| Plan Review Stops For Permit 03031318 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2003-06-10 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2003-06-10 |
Time |
15:32 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2003-05-16 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-05-16 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-05-16 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2003-05-16 00:00:00 | PLANS DATED 5/14/03 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2003-05-09 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-05-09 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-05-09 |
Time |
11:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2003-05-01 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-05-01 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-04-30 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2003-05-01 00:00:00 | PLEASE PROVIDE SPECIFIC CONSTRUCTION | | | DETAILS AND ENGINEERING FOR THE | | | INSTALLATION OF THE NEW DOORS TO BE CUT | | | INTO THE WALL SHOWN AS 105B 105C AND | | | E108. FBC 104.2. | | | | | | SHOW THE WIND DESIGN PRESSURES FOR THE | | | OPENINGS IN THE EXTERIOR WALL SEE FBC | | | 1606.1.7. | | | | | | THE STORAGE AREA REQUIRES A MINIMUM TWO | | | HOUR FIRE RATED SEPARATION.SEE FBC | | | 7041.1. | | | | | | THE SERVICE AREA REQUIRES A ONE HOUR | | | FIRE RATED SEPARATION, (GROUP B SIM | | | 404.5) FROM THE MERCANTILE USE. | | | | | | ALL OF THE FIRE RATED WALLS REQUIRE | | | FIRE RATED OPENING PROTECTION.FBC | | | 705.1.2. | | | | | | EGRESS IS NOT ALLOWED THROUGH THE | | | STORAGE ROOM.SEE FBC1001.1.3. | | | | | | SHEET A3, WHAT IS THE NEW CEILING THAT | | | IS TO MATCH THE EXISTING CEILING HEIGHT? | | | | | | SHEET A4, SHOW SPECIFIC CONSTRUCTION | | | DETAILS AND FASTENINGS FOR THE BRACING | | | OF THE PARTITIONS NOTED UNDER PARTITION | | | NOTES.SEE FBC 104.2. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-04-08 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-04-08 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-04-08 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2003-04-08 00:00:00 | | | | THE PLANS DO NOT HAVE ENOUGH | | | INFORMATION SEE FBC 104.2.1. | | | | | | IT APPEARS NEW DOORS WILL BE CUT INTO | | | THE SERVICE AREA.SHOW A DETAIL. | | | | | | SHOW A CONSTRUCTION DETAIL FOR THE | | | PARTITIONS INCLUDING FIRE DESIGN NUMBER | | | WHERE APPLICABLE. | | | | | | PROVIDE A DOOR AND WINDOW SCHEDULE. | | | | | | SHOW OR NOTE THE CEILING EXISTING OR | | | PROPOSED. | | | | | | PROVIDE A FIRE RATED MIXED OCCUPANCY | | | SEPARATION IN ACCORDANCE WITH FBC 704.1. | | | 1 FOR MERCANTILE AND STORAGE. | | | | | | SHOW THE FIRE RATED SEPARATION IF THIS | | | IS A MULTIPLE TENANT BUILDING. | | | | | | SHEET A1, WHAT DOES THE DOTTED LINE | | | REPRESENT BETWEEN THE RETAIL DISPLAY | | | AND THE WHEEL TIRE STORAGE? | | | | | | SHOW THE HANDICAP ACCESSIBILITY IN | | | ACCORDANCE WITH FBC 11-4.1.6 (2) | | | | | | SHOW THE AIR CONDITIONING WORK WHERE | | | APPLICABLE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2003-05-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-05-16 |
Time |
13:06 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-05-16 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2003-05-16 00:00:00 | *********** NOTES/ PROVISO ******* | | | | | | 1)NOTE: PLEASE SUBMIT PLAN SHOWING ALL | | | NEW CIRCUITING AND CORRELATE WITH PANEL | | | SCHEDULE. | | | 700-12E | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. BEFORE ROUGH. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2003-05-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-05-08 |
Time |
10:24 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-05-08 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2003-05-08 00:00:00 | ************** UNSAT *************** | | | | | | PLEASE SEE THAT THE SAME PLANS HAVE | | | BEEN SUBMITTED AGAIN W/ NO COMMENTS | | | ADDRESSED FROM THE FIRST TWO REVIEWS. | | | | | | PLEASE SEE BZ RECEIPT ATTACHED FOR A | | | FOUR TIME FEE THAT HAS BEEN ADDED FOR | | | PLANS REVIEW AS REQ`D UNDER FS 553.80(2) | | | (B). THIS WAS MENTIONED AND LETTER WAS | | | AATACHED TO PACKAGE LAST TIME PLANS WENT | | | OUT FOR CORRECTIONS. | | | | | | PLEASE SEE NOTES FROM FIRST REVIEW, | | | PLEASE ADDRESS NOTES AND IF THERE ARE | | | ANY QUESTIONS, AS MENTIONS IN THE LAST | | | TWO REVIEWS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2003-04-24 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-05-08 |
Time |
09:55 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2003-04-24 |
Time |
17:59 |
Sent To |
|
|
| Notes |
| 2003-04-24 00:00:00 | **************** UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE NOTES FROM FIRST | | | REVIEW AND ADDRESS. | | | NOT ALL NOTES WERE ADDRESSED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | PLEASE SEE LETTER ATTACHED PER FS 553.80 | | | (2)(B). |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-03-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-03-26 |
Time |
07:56 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-03-26 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2003-03-26 00:00:00 | ********** UNSAT **************** | | | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH SUBMITTED PANEL | | | SCHEDULE. | | | | | | 2)NOTE: PLEASE SEE PLANS, PANEL SCHEDULE | | | SHOWS "SHOW WINDOW" AND RECETPS ARE NOT | | | SHOWN ON PLANS? | | | 210-62 | | | | | | 3)NOTE: PLEASE CLARIFY NEW OR EXSITNG | | | SIGN CIRCUIT PER 600-5. | | | | | | 4)NOTE: PLEASE SHOW ALL CONTINOUS LOADS | | | AT 125%. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2003-06-12 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-06-12 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-06-12 |
