| Plan Review Stops For Permit 03031228 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
12 |
Status |
P |
Date |
2004-11-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-11-17 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2004-11-17 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2004-11-17 00:00:00 | 11-17-04 SUBMITTAL |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
11 |
Status |
P |
Date |
2004-07-26 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-07-26 |
Time |
11:39 |
Rev Time |
0.25 |
| Received By |
alange |
Date |
2004-07-26 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2004-07-26 00:00:00 | SUBMITTAL DATED 6-28-04 OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
P |
Date |
2004-07-01 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-26 |
Time |
11:06 |
Rev Time |
0.25 |
| Received By |
alange |
Date |
2004-07-01 |
Time |
10:17 |
Sent To |
|
|
| Notes |
| 2004-07-01 00:00:00 | REVISION OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2004-05-27 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-30 |
Time |
15:23 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2004-05-27 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2004-05-27 00:00:00 | RECEIVED NEW PRODUCT APPROVALS FOR | | | ROOFING.ALANGE |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2004-05-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-05-20 |
Time |
11:45 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2004-05-20 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2004-05-20 00:00:00 | DETAIL MODIFICATION DATED 4/27/04 | | | FROM GLENN GOLDBERG PE |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2004-01-07 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-18 |
Time |
15:28 |
Rev Time |
1.25 |
| Received By |
jwitmer |
Date |
2004-01-07 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2004-01-07 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 03031228 | | | ADD: 4011 NORTH SHORE DR | | | CONT: DON CLAY | | | TEL: (561)719-0136 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | SUBMITTALS RECEIVED 12/29/03 | | | ACTION: DENIED | | | | | | 1) PLANS, SPECIFICATIONS,REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN | | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | THIS JOB IS A THRESHOLD STRUCTURE, | | | "ALL DOCUMENTS" SUBMITTED BY THE ENGINE- | | | ER SHALL BE "SIGNED, SEALED & DATED" ALL | | | COPIES (3). | | | | | | 1) THE DOCUMENT FROM GLENN GOLDBERG, | | | DATED NOV. 4, 2003 RE: BAR JOIST, STRUC, | | | TURAL STEEL,AND SHOP DRAWINGS IS NOT | | | SIGNED, NOR DATE OF SIGNATURE. | | | | | | 2)THE DOCUMENT RE: MASONARY WALL VERT. | | | POURED CELLS, AGAIN NOT A SIGNATURE ON | | | THE SEAL, AND ONLY TWO COPIES, (3) ARE | | | REQUIRED. | | | | | | 3) DOCUMENT 8X11 1/2 GYM END WALL DETAIL | | | 61G15-23.002 | | | (1) A PROFESSIONAL ENGINEER SHALL SIGN | | | HIS NAME AND AFFIX HIS SEAL TO ALL | | | PLANS, MISSING | | | (2) A TITLE BLOCK ON EACH SHEET CONTAIN- | | | ING THE PRINTED NAME, ADDRESS AND THE | | | NUMBER OF THE ENGINEER OR THE ENGINEER- | | | ING BUSINESS. MISSING | | | | | | 4) VARIOUS REPORTS FROM PEICO, NO DOCU- | | | MENTATION THAT THE ENGINEER OF RECORD | | | HAS REVIEWED AND ACCEPTED THESE REPORTS. | | | THE SECOND ISSUE ONLY ONE COPY IS | | | SIGNED & SEALED. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2003-11-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-29 |
Time |
16:38 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2003-11-12 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2003-11-12 00:00:00 | 11/12/03 JOE IAGROSSI BROUGHT IN 2 COP- | | | IES OF SOIL DENSITY REPORT AND REVISION | | | FROM P.E. | | | FAILED REQUIRES 3 COPIES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2003-09-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-09-26 |
