| Plan Review Stops For Permit 03031795 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2004-03-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-03-09 |
Time |
12:11 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2004-03-09 |
Time |
12:11 |
Sent To |
|
|
| Notes |
| 2004-03-09 00:00:00 | REVISION OK - LETTER FROM ARCH +-37 FOR | | | GARAGE DOOR, GAR DOOR PROD APP AND | | | SHUTTER PROD APP |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2004-03-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-03-05 |
Time |
12:26 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2004-03-05 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2004-03-05 00:00:00 | ****CORRECTIONS**** | | | | | | REVISION - GARAGE DOOR, SHUTTERS | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | | | | 1.)DESIGNER OF RECORD IS TO PROVIDE | | | DESIGN PRESSURES FOR THE GARAGE DOOR. | | | THE ORIGINAL PRODUCT SELECTED HAD A | | | DESIGN LIMITATION OF +62/-70.THE | | | NEW PROPOSED PRODUCT SUBMITTED HAS A | | | LIMITATION OF +-37. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2003-12-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2003-12-17 |
Time |
16:36 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2003-12-17 |
Time |
16:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2003-12-16 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-17 |
Time |
10:34 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2003-12-16 |
Time |
16:29 |
Sent To |
|
|
| Notes |
| 2003-12-16 00:00:00 | *****CORRECTIONS****** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)SEE FS 481.221 AND FAC61G1-16: | | | THE SHEETS MUST BE SEALED BY THE | | | DESIGNER OF RECORD | | | | | | THE SIGNATURE IS TO BE A WET SIGNATURE | | | NOT A PHOTOCOPY | | | | | | THE FIRM LICENSE NUMBER IS TO BE ON | | | THE PLAN | | | | | | THE PRINTED NAME OF THE PERSON SEALING | | | THE PLAN IS TO BE ON THE TITLE BLOCK. | | | | | | 2.)HAVE THE NEW SHEETS STAMPED BY | | | THE HISTORIC PRESERVATION DIVISION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-05-15 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-11 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-05-15 |
Time |
10:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-04-29 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2003-04-12 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-04-29 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2003-04-29 00:00:00 | THE GARAGE SHOWN ON SHEET A1 DOES NOT | | | INDICATE A RIDGE BOARD OR COLLAR BEAMS | | | FOR THE ROOF FRAMING.SEE FBC 2309.1.2 | | | AND 2309.1.7. | | | | | | PLEASE SHOW A CONSTRUCTION DETAIL FOR | | | THE SHED ROOF AND ITS CONNECTION TO THE | | | GARAGE.SEE FBC 104.2. | | | | | | NOTE A SEPARATE PERMIT IS REQUIRED FOR | | | THE GARAGE CONSTRUCTION. | | | | | | PLEASE PROVIDE A CONSTRUCTION DETAIL FOR | | | THE FIRE PLACE CHIMNEY.FBC 104.2. | | | | | | PROVIDE CONSTRUCTION DETAILS FOR THE | | | STAIRS.SEE FBC 104.2. | | | | | | PROVIDE A CONSTRUCTION DETAIL FOR THE | | | FRAMED BUMP OUT AT THE STAIRS ON THE | | | EAST SIDE. | | | | | | SHOW A CONNECTION DETAIL FOR THE DORMER | | | TO THE TRUSSES. | | | | | | PLEASE PROVIDE A CALCULATION FOR THE | | | ATTIC VENTILATION IN ACCORDANCE WITH | | | FBC2309.7.1, INCLUDE THE FREE AREA OF | | | THE SCREENED VENTS. | | | | | | BEFORE A PERMIT TO CONSTRUCT MAY BE | | | ISSUED IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, THE PERMIT PLANS STAMPED | | | BY THAT OFFICE AND A COPY OF THE PAID | | | RECEIPTATTACHED TO THE PERMIT | | | APPLICATION.CALL 561-233-5025 FOR | | | MORE INFORMATION. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-12-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-12-08 |
Time |
07:10 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2003-12-08 |
Time |
07:10 |
Sent To |
|
|
| Notes |
| 2003-12-08 00:00:00 | REDLINED FOOTER STEEL REQ'D PER 250.50 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-05-13 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-01 |
Time |
11:21 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2003-05-13 |
Time |
11:08 |
Sent To |
P |
|
| Notes |
| 2003-05-13 00:00:00 | REDLINED GFI PROTECTION FOR GARAGE 210-8 | | | REDLINED GROUNDING ELECTRODE SYSTEM AT | | | MAIN SERVICE. 250-50 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-04-03 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-12 |
Time |
11:16 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2003-04-03 |
Time |
19:48 |
Sent To |
P |
|
| Notes |
