Plan Review Details - Permit 03031232
Plan Review Stops For Permit 03031232
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-06-02 Cont ID  
Sent By sthyng Date 2003-06-02 Time 17:32 Rev Time 1.50
Received By sthyng Date 2003-06-02 Time 17:32 Sent To  
Notes
2003-06-02 00:00:00*****PROVISO*****
 SEPARATE PERMIT REQUIRED FOR
 WINDOWS, FRENCH DOORS AND
 IMPACT PROTECTION.SUBMIT TWO
 LEGIBLE COPIES OF PRODUCT
 APPROVALS.
  
 *****PROVISO******
 SUBMIT APPROVED ZONING SITE
 PLAN MISSING FROM PACKAGE
 BEFORE FIRST INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-05-05 Cont ID  
Sent By sthyng Date 2003-05-05 Time 19:14 Rev Time 1.50
Received By sthyng Date 2003-05-05 Time 19:14 Sent To  
Notes
2003-05-05 00:00:00**********CORRECTIONS************
  
 1.)REFER TO NOTE 5 AND 6 ON PREVIOUS
 CORRECTION LIST REGARDING PRODUCT
 APPROVALS.
  
 2.)NOTE 1 ON PREVIOUS CORRECTION
 NOTICE; NOTICE OF COMMENCEMENT REQUIRED.
  
 3.)REFER TO NOTE 7 ON PREVIOUS
 CORRECTION LIST; CLARIFY FOUNDATION
 DETAILS (SHOULD BE TWO DIFFERENT
 DETAILS).
  
 4.)WINDOW AND DOOR BUCKS ARE TO
 PROVIDE FULL SUPPORT, FBC 1707.4.4.2.
  
 5.)DRAFTSTOPPING REQUIRED; FBC705.3.2.
  
 6.)IMPACT FEES; REFER TO NOTE 14 ON
 PREVIOUS CORRECTION LIST.
  
 7.)PLEASE SIGN BOTH COPIES OF THE
 ENERGY CALCS (OWNER/AGENT LINE).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-17 Cont ID  
Sent By shernand Date 2003-05-05 Time 10:46 Rev Time 4.00
Received By sthyng Date 2003-04-17 Time 07:03 Sent To  
Notes
2003-04-17 00:00:00**********CORRECTIONS************
  
 1.)A NOTICE OF COMMENCEMENT IS TO BE
 FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED; FBC 104.1.9.
  
 2.)THE SITE PLAN, ELEVATIONS, FLOOR
 PLAN, AND SURVEY SUBMITTED (10/4/02,
 JEFFERS AND ASSOCIATES) CONFLICT. SUBMIT
 A SITE PLAN, DRAWN TO SCALE, SHOWING ALL
 PROPOSED IMPROVEMENTS WITH DIMENSIONS
 AND THE CORRECT DISTANCE FROM THE
 PROPERTY LINE.THIS WILL REQUIRE A
 ZONING REVIEW AS THE SITE PLAN APPROVED
 IS INACCURATE.
  
 3.)IMPROVEMENTS MUST COMPLY WITH
 FBC TABLE 600 (NOTE REQUIREMENTS FOR
 EXTERIOR WALLS LESS THAN 10 FEET FROM
 THE PROPERTY LINE).
  
 4.)FBC 1503.4; INDICATE NUMBER AND
 LOCATION OF SCUPPERS AND OVERFLOW
 SCUPPERS AS REQUIRED.
  
 5.)PRODUCT APPROVALS WERE SUBMITTED AS
 LOOSE SHEETS.WHEN RESUBMITTING, STAPLE
 EACH INDIVIDUAL PRODUCT APPROVAL. SUBMIT
 TWO COPIES OF EACH REQUIRED PRODUCT
 APPROVAL.
  
 6.)PRODUCT APPROVALS REQUIRED ARE:
 HURRICANE PROTECTION IF WINDOWS
 ARE NOT IMPACT
 SINGLE HUNG WINDOW
 WINDOW MULLION
 FRENCH DOOR
 ANY OTHER EXTERIOR DOORS NOT
 COVERED UNDER THE FRENCH DOOR
 PRODUCT APPROVAL, IF ANY
  
 7.)THE TYPICAL WALL SECTION SHOWS A
 LEDGER IN THE EARTH TO CARRY EXISTING
 FLOOR.ARE YOU BUILDING A STEM WALL AT
 THAT LOCATION AS SHOWN ON THE PLAN?
 SUBMIT A SEPARATE DETAIL TO CLARIFY.
 INCLUDE LENGTH OF BOLTS ATTACHING THE
 LEDGER TO THE CONCRETE.
  