Time |
17:01 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
2003-09-26 |
Time |
17:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2003-07-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-07-23 |
Time |
07:22 |
Rev Time |
6.00 |
| Received By |
jwitmer |
Date |
2003-07-23 |
Time |
07:22 |
Sent To |
|
|
| Notes |
| 2003-07-23 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 03031228 | | | ADD: 4011 NORTH SHORE DRIVE | | | CONT: DON CLAY | | | TEL: (561)683-0609 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1)FL S. S. 553.71(7) " THRESHOLD | | | BUILDING" MEANING ANY BUILDING WHICH IS | | | GREATER THAN (3) STORIES OR 50 FT IN | | | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN | | | CY CLASSIFICATION AS DEINED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS | | | 5,000 SQ FT IN AREA AND AN OCCUPANT | | | CONTENT OF GREATER THAN 500 PERSONS. | | | 105.13.1 THE ENFORCING AGENCY SHALL | | | REQUIRE A SPECIAL INSPECTOR TO PERFORM | | | SRUCTURAL INSPECTIONS ON A THRESHOLD | | | BUILDING PURSUANT TO A STRUCTURAL INSPEC | | | TION PLAN PREPARED BY THE ENGINEER OF | | | RECORD. THE STRUCTURAL INSPECTION PLAN | | | MUST BE SUBMITTED TO THE ENFORCING AGEN- | | | CY PRIOR TO THE ISSUANCE OF A BUILDING | | | PERMIT FOR THE CONSTRUCTION OF A THRESH- | | | OLD BUILDING. THE PURPOSE OF THE SRUCTUR | | | AL INSPECTION PLAN IS TO PROVIDE SPECIF- | | | IC INSPECTION PROCEDURES AND SCHEDULES | | | SO THAT THE BUILDING CAN BE ADEQUATELY | | | INSPECTED FOR COMPLIANCE WITH THE | | | PERMITTED DOCUMENTS. | | | | | | 2) REQUIRED CORRECTION- TITLE SHEET, | | | NOT THE 2002 FLORIDA BUILDING CODE. | | | | | | 3) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORT, SBCCI OR DADE COUNTY | | | REPORT ARE ACCEPTED. MISSING REPORTS: | | | A) EXT. METAL DOOR W/ 1/2 LIGHT (D-1) | | | B) ROOF SHINGLES | | | | | | 4) COMPONENTS & CLADDING SHEET A-23, | | | THE WIND PRESSURES GIVEN ARE LOW,THE PRE | | | SSURES TAKEN FROM TABLE 1606.2B ARE | | | GIVEN WITHOUT ANY IMPORTANCE FACTOR | | | INCREASES. THIS BUILDING IS TO BE DESIGN | | | ED AT A IMPORTANCE FACTOR OF 1.15, ALSO | | | THE MEAN ROOF HEIGHT IS APPROX 21.25'. | | | WHICH ALSO INCREASES PRESSURES. | | | | | | 5) NEW TO THE 2001 FLORIDA BUILDING CODE | | | 2117.1.2 CATHEDRAL END WALLS, AS PER | | | FROM THE BUILDING OFFICIAL, THE PLANS | | | SHALL COMPLY WITH THIS CODE SECTION AT | | | TIME OF PERMITTING. THE CONTRACTOR MAY | | | SUBMIT A REVISION UNDER ALTERNATE MATERI | | | ALS AND METHODS, A PEER REVIEW WILL BE | | | PREFORMED ,WITH AN INDEPENDENT ENGINEER | | | OF THE CITY'S CHOICE AT THE COST TO THE | | | PERMIT HOLDER. | | | | | | 6) TRUSS I-JOIST ITEM (27) FROM SECOND | | | PLAN REVIEW (A,B,D,E,&F HAVE NOT BEEN | | | ADDRESSED. | | | A) MISSING THE MANUFACTURERS SPEC & | | | ROOF SPAN CHART? | | | THE DESIGNER IS SPECING A 11 7/8" | | | TRUSS- JOIST, NO MANUFACTURER SPECED, | | | IF TRUSS-JOIST MC MAC MILLIAN IS THE | | | JOIST TO BE SPECED, A RESIDENTIAL OR COM | | | MERCIAL JOIST? WHAT SERIES OF JOIST, | | | 11 7/8" TJI 15 DF/SP,25DF/SP,35P,35P, | | | 40P OR 40C????????????????????????? | | | B) PROVIDE CURRENT 2003 MANUFACTURERS | | | INFORMATION, IS THIS A FACE MOUNT OR TOP | | | MOUNT UNIT? USING THE 2 SIMPSON HGA10 | | | CLIPS A TOTAL COMBINED RESISTANCE IS | | | 870 LBS., ONLY THE BOTTOM FASTENER HOLES | | | WILL CATCH THE BOTTOM RAIL OF THE I | | | JOIST, AGAIN NO MENTION OF WEB STIFFEN- | | | ERS TO INDICATE HOW TO