| 2003-04-03 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SHOWING GROUNDING ELEC- | | | -TRODE SYSTEM TO FOOTER STEEL AND COLD | | | WATER PIPE. PER 250-50 | | | | | | 2)NOTE: PANEL IS NOT PERMITTED ON | | | SECOND FLOOR AS SHOWN. PLEASE SEE NEC | | | ART 225-32 AND ALSO PER LOCAL AMENDMENTS | | | 230-70, NO MORE THAN 8' OF UNPROTECTED | | | CONDUCTOR ARE PERMITTED INSIDE BLDG. | | | PLEASE ADJUST LOCATION OF PANEL. | | | PLEASE ALSO CLARIFY TYPE OF LV PANEL | | | SHOWN BEHIND DOOR? ALARM? RECEPT REQ`D. | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATING FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | PANELS/MAINS/BREAKERS ALL MUST BE RATED | | | FOR THE AVAILABLE FAULT CURRENT.110-9/ | | | 215-5 | | | | | | 4)NOTE: PLEASE SHOW MIN KW RATING FOR | | | WASHER PER 220-16. 1.5KW. | | | | | | 5)NOTE: PLEASE SHOW ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI | | | PROTECTED. PER 210-8-A-6 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2003-12-17 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-17 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-12-17 |
Time |
10:33 |
Sent To |
B |
|
| Notes |
| 2003-12-17 00:00:00 | TO SH DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2003-12-11 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-11 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-12-11 |
Time |
09:54 |
Sent To |
B |
|
| Notes |
| 2003-12-11 00:00:00 | TO ST DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2003-12-03 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-03 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-12-03 |
Time |
13:38 |
Sent To |
M |
|
| Notes |
| 2003-12-03 00:00:00 | TO PK BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-12-01 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-01 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-12-01 |
Time |
11:20 |
Sent To |
E |
|
| Notes |
| 2003-12-01 00:00:00 | TO DP DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-07-07 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-07 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-07 |
Time |
09:54 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-05-12 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-12 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-12 |
Time |
11:16 |
Sent To |
E |
|
| Notes |
| 2003-05-12 00:00:00 | DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-03-21 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-21 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-21 |
Time |
11:04 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2003-12-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-12-10 |
Time |
07:39 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2003-12-10 |
Time |
07:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-05-15 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-03 |
Time |
13:38 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2003-05-15 |
Time |
08:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-04-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-05-14 |
Time |
17:00 |
Rev Time |
0.50 |
| Received By |
hmoser |
Date |
2003-04-12 |
Time |
13:21 |
Sent To |
B |
|
| Notes |
| 2003-04-12 00:00:00 | PLAN DENIED | | | 1) MISSING MANUAL (J) | | | 2) NEED LOCATION OF CONDENSING UNIT | | | 3) REFER TO SECTION 402.3.1 FBC.(M) | | | BATHROOM EXHAUST | | | 4) NEED RETURN AIR IN DINING ROOM IF YOU | | | HAVE DOORS | | | 5) REFER TO SECTION 606.2.1 SMOKE | | | DETECTION | | | PLAN REVIEW BY HAROLD MOSER | | | (561)805-6732 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-07-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-07-12 |
Time |
06:13 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-07-12 |
Time |
06:13 |
Sent To |
|
|
| Notes |
| 2003-07-12 00:00:00 | REVISION OK - CHANGED LAYOUT OF POWDER | | | ROOM - PROVISO D.W. TO TIE INTO THE KIT. | | | SINK TAILPIECE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-05-14 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-07 |
Time |
09:54 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2003-05-14 |
Time |
16:59 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-04-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-05-13 |
Time |
11:12 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2003-04-09 |
Time |
18:23 |
Sent To |
M |
|
| Notes |
| 2003-04-09 00:00:00 | DENIED; | | | RISER DIAGRAM NOT TO CODE. SEE RED LINES | | | ON PLANS | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8369 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2003-03-24 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-21 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
E |
|
| Notes |
|
|