 8.)GIVE A DETAIL FOR THE TRELLIS.
 INCLUDE ALL ATTACHMENTS.
  
 9.)MARK B ON THE WINDOW SCHEDULE
 AND FLOOR PLAN CONFLICTS WITH THE
 ELEVATION (MARK 6 SHOWS A DOOR).
  
 10.) WINDOWS A AND B ON THE WINDOW
 SCHEDULE APPEAR TO BE LOCATED IN
 HAZARDOUS LOCATIONS PER FBC 2405.2.
 INDICATE AS SAFETY GLASS.
  
 11.)CLEARLY SHOW THE COLUMNS AND
 TRELLIS ON THE FLOOR PLAN AND SITE PLAN,
 INCLUDING DECORATIVE FINISHES.
  
 12.)THE HEADER DETAIL WITH ATTACHMENTS
 IS FOR A 4" WALL; CONFLICTS WITH TYPICAL
 WALL SECTION (6" WALL).
  
 13.)STAIR RAILING MUST COMPLY WITH
 1608.2.2.
  
 14.) BEFORE A PERMIT TO CONSTRUCT MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2003-06-02 Cont ID  
Sent By sthyng Date 2003-06-02 Time 17:41 Rev Time 0.00
Received By sthyng Date   Time   Sent To  
Notes
2003-06-02 00:00:00TOOK ELEC OFF OF PLAN PER ARCH/OWNER/
 CONTRACTOR

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-05-06 Cont ID  
Sent By shernand Date 2003-06-02 Time 14:07 Rev Time 0.50
Received By dpalmer Date 2003-05-06 Time 09:38 Sent To  
Notes
2003-05-06 00:00:00******** UNSAT ********
  
 PLEASE SEE SAME NOTES AS FIRST REVIEW.
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-03 Cont ID  
Sent By sthyng Date 2003-03-25 Time 16:49 Rev Time 0.50
Received By dpalmer Date 2003-04-03 Time 05:33 Sent To B
Notes
2003-04-03 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE CLARIFY CONDUCTORS
 ON SERVICE? SHOWS 3/0` TO 100A AND 50A
 PANEL? PLEASE CLARIFY HOW 3/0'S WILL FIT
 IN LUGS?
 PLAN ALSO SHOWS 350 MCM FOR 150A SERVICE
 ?
 PLEASE CALFIY THE ABOVE.
  
 2)NOTE: PLEASE ALSO SEE 250-66 FOR
 SIZING OF GROUNDING ELECTRODE SYSTEM.
 PER 350MCM'S?
  
 3)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 SHOWING ALL NEW AND EXSITING.215-5
  
 4)NOTE: PLEASE SHOW ALL KITCHEN COUNTER-
 -SPACE OUTLETS AS GFI/ GFI PROTECTED.
 210-8-A-6
  
 5)NOTE: PLEASE SEE PLANS,SOME AREAS ARE
 DARK AND CLEARLY VISABLE. PLEASE REPRINT
 FOR CLARITY. 104.2
  
 6)NOTE: PLEASE SHOW ALL OUTSIDE RECEPTS
 AS GFI.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-06-02 Cont ID  
Sent By shernand Date 2003-06-02 Time 14:07 Rev Time 0.00
Received By shernand Date 2003-06-02 Time 14:06 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 10:46 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 10:46 Sent To B
Notes
2003-05-05 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-25 Cont ID  
Sent By sthyng Date 2003-03-25 Time 16:46 Rev Time 0.00
Received By sthyng Date 2003-03-25 Time 16:46 Sent To E
Notes
2003-03-25 00:00:00TO ELEC IN BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-17 Cont ID  
Sent By sthyng Date 2003-03-17 Time 16:23 Rev Time 0.00
Received By sthyng Date 2003-03-17 Time 16:23 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-25 Cont ID  
Sent By sthyng Date 2003-03-17 Time 16:23 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***