TRANSFER LOADS. | | | IN THIS CASE ONLY 1/2 THE LOAD OR 435 | | | LBS CAN BE USED. | | | DEPENDING ON THE WIND ZONE LOCATION | | | WORST CASE ZONE#3,21' SPAN@(-37.3X1.15)= | | | -42.8PSF UPLIFTX42SQ FT(TRIBUTARY AREA)= | | | 1797/2=898.8 UPLIFT PER END. | | | D) ARE WEB STIFFENERS REQUIRED? AT WHAT | | | SPACING WILL THE BRIDING BE REQUIRED? | | | E)COMMENT OK | | | F) OUTLOOKERS NOW HAVE WEB STIFNERS BUT | | | NO DETAIL FROM THE MANUFACTURER INDICATI | | | NG THAT THEY ARE TO BE FULL HEIGHT, ON | | | ONE SIDE ONLY ? | | | | | | 7) THE MICRO-LAMB BEAM DETAIL SHEET IS | | | NOT A ENGINEERED SHEET, THE SECOND ISSUE | | | THE DESIGN WAS UNDER THE 1997 SBC @ | | | 110 MPH. THE FLORIDA CODE IS 140 MPH, | | | THIS DESIGN WILL NEED TO BE UPGRADED TO | | | THE PRESENT DAY CODE. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2003-05-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-05-29 |
Time |
14:44 |
Rev Time |
6.50 |
| Received By |
jwitmer |
Date |
2003-05-29 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2003-05-29 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 03031228 | | | ADD: 4011 NORTH SHORE DRIVE | | | CONT: DON CLAY | | | TEL: (561)683-0609 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1) COUNTY AMENDMENT 105.3 (5) SPECIAL | | | INSPECTOR PROGRAM: TO REGISTER WITH DON | | | NEELY, THRESHOLD & RESIDENT INSPECTOR | | | COORDINATOR 805-6665. | | | FL S. S. 553.71(7) " THRESHOLD | | | BUILDING" MEANING ANY BUILDING WHICH IS | | | GREATER THAN (3) STORIES OR 50 FT IN | | | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN | | | CY CLASSIFICATION AS DEINED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS | | | 5,000 SQ FT IN AREA AND AN OCCUPANT | | | CONTENT OF GREATER THAN 500 PERSONS. | | | 105.13.1 THE ENFORCING AGENCY SHALL | | | REQUIRE A SPECIAL INSPECTOR TO PERFORM | | | SRUCTURAL INSPECTIONS ON A THRESHOLD | | | BUILDING PURSUANT TO A STRUCTURAL INSPEC | | | TION PLAN PREPARED BY THE ENGINEER OF | | | RECORD. THE STRUCTURAL INSPECTION PLAN | | | MUST BE SUBMITTED TO THE ENFORCING AGEN- | | | CY PRIOR TO THE ISSUANCE OF A BUILDING | | | PERMIT FOR THE CONSTRUCTION OF A THRESH- | | | OLD BUILDING. THE PURPOSE OF THE SRUCTUR | | | AL INSPECTION PLAN IS TO PROVIDE SPECIF- | | | IC INSPECTION PROCEDURES AND SCHEDULES | | | SO THAT THE BUILDING CAN BE ADEQUATELY | | | INSPECTED FOR COMPLIANCE WITH THE | | | PERMITTED DOCUMENTS. | | | 105'X72'=7560 SQ FT, 7650@ 15=504 OCC. | | | NET AND STAGE NOT INCLUDED. | | | | | | NOTE: IMPACT FEES PAID UNDER PERMIT | | | # 9908 0492 APRIL 4, 2000. REV# 00-12234 | | | | | | 2) TABLE 803.3 MINIMUM INTERIOR FINISH | | | CLASSIFICATION; PROVIDE INFORMATION | | | BASED ON INTERIOR FINISH REQUIREMENTS | | | BASED ON OCCUPANCY. PROVIDE INFORMATION | | | PER ROOM OR EGRESS REQUIREMENTS. | | | | | | 3) PLANS INDICATE THE USE OF FIRE SPRINK | | | LERS, AS WELL AS THE BUILDING AREA FOR | | | EDUCATIONAL USAGE (TABLE 600) NO FIRE | | | SPRINKLER PLANS ARE INCLUDED IN THIS | | | PACKAGE. | | | | | | 4)FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | SHEET A-1, THE PLANS INDICATE A LOT OF | | | 3'-0" DOORS DRAWN IN AT 2'-0". FLORIDA | | | ACCESSIBILITY, REQUIRED MANEUVERING | | | CLEARENCES AT DOORS ARE NOT MET, THERE | | | IS NO 5'-0" TURNING RADIUS IN THE BATH- | | | ROOMS, OR EVEN ENOUGH ROOM TO GET A | | | WHEELCHAIR PAST THE ONE ENTRY DOOR | | | CLOSEST TO THE WATER CLOSET. PLANS INDIC | | | ATE A "JUNIOR SIZE " WATER CLOSET IS TO | | | BE USED, PROVIDE ADDITIONAL INFORMATION. | | | PROVIDE PATH OF ACCESSIBILITY. | | | THE 2'-0" WIDE DOOR IS ALSO AND ISSUE | | | AT THE WATER CLOSET AT THE SHOWERS. | | | | | | P-1 