Time |
10:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2003-05-08 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-05-08 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-05-08 |
Time |
09:54 |
Sent To |
E |
|
| Notes |
| 2003-05-08 00:00:00 | **************PROVISO******************* | | | 1) LETTER INDICATING SALES OF WHEELS, | | | TIRES AND SHOCKS FOR INSTALLATION ONLY. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT 8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2003-05-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-05-02 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-05-02 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2003-05-02 00:00:00 | 1) PLANS DO NOT INDICATE LOCATIONS | | | OF ILLUMINATED EXIT SIGNS. | | | | | | 2) PLANS AGAIN DO NOT INDICATE IF THE | | | BUILDING IS FIRE SPRINKLER PROTECTED. | | | | | | 3) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION PROVIDED FOR WALLS AND | | | CEILINGS. | | | | | | 4) THE ONE HOUR WALL THAT IS BEING | | | PROPOSED SHALL BE AT LEAST TWO HOUR | | | FIRE RATED WITH ONE AND HALF HOUR | | | OPENING PROTECTIVES. TIRE STORAGE AND | | | RETAIL AREA. | | | | | | 5) NO EXPLANATION ON HOW TIRES WILL | | | BE STORED. | | | | | | 6) PLEASE SHOW DEMISING WALLS AND | | | THEIR RESPECTIVE FIRE RATINGS. | | | | | | 7) NO OCCUPANT LOAD TOTALS PROVIDED. | | | | | | 8) NO DETAILS ON VEHICLE STORAGE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-04-04 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-04-04 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-04-04 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2003-04-04 00:00:00 | 1) PLANS DO NOT INDICATE IF A FIRE | | | SPRINKLER SYSTEMS EXISTS. | | | | | | 2) PLANS DO NOT INDICATE IF ANY FIRE | | | SEPARATION EXISTS BETWEEN THE WHEEL | | | TIRE STORAGE AND THE OFFICES AND RETAIL | | | DISPLAY. | | | | | | 3) PLEASE EXPLAIN TIRE STORAGE. HOW | | | MANY AND HOW WILL THEY BE STORED. | | | | | | 4) NO ILLUMINATED EXIT SIGNS SHOWN | | | ON PLANS. | | | | | | 5) NO OCCUPANT LOAD TOTALS GIVEN. | | | | | | 6) NO WALL DETAILS. | | | | | | 7) NO DOOR DETAILS. | | | | | | 8) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION PROVIDED ON THE PLANS. | | | | | | 9) NO DETAILS ON VEHICLE STORAGE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2003-06-06 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-06 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-06 |
Time |
08:07 |
Sent To |
|
|
| Notes |
| 2003-06-06 00:00:00 | COMM BOARD #25 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-05-16 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-16 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-16 |
Time |
12:06 |
Sent To |
|
|
| Notes |
| 2003-05-16 00:00:00 | COMM BOARD #61 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-05-07 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-07 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-07 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2003-05-07 00:00:00 | COMM BOARD #11 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-04-23 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-23 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-23 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2003-04-23 00:00:00 | COMM BOARD #34 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-03-17 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-17 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-17 |
Time |
16:18 |
Sent To |
|
|
| Notes |
| 2003-03-17 00:00:00 | COMM BOARD #23 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2003-04-08 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-04-08 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2003-06-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-06-12 |
Time |
16:53 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2003-06-12 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2003-06-12 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | | | | 1) SHT MEP-1 SANITARY RISER DIAGRAM & | | | WATER RISER DIAGRAM. FINAL PLAN REVIEW | | | NOTE FOR PLUMBING STATES THAT SANT. AND | | | WATER RISERS SHALL BE SUBMITTED AT TIME | | | OF PLUMBING PERMIT APPLICATION. ALL | | | RISER DIAGRAM SHALL SHOW ALL PIPE SIZES, | | | AND VENTING. SECTION 1-4.2.1 | | | | | | 2) ONLY FIXTURES FROM THE BATHROOM GROUP | | | SHALL DRAIN INTO THE WET VENT FOR THE | | | BATHROOM FIXTURES. ALL OTHER FIXTURES | | | SHALL TIE IN DOWNSTREAM OF THE WET VENT. | | | SECTION 909.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2003-05-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-05-21 |
Time |
10:13 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-05-21 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2003-05-21 00:00:00 | PLANS TO BE SUBMITTED AT TIME OF PLUMB- | | | ING APPLICATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2003-05-09 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-05-09 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2003-05-09 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-04-08 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|