| 2003-04-30 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03031408 |
| | ADD: 10325 SAND CAY LANE |
| | CONT: G W PURUCKER HOMES |
| | TEL: (561)775-1170 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | ***NOTE*** |
| | FUTURE POOL |
| | 1803.1.3 EXCAVATION FOR ANY PURPOSE |
| | SHALL NOT EXTEND WITHIN 1 FT OF THE |
| | ANGLE OF REPOSE OR NARURAL SLOPE OF THE |
| | SOIL UNDER ANY FOOTING OR FOUNDATION, |
| | UNLESS SUCH FOOTING OR FOUNDATION IS |
| | FIRST PROPERLY UNDERPINNED OR PROTECTED |
| | AGAINST SETTLEMENT. |
| | |
| | 1) 1707.4.4.2 TAPERED BUCKS: |
| | SHALL EXTEND BEYOND THE INTERIOR FACE |
| | OF THE WINDOW OR DOOR FRAME SUCH THAT |
| | FULL SUPPORT OF THE FRAME IS SUPPORTED. |
| | |
| | 2)SITE SPECIFIC ENGINEERING (PRODUCT |
| | APPROVAL) REQUIRES THE WET SIGNATURE, |
| | DATE AND EMBOSSED SEAL OF THE ENGINEER |
| | CERTIFYING THE PRODUCT AND SIGNATURE |
| | AND SEAL OF THE DESIGN PROFESSIONAL |
| | OF RECORD. |
| | A) STORM SHUTTER REPORT REQUIRES SITE |
| | SPECIFIC ENGINEERING, THE CITY |
| | FORM FOR SITE SPECIFIC REPORTS IS |
| | ATTACHED. |
| | B) CASTLEGATE/ MASONITE DOOR ALSO WILL |
| | REQUIRE SITE SPECIFIC ENGINEERING! |
| | |
| | 3) STORM SHUTTERS: HIGHLIGHT THE SYSTEM |
| | OR THE TYPE OF APPLICATION BEING USED TO |
| | ANCHOR THE STORM PANELS. |
| | |
| | THE SECOND PROBLEM WITH THE SCHEDULE |
| | THAT IS PROVIDED IS THAT THE 12" SPACING |
| | TAKEN FOR TOP AND BOTTOM ANCHORING IS |
| | FOR CONCRETE, NOT MASONARY, RE-EVALUATE |
| | SPACING. |
| | |
| | THE THIRD PROBLEM EGRESS, HOW WILL |
| | EGGRESS BE HANDLED WITH STORM SHUTTERS? |
| | |
| | STORM SHUTTER INSTALL SCHEDULE |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | 4) ANCHOR SCHEDULE : |
| | (TA 22) USP LUGT C2 FI= 500 |
| | (TA 24) USP HC10 USP 2003 CATOLOG, |
| | USP ISSUED PRODUCTS DELETED FROM |
| | THE 2003 CATALOG! |
| | |
| | BUILDING PLAN REVIW |
| | JIM WITMER |
| | (561)805-6715 |