DRAWINGS INDICATE STALL DOORS TO BE | | | 24" WIDE VS 32" REQUIRED. | | | | | | 5) PROVIDE INFORMATION FOR AN ACCESSIBLE | | | DINING ROOM? 11.5.4 ARE THE TABLES BENCH | | | TYPE WITH FIXED SEATING, OR ARE CHAIRS | | | REMOVABLE? | | | | | | 6)11-4.1.2 VERTICAL ACCESSIBILITY, | | | NOTHING IN THIS CODE SHALL BE CONSTRUED | | | TO RELIEVE THE OWNER OF ANY BUILDING, | | | STRUCTURE OR FACILITY FROM THE DUTY TO | | | PROVIDE VERTICAL ACCESSIBILITY TO ALL | | | LEVELS ABOVE OR BELOW THE OCCUPIAABLE | | | GRADE LEVEL. PROVIDE MANUFACTURERS SPEC | | | ON CHAIRLIFT. IS THIS MODEL PERMANENT OR | | | PORTABLE? IF PORTABLE WHERE WILL IT BE | | | STORED WHEN NOT REQUIRED? | | | | | | 7) REQUIRED CORRECTIONS? TITLE SHEET, | | | 2002 FLORIDA BUILDING CODE. | | | | | | 8) 2111.1.9 1 1/2" RECESS A WATERSTOP IS | | | REQUIRED FOR EXTERIOR WALLS. PLANS ARE | | | TO INDICATE THIS. IF SLAB IS POURED AND | | | A WATERSTOP IS NOT PRESENT HOW WILL THIS | | | BE CORRECTED? | | | | | | 9) MISSING WINDOW SCHEDULE, SHEET A-24 | | | INDICATES THE USE OF EITHER CASEMENT OR | | | HORIZONTAL ROLLING WINDOWS? PRODUCT TEST | | | ING REPORTS SUBMITTED ARE FOR SINGLE | | | HUNG WINDOWS. THERE IS NO WAY TO INTER- | | | PET IF MULLIONS ARE TO BE REQUIRED? | | | | | | 10)FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORT, SBCCI OR DADE COUNTY | | | REPORT ARE ACCEPTED.MISSING REPORTS: | | | A) WINDOW MULLIONS | | | B) ROOFING ASSEMBLIES, FLAT AND SLOPED | | | ROOFING MATERIALS | | | | | | 11) COMPONENTS & CLADDING SHEET A-23 | | | THE PRESSURES GIVEN UNDER THIS CHART ARE | | | AT AN IMPORTANCE FACTOR OF (1). THIS | | | BUILDING IS TO BE DESIGNED AT A IMPORT- | | | ANCE FACTOR OF 1.15!!! PRESSURES INDI- | | | CATED ARE LOW!!!! | | | | | | GYMNASIUM: | | | 12) 1012.1.2 EGRESS DOORS SHALL BE SIDE | | | SWINGING TYPE. DOORS SHALL SWING IN THE | | | DIRECTION OF EGRESS FOR THE FOLLOWING: | | | DOUBLE GYMNASIUM DOORS SWING IN THE | | | WRONG DIRECTION, OR EACH LEAF SWING IN | | | THE DIRECTION OF TRAVEL. | | | | | | 13) FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | SHEET A-5 DETAIL (3) DOESN'T INDICATE | | | THE SIZE OF THE ANCHOR BOLTS DIA OR | | | LENGHT? | | | | | | 14) NEW 2001 FBC 2117.1.2 CATHEDRAL END- | | | WALLS, GABLE ENDWALLS ADJACENT TO CATHED | | | RAL CEILINGS SHALL BE CONTINIOUS FROM | | | THE UPPERMOST FLOOR TO THE CEILING | | | DIAPHRAM OR TO THE ROOF DIAPHRAM. | | | | | | 15) TRUSS I JOIST:ITEM (27) FIRST REVIEW | | | (A-F) HAVE NOT BEEN ADDRESSED! | | | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | | ON THE APPLICATION, PLANS, OR ATTACHED | | | SEPARATELY. WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | TEL: (561)659-8096 X 8412 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2003-04-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-04-11 |
Time |
15:25 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
2003-04-11 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2003-04-11 00:00:00 | | | | CONTINUATION OF BUILDING PLAN REVIEW | | | DATED 3/11/2003 | | | COMMENTS: | | | 18) FL BLDG 1909.3 (EXEPTION# 2) | | | CONCRETE SLABS ON GRADE CONTAINING 6X6/ | | | W1.4XW1.4 WELDED WIRE REINFORCEMENT | | | FABRIC LOCATED IN THE MIDDLE TO THE | | | UPPER 1/3RD OF THE SLAB SHALL BE SUP- | | | PORTED BY APPROVED MATERIALS OR SUPPORTS | | | AT SPACING NOT TO EXCEED 3 FT OR IN | | | ACCORDANCE WITH MANUFACTURER'S SPEC. | | | | | | 19) SHEET A-10, A-11 & A-12EXTERIOR | | | WALLS ARE MISSING THE 1 1/2" RECESS | | | FOR BLOCK WORK AT FLOOR LEVEL. | | | | | | 20) MISSING A WINDOW SCHEDULE, SHEET | | | A-24, WHAT TYPE OF WINDOWS WILL BE USED | | | WHERE. | | | | | | 