WATER PIPE. PER 250-50
  
 2)NOTE: PANEL IS NOT PERMITTED ON
 SECOND FLOOR AS SHOWN. PLEASE SEE NEC
 ART 225-32 AND ALSO PER LOCAL AMENDMENTS
 230-70, NO MORE THAN 8' OF UNPROTECTED
 CONDUCTOR ARE PERMITTED INSIDE BLDG.
 PLEASE ADJUST LOCATION OF PANEL.
 PLEASE ALSO CLARIFY TYPE OF LV PANEL
 SHOWN BEHIND DOOR? ALARM? RECEPT REQ`D.
  
 3)NOTE: PLEASE SUBMIT AIC RATING FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 PANELS/MAINS/BREAKERS ALL MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT.110-9/
 215-5
  
 4)NOTE: PLEASE SHOW MIN KW RATING FOR
 WASHER PER 220-16. 1.5KW.
  
 5)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED. PER 210-8-A-6
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-12-17 Cont ID  
Sent By csiegber Date 2003-12-17 Time 10:33 Rev Time 0.00
Received By csiegber Date 2003-12-17 Time 10:33 Sent To B
Notes
2003-12-17 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-12-11 Cont ID  
Sent By csiegber Date 2003-12-11 Time 09:54 Rev Time 0.00
Received By csiegber Date 2003-12-11 Time 09:54 Sent To B
Notes
2003-12-11 00:00:00TO ST DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-12-03 Cont ID  
Sent By csiegber Date 2003-12-03 Time 13:38 Rev Time 0.00
Received By csiegber Date 2003-12-03 Time 13:38 Sent To M
Notes
2003-12-03 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-01 Cont ID  
Sent By csiegber Date 2003-12-01 Time 11:21 Rev Time 0.00
Received By csiegber Date 2003-12-01 Time 11:20 Sent To E
Notes
2003-12-01 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-07 Time 09:54 Rev Time 0.00
Received By shernand Date 2003-07-07 Time 09:54 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-12 Cont ID  
Sent By shernand Date 2003-05-12 Time 11:16 Rev Time 0.00
Received By shernand Date 2003-05-12 Time 11:16 Sent To E
Notes
2003-05-12 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-21 Cont ID  
Sent By sthyng Date 2003-03-21 Time 11:04 Rev Time 0.00
Received By sthyng Date 2003-03-21 Time 11:04 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-12-10 Cont ID  
Sent By pkrauss Date 2003-12-10 Time 07:39 Rev Time 0.25
Received By pkrauss Date 2003-12-10 Time 07:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-05-15 Cont ID  
Sent By csiegber Date 2003-12-03 Time 13:38 Rev Time 0.30
Received By pkrauss Date 2003-05-15 Time 08:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-04-12 Cont ID  
Sent By kstevens Date 2003-05-14 Time 17:00 Rev Time 0.50
Received By hmoser Date 2003-04-12 Time 13:21 Sent To B
Notes
2003-04-12 00:00:00PLAN DENIED
 1) MISSING MANUAL (J)
 2) NEED LOCATION OF CONDENSING UNIT
 3) REFER TO SECTION 402.3.1 FBC.(M)
 BATHROOM EXHAUST
 4) NEED RETURN AIR IN DINING ROOM IF YOU
 HAVE DOORS
 5) REFER TO SECTION 606.2.1 SMOKE
 DETECTION
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-07-12 Cont ID  
Sent By kstevens Date 2003-07-12 Time 06:13 Rev Time 0.50
Received By kstevens Date 2003-07-12 Time 06:13 Sent To  
Notes
2003-07-12 00:00:00REVISION OK - CHANGED LAYOUT OF POWDER
 ROOM - PROVISO D.W. TO TIE INTO THE KIT.
 SINK TAILPIECE

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-07-07 Time 09:54 Rev Time 0.33
Received By kstevens Date 2003-05-14 Time 16:59 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-04-09 Cont ID  
Sent By dpalmer Date 2003-05-13 Time 11:12 Rev Time 0.50
Received By jleech Date 2003-04-09 Time 18:23 Sent To M
Notes
2003-04-09 00:00:00DENIED;
 RISER DIAGRAM NOT TO CODE. SEE RED LINES
 ON PLANS
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-21 Time 11:04 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***