Plan Review Details - Permit 03031408
Plan Review Stops For Permit 03031408
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-05-19 Cont ID  
Sent By jwitmer Date 2003-05-19 Time 12:24 Rev Time 0.11
Received By jwitmer Date 2003-05-19 Time 12:24 Sent To  
Notes
2003-05-19 00:00:001609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 RE-EVALUATE TRUSS ANCHOR SCHEDULE BEFORE
 FOOR FRAMING INSPECTION.
 JIM WITMER
 (561)805-6715

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-05-16 Cont ID  
Sent By jwitmer Date 2003-05-16 Time 18:08 Rev Time 1.11
Received By jwitmer Date 2003-05-16 Time 18:08 Sent To  
Notes
2003-05-16 00:00:00BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 PROVISO:
 TRUSS SCHEDULE RED LINED TO INDICATE THE
 2003 VALUES ON STRAPS W/ NO ALLOWABLE
 INCREASE AS PER 1609.4.3
 NEW TRUSS ANCHOR SCHEDULE BEFORE ROOF
 FRAMING INSPECTION.
  
 SHUTTERS TO BE UNDER SEPERATE PERMIT!!!
  
 JIM WITMER
 BUILDING PLAN REVIEW
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-05-08 Time 14:55 Rev Time 3.00
Received By jwitmer Date 2003-04-30 Time 07:40 Sent To  
Notes
2003-04-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03031408
 ADD: 10325 SAND CAY LANE
 CONT: G W PURUCKER HOMES
 TEL: (561)775-1170
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 ***NOTE***
 FUTURE POOL
 1803.1.3 EXCAVATION FOR ANY PURPOSE
 SHALL NOT EXTEND WITHIN 1 FT OF THE
 ANGLE OF REPOSE OR NARURAL SLOPE OF THE
 SOIL UNDER ANY FOOTING OR FOUNDATION,
 UNLESS SUCH FOOTING OR FOUNDATION IS
 FIRST PROPERLY UNDERPINNED OR PROTECTED
 AGAINST SETTLEMENT.
  
 1) 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 2)SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.
 A) STORM SHUTTER REPORT REQUIRES SITE
 SPECIFIC ENGINEERING, THE CITY
 FORM FOR SITE SPECIFIC REPORTS IS
 ATTACHED.
 B) CASTLEGATE/ MASONITE DOOR ALSO WILL
 REQUIRE SITE SPECIFIC ENGINEERING!
  
 3) STORM SHUTTERS: HIGHLIGHT THE SYSTEM
 OR THE TYPE OF APPLICATION BEING USED TO
 ANCHOR THE STORM PANELS.
  
 THE SECOND PROBLEM WITH THE SCHEDULE
 THAT IS PROVIDED IS THAT THE 12" SPACING
 TAKEN FOR TOP AND BOTTOM ANCHORING IS
 FOR CONCRETE, NOT MASONARY, RE-EVALUATE
 SPACING.
  
 THE THIRD PROBLEM EGRESS, HOW WILL
 EGGRESS BE HANDLED WITH STORM SHUTTERS?
  
 STORM SHUTTER INSTALL SCHEDULE
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 4) ANCHOR SCHEDULE :
 (TA 22) USP LUGT C2 FI= 500
 (TA 24) USP HC10 USP 2003 CATOLOG,
 USP ISSUED PRODUCTS DELETED FROM
 THE 2003 CATALOG!
  
 BUILDING PLAN REVIW
 JIM WITMER
 (561)805-6715

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-04-09 Cont ID  
Sent By shernand Date 2003-06-20 Time 11:05 Rev Time 0.33
Received By dpalmer Date 2003-04-09 Time 02:20 Sent To P
Notes
2003-04-09 00:00:00********** NOTES REDLINED ***********
  
 PLEASE SEE PLANS FOR THE FOLLOWING
 MISSING ITEMS.
  
 RECEPT IN BEDROOM 210-52
 RECEPT IN KITCHEN 210-52C-3,4,5
 SD OUTSIDE BEDROOM. NFPA-72 8-1.4.2
 EQUIPMENT GROUNDING COND FROM MAIN PANEL
 TO SUB PANEL. 250-122
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-20 Cont ID  
Sent By shernand Date 2003-06-20 Time 11:05 Rev Time 0.00
Received By shernand Date 2003-06-20 Time 11:05 Sent To E
Notes
2003-06-20 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-08 Cont ID  
Sent By shernand Date 2003-05-08 Time 14:55 Rev Time 0.00
Received By shernand Date 2003-05-08 Time 14:55 Sent To B
Notes
2003-05-08 00:00:00JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-19 Cont ID  
Sent By sthyng Date 2003-03-19 Time 09:50 Rev Time 0.00
Received By sthyng Date 2003-03-19 Time 09:50 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-04-12 Cont ID  
Sent By hmoser Date 2003-04-12 Time 13:00 Rev Time 0.50
Received By hmoser Date 2003-04-12 Time 13:00 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-04-12 Cont ID  
Sent By dpalmer Date 2003-04-09 Time 02:26 Rev Time 0.33
Received By hmoser Date 2003-04-09 Time 17:22 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-19 Time 09:50 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***