21)FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORT, SBCCI OR DADE COUNTY | | | REPORT ARE ACCEPTED. MISSING REPORTS: | | | A) WINDOW MULLIONS | | | B) ROOFING ASSEMBLIES, FLAT ROOF & | | | SLOPED ROOFS | | | | | | 22) 1707.4.5.1 MULLIONS OCCURRING | | | BETWEEN INDIVIDUAL WINDOW AND GLASS | | | DOOR ASSEMBLIES. TESTING REPORTS ARE | | | REQUIRED BY AN APPROVED TESTING | | | LABORATORY OR BE ENGINEERED. | | | | | | 23) 1707.4.5.2 MULLIONS SHALL BE DESIGN- | | | ED TO TRANSFER THE DESIGN PRESSURE LOADS | | | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES | | | TO THE ROUGH OPENING SUBTRATE. | | | | | | | | | 24) GYMNASIUM 105'X72'=7560 SQ FT | | | OCCUPANT LOAD: 7560 @ 15= 504 ALLOWABLE | | | TABLE 1606 : | | | BUILDINGS AND STRUCTURES WHERE THE OCCU- | | | PANT LOAD IS 300 OR MORE IN ONE ROOM. | | | IMPORTANCE FACTOR 1.15 CORRECT: COVER- | | | SHEET. | | | | | | 25) FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | SHEET A-5 DETAILS DO NOT INDICATE | | | WHAT SIZE DIA OR LENGHT ANCHOR BOLTS | | | THAT ARE TOBE EMBEDDED INTO THE CONCRETE | | | NOR IS THERE INFORMATION ON THE BOLTS | | | THAT ARE TO GO THROUGH THE BOTTOM PLATE | | | THROUGH THE WOOD ARCH. SHEET A-16 GIVES | | | A DETAIL FOR THE BOTTOM PLATE BUT NOT EN | | | OUGH INFORMATION, WHAT SIZE WELDS ARE | | | TO BE USED? | | | | | | 26) NEW 2001 FBC! 2117.1.2 CATHEDRAL | | | ENDWALLS, GABLE ENDWALLS ADJACENT TO | | | CATHEDRAL CEILINGS SHALL BE CONTINUOUS | | | FROM THE UPPERMOST FLOOR TO THE CEILING | | | DIAPHRAM OR TO THE ROOF DIAPGRAM. | | | | | | 27) TRUSS I JOIST: | | | A) MISSING THE MANUFACTURERS SPECS & | | | ROOF SPAN CHARTS? | | | B) PROVIDE CURRENT 2003 MANUFACTURERS | | | INFORMATION FOR FRAMING CONNECTION, TOP | | | MOUNT VERSES FACE MOUNT. | | | C) PROVIDE INFORMATION FROM THE TRUSS | | | JOIST MANUFACTURER THAT THE I-JOIST DO | | | NOT NEED TO SIT PERPENDICULAR BUT | | | PERPENDICULAR TO THE SLOPE OF THE ROOF. | | | I-JOIST ACTING AS PURLINS. HOW WILL THE | | | ACCENTRIC LOADING OF THE BOTTOM CORD | | | BE HANDLED SINCE DETAIL 10/A-15 THE | | | OUTLOOKERS DO NOT ATTACH TO THE BOTTOM | | | CORD OF THE I-JOIST? ALSO HOW ARE THE | | | F-2 VALUES TRANSFERED INTO THE OUTTOOK- | | | ERS, A H-10 CONNECTOR SPECIFIED IN | | | DETAIL 01/A-18?WHAT MANUFACTURER? | | | D) ARE WEB STIFFENERS REQUIRED? AT WHAT | | | SPACING WILL THE SOLID BRIDGING BE | | | INSTALLED? | | | E) PLANS INDICATE A VENTED SOFFIT AS RE- | | | QUIRED 2309.7.1.HOW WILL THE INTERIOR | | | JOIST BE VENTED SINCE THIS DESIGN IS | | | SOLID WOOD JOIST NOT OPEN WEB TRUSSES? | | | F) OUTLOOKERS WHAT TYPE OF CONNECTION | | | WILL BE MADE TO THE I-JOIST? | | | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | | ON THE APPLICATION, PLANS, OR ATTACHED | | | SEPARATELY. WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | TEL: (561)659-8096 X 8412 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-04-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-04-11 |
Time |
13:15 |
Rev Time |
6.75 |
| Received By |
jwitmer |
Date |
2003-04-11 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2003-04-11 00:00:00 | | | | | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 03031228 | | | ADD: 4011 NORTH SHORE DR | | | CONT: DON CLAY CONSTRUCTION | | | TEL: (561)683-0609 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | ACTION: DENIED | | | | | | 1) COUNTY AMENDMENTS: 105.3(5) | | | SPECIAL INSPECTOR PROGRAM, BUILDINGS > | | | 20,000 SQ. FT. | | | SPECIAL INSPECTOR TO REGISTER WITH | | | DON NEELY THE SPECIAL INSPECTOR & | | | THRESHOLD INSPECTOR COORDINATOR AT | | | 659-6700 X6665 | | | | | | NOTE PROVIDE (3) COPIES OF DOCUMENTS FOR | | | THE PERMITED SET