Plan Review Details - Permit 03031740
Plan Review Stops For Permit 03031740
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-28 Cont ID  
Sent By jwitmer Date 2003-04-28 Time 17:26 Rev Time 0.75
Received By jwitmer Date 2003-04-28 Time 17:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-09 Cont ID  
Sent By jwitmer Date 2003-04-09 Time 06:55 Rev Time 1.00
Received By jwitmer Date 2003-04-08 Time 17:50 Sent To  
Notes
2003-04-09 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03031740
 ADD: 205 N DIXIE HWY
 CONT: M.A.C. CONSTRUCTION
 TEL: (305)598-4317
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) 303.1 MULTIPLE OCCUPANCIES: WHAT WILL
 THE REST OF EACH FLOOR BE USED FOR?
  
 2) WHAT TYPE OF STORAGE WILL THIS BE
 USED FOR? IF USED FOR STORAGE OF RECORDS
 HOW WILL THEY BE BUNDLED? ALSO WHAT TYPE
 OF SHELVING SYSTEM WILL BE USED AND HOW
 HIGH WILL THIS UNIT BE IN COMPARISON TO
 THE EXISTING FIRE SPRINKLERS?
  
 3) SECTION 312.2.2 PAPER CARTONS IS
 CONSIDERED S2 HAZARD STORAGE 2 HR WALL.
 WHERE IS THE SEPERATION OCCURING?
  
 4) SHOW HOW EGRESS ISLES WILL BE MAIN-
 TAINED IN THE STORAGE AREAS AND DESIGNAT
 ED?
  
 5) EXPLAIN HOW THE CARD READERS WILL
 WORKFOR EGRESS, IF IN THE STORAGE AREA
 WILL THE GATES SHUT AUTOMATICALLY? HOW
 WILL YOU BE ABLE TO GET OUT?

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-03-26 Cont ID  
Sent By dpalmer Date 2003-03-26 Time 06:09 Rev Time 0.25
Received By dpalmer Date 2003-03-26 Time 06:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-04-25 Cont ID  
Sent By mcarsill Date 2003-04-25 Time 13:43 Rev Time 0.00
Received By mcarsill Date 2003-04-25 Time 13:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-04-04 Cont ID  
Sent By mcarsill Date 2003-04-04 Time 15:46 Rev Time 0.00
Received By mcarsill Date 2003-04-04 Time 15:46 Sent To  
Notes
2003-04-04 00:00:001) WHAT TYPE OF HARDWARE WILL BE
 PRESENT ON THE GATES.
  
 2) HOW WILL THE RECORDS BE STORED.
  
 3) AN EXIT SIGN IS SHOWN ADJACENT TO
 A GATE THAT IS WIDER THEN FOUR FEET.
 PLEASE EXPLAIN RATIONALE.
  
 4) PLEASE EXPLAIN IF ANY SECURITY
 DEVICES WILL AFFECT EXISTING FROM
 THE RECORDS AREA.
  
 5) HOW WILL AISLES BE MAINTAINED WITHIN
 THE LARGE RECORDS STORAGE AREA.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-21 Cont ID  
Sent By shernand Date 2003-04-21 Time 12:48 Rev Time 0.00
Received By shernand Date 2003-04-21 Time 12:48 Sent To  
Notes
2003-04-21 00:00:00COMM BOARD #3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-20 Cont ID  
Sent By sthyng Date 2003-03-20 Time 14:48 Rev Time 0.00
Received By sthyng Date 2003-03-20 Time 14:48 Sent To  
Notes
2003-03-20 00:00:00TO COMM BOARD #51