OF PLANS. | | | | | | | | | 2)FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | THE PLANS ARE NOT CLEAR AS TO THE FOUNDA | | | TION, AREAL PHOTOS INDICATE AN EXISTING | | | SLAB. IS THIS SLAB TO BE REMOVED? IF NOT | | | THIS SLAB HAS TO BE CERTIFIED BY THE | | | ENGINEER THAT IT WILL ACCEPT THE LOADS | | | BEING IMPOSED ON IT! | | | | | | 3) FL BLD CODE 1804.2.2 QUESTIONABLE | | | SOILS, WHERE THE BEARING CAPACITY IS | | | NOT DEFINETLY KNOWN OR IS IN QUESTION. | | | SOILS REPORT SIGNED/ SEALED BY SOILS | | | ENGINEER. | | | | | | 4) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 5)BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | IF COUNTY IMPACT FEES WERE PAID UNDER | | | THE OLD CANCEALED PERMIT, THE PLANS | | | STILL NEED TO SUBMITTED TO THE COUNTY | | | FOR REVIEW AND STAMPING! | | | | | | 6)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 7) TABLE 803.3 MINIMUM INTERIOR FINISH | | | CLASSIFICATION; PROVIDE INFORMATION | | | BASED ON INTERIOR FINISH REQUIREMENTS | | | BASED ON OCCUPANCY | | | | | | 8)1005.4 EMERGENCY ESCAPE AND RESCUE | | | OPENINGS, | | | (2) EVERY ROOM OR SPACE GREATER THAN | | | 250 FT USED FOR CLASSROOM OR OTHER ED- | | | UCATIONAL PURPOSES OR NORMALLY SUBJECT | | | TO STUDENT OCCUPANCY, AND EVERY ROOM | | | SUBJECT TO CLIENT OCCUPNCY SHALL NOT | | | HAVE NOT LESS THAN ONE OUTSIDE WINDOW | | | FOR EMERGENCY RESCUE, SEE EXCEPTIONSALSO | | | EXCEPTION #1 AN AUTOMATIC FIRE | | | SPRINKLER SYSTEM, PLANS INDICATE THERE | | | SHALL BE ONE, BUT NO PLANS WERE SUBMIT- | | | TED? | | | | | | 9)FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | SHEET A-1 THE PLANS INDICATE ALOT OF THE | | | 3'-0" DOORS BEING DRAWN IN AS A 2'-0" | | | DOOR, THIS MAY CAUSE PROBLEMS WITH THE | | | REQUIRED MANEUVERING CLEARENECES AT | | | DOORS, (11-4.13.6) DOORS 27 & 42 DO NOT | | | HAVE THE REQUIRED 18" ON THE LATCH SIDE! | | | THE DOORWAYS DRAWN IN AS 2'-0" MAY ALSO | | | RUN INTO THESE SAME PROBLEMS, PLEASE | | | REVIEW? | | | | | | 10) ACCESSIBLE MEANS OF EGRESS, | | | 11-4.1.3(8), (9) | | | ALL CLASSROOMS HAVING EXTERIOR DOORS & | | | LANDINGS SHOULD BE MADE TO BE ACCESSIBLE | | | LANDINGS NO LOWER THAN 1/2" BELOW THE | | | INTERIOR FINISH FLOOR. SHEET A-3 DETAIL | | | 11/A5 A CUT SECTION THRU A EXTERIOR DOOR | | | AND STOOP. STOOP ELEVATION MISSING FROM | | | THE CUT SECTION? SHEET A-10 NOTES: INDIC | | | ATE SLOPED SIDEWALKS TO MEET ADA GUIDE- | | | LINES, THIS SHOULD ALSO INCLUDE THE | | | EXTERIOR DOOR LANDINGS. LANDINGS NEED TO | | | BE BIG ENOUGH FOR TURNING RADIUS, AND | | | THE DRADE NEEDS TO BE TO THE TOP OF THE | | | LANDING FOR ACCESSIBILITY, WITH POSITIVE | | | SLOPE AWAY FROM THE BUILDING. | | | | | | 11) BUILDING SIGNAGE: 11-4.1.3(16)(A)(B) | | | SIGNS WHICH DESIGNATE PERMANENT ROOMS & | | | SPACESSHALL COMPLY WITH 11-4.30.1, | | | 11-4.30.4, 11-4.30.(5-6). | | | B) OTHER SIGNS WHICH PROVIDE DIRECTION | | | TO OR INFORMATION ABOUT FUNCTION SPACES | | | OF THE BUILDING SHALL COMPLY WITH: | | | 11-4.30.1, 11-4.30.2, 11-4-30.3 & 11-4.5 | | | | | | 12) PROVIDE INFORMATION FOR AN ACCESS- | | | IBLE DINING ROOM 11.5.4. | | | | | | 13) 11-4.1.2 VERTICAL ACCESSIBILITY, | | | NOTHING IN THIS CODE SHALL BE CONSTRUED | | | TO RELIEVE THE OWNER OF ANY BUILDING, | | | SSTRUCTURE OR FACILITY FROM THE DUTY TO | | | PROVIDE VERTICAL ACCESSIBILITY TO ALL | | | LEVELS ABOVE OR BELOW THE OCCUPIAABLE | | | GRADE LEVEL. | | | PROVIDE INFORMATION FOR VERTICAL | | | LIFT ONTO THE STAGE. | | | | | | 14)11-4.22.2 DOORS. ALL DOORS TO | | | ACCESSIBLE TOLIET ROOMS SHALL COMPLY | | | WITH 11-4.13. DOORS SHALL NOT SWING INTO | | | CLEAR FLOOR SPACE REQUIRED FOR ANY | | | FIXTURE. | | | ROOM # 35 GIRLS HANDICAPPED STALL OVER | | | LAPPING DOOR SWING INTO CLEARTHE CLEAR | | | FLOOR SPACE. | | | | | | 15) 1021.4(NEW UNDER 2001 FBC) DOORS | | | THAT SWING INTO AN EXIT ACCESS CORRIDOR | | | SHALL BE RECESSED TO PREVENT INTERFE- | | | ENCE WITH CORRIDOR TRAFFIC: ANY DOORS | | | NOT RECESSED SHALL OPEN 180 DEGREES TO | | | STOP AGAINST THE WALL. DOORS IN ANY POSI | | | TION SHALL NOT REDUCE THE REGUIRED CORRI | | | DOR WIDTH BY MORE THAN ONE HALF. | | | | | | 16) REQUIRED CORRECTIONS: | | | A) TITLE SHEET 2002 FLORIDA BUILDING | | | CODE | | | B) SHEET A-5, REFRENCE TO STANDARD | | | BUILDING CODE | | | C) SHEET A-5 BASIC WIND VELOCITY 110 | | | | | | 17)COVER SHEET MISSING : | | | FL. BLD CODE 1606.1.7 THE FOLLOWING | | | INFORMATION RELATED TO WIND SHALL BE | | | SHOWN ON THE CONSTRUCTION DRAWINGS, | | | 1)- BASIC WIND SPEED, MPH | | | 2)- WIND IMPORTANCE FACTOR, & BUILDING | | | CATEGORY | | | 3)- WIND EXPOSURE | | | 4)- INTERNAL PRESSURE COEFFICIENT, | | | 5)- COMPONENTS & CLADDING, THE DESIGN | | | WIND PRESSURES IN TERMS OF PSF. | | | MISSING # (4) INTERNAL PRESSURE COEF. | | | | | | NOTE: PLAN REWIEW ALLOWS FOR 200 | | | LINES, ANOTHER"BUILDING PLAN REVIEW" | | | WILL NEED TO BE OPENED TO CONTINUE | | | COMMENTS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2004-07-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-07-28 |
Time |
18:09 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-07-28 |
Time |
18:09 |
Sent To |
|
|
| Notes |
| 2004-07-28 00:00:00 | *********** UNSAT ************** | | | | | | 1)NOTE: PLANS NEED TO BE REVISED BY THE | | | ENGINEER OF RECORD. | | | FS 471 | | | REVIEW FOR CODE COMPLIANCE WILL BE DONE | | | AT THAT TIME. | | | IF NEW ENGINEER, PLEASE FOLLOW FS 471- | | | .027 FOR SUBMITTING ALL NEW PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2003-09-26 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-26 |
Time |
11:22 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-09-26 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2003-09-26 00:00:00 | REDLINED NOTES, RISER SHOWS ONLY 2-RUNS | | | OD SEC`S, NOTES MENTION 3-RUNS? | | | PLEASE CORRELATE AND SEE 310.16 | | | THIS DOES NOT REQUIRE PLANS TO BE | | | REVISED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2003-07-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-07-28 |
Time |
15:29 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2003-07-28 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2003-07-28 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE NOTES FROM TWO REVIEW | | | -S. PLEASE CORRELATE RISER DIAGRAMS. | | | MP IS STILL SHOWN ON RISER AS "800A MAIN | | | S". | | | PLANS NOW SHOW A MAIN DISCONNECT OUTSIDE | | | AND NOT ENOUGH INFORMATION FOR THIS MAIN | | | PLEASE SHOW SIZING ETC. | | | PANEL MP MAY BE A MCB PANEL, AS LONG | | | AS THERE IS NO MORETHAN 8' OF UNPROTECT | | | -ED CONDUCTORS INSIDE THE BLDG. | | | 210-70 OF LOCAL AMENDMENTS. ALL OTHER | | | INFORMATION PER, 215-5,240-3, 230-2, | | | 230-71,,, | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | THAT MY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. | | | | | | PLEASE SEE ATTACHED LETTER PER FS 553.80 | | | (2)(B). PLEASE NOTE, THIS NOTE AND | | | LETTER WAS ATTACHED TO LAST SET OF NOTES | | | AS A NOTICE TO DESIGN PROFESSIONALS. | | | PLEASE NOTE, A 4X FEE FOR PLAN REVIEW | | | PORTION OF PERMIT FEES WILL BE ACCESSED | | | AND DUE UPON NEXT SUBMITTAL. | | | PLEASE ALSO SEE COMMENTS FROM FIRE, | | | BLDG, AND PLUMB FOR REPEAT COMMENTS. | | | BZ # 228657 $11,100.00 | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2003-05-08 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2003-05-20 |
Time |
12:40 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-05-08 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2003-05-08 00:00:00 | ************ UNSAT *************** | | | | | | PLEASE SEE THAT THE SAME ELECTRICAL | | | PLANS WERE SUBMITTED ABCK FOR REVIEW.? | | | | | | PLEASE SEE ORIGINAL REVIEW COMMENTS AND | | | PLEASE ADDRESS. | | | PLEASE TAKE OUT ANY OLD/ VOIDED SHEETS | | | AND INSERT NEW SHEETS FOR COMPLETE SETS | | | FOR REVIEW AND STAMPING. OLD/VOIDED | | | SHEETS MAY BE SUBMITTED SEPARATE. | | | | | | PLEASE SEE ATTACHED LETTER FOR PLAN | | | REVIEW AND RESPECT TO DESIGN PROFESSION- | | | -AL. FS 553.80(2)(B) | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-03-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-03-27 |
Time |
08:22 |
Rev Time |
1.50 |
| Received By |
dpalmer |
Date |
2003-03-27 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2003-03-27 00:00:00 | ************** UNSAT ************* | | | | | | 1)NOTE: PLEASE CLARIFY MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MDP AND | | | SUB-PANELS. SIZE PER 250-122 | | | | | | 2)NOTE: PLEASE CORRELATEMDP AND RISER. | | | RISER MENTIONS A 800A MAINS AND MDP | | | SHOWS MLO? | | | | | | | | | PLEASE CORRECT THE ABOVE FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | [email protected] | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2003-07-17 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2003-07-17 |
Time |
10:55 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2003-07-17 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2003-07-17 00:00:00 | PASSED : | | | 1. SEE PERMIT # 03071082 FOR UNDERGROUND | | | UTILITIES AND SITE WORK. | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2003-05-06 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2003-05-06 |
Time |
10:35 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2003-05-06 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2003-05-06 00:00:00 | FAILED: | | | 1. PLEASE REFER TO PREVIOUS REVIEW | | | COMMENTS DATED 3-18-03 (SEE ATTACHED) | | | 2. CIVIL/SITE PLANS MUST BE APPROVED BY | | | PUBLIC UTILITIES FOR ALL THE CONNECTIONS | | | TO CITY SERVICES AND FOR LOCATION OF | | | BACKFLOW, METERS, ETC. | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2003-03-18 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2003-03-18 |
Time |
09:13 |
Rev Time |
2.00 |
| Received By |
mamini |
Date |
2003-03-18 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2003-03-18 00:00:00 | FAILED: | | | 1. PLEASE NOTE THAT A SEPARATE PERMIT | | | APPLICATION AND FEES FOR UNDERGROUND | | | UTILITIES AND SITE WORK WILL BE REQUIRED | | | 2. RIGHT OF WAY PERMIT FROM CITY | | | ENGINEERS OFFICE FOR ALL THE WORK WITHIN | | | PUBLIC RIGHT OF WAY WILL BE REQUIRED, | | | 659-8040. | | | 3. SURVEYING PLAN BY O'BRIEN, SUITER & | | | O'BRIEN, INC. SHOWS 12' OF UTILITY EASE- | | | MENT AT NORTH SIDE IN PROPERTY ALONG THE | | | CANAL, PLEASE NOTE THAT NO CONSTRUCTION | | | OR PLANTING TREE IN THIS AREA IS | | | PERMITTED. | | | 4. MAIN ENTRANCE; FROM CURB-CUT/ HEADER | | | CURB TO THE PROPERTY LINE MUST BE | | | CONSTRUCTED USING 6" CONCRETE PER CITY | | | REQUIREMENT. | | | 5. PLEASE PROVIDE STORM WATER CALC., | | | SUBMITTAL SHOULD INCLUDE PERVIOUS, | | | IMPERVIOUS, AND TOTAL SITE AREA CALC.. | | | 6. PLEASE SUBMIT A COPY OF SFWMD PERMIT. | | | 7. POLLUTION PREVENTION PLANS MUST BE | | | INSTALLED IN FIELD PRIOR TO ANY EARTH | | | WORK, NOTE TO GC. | | | IF ANY QUESTION PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2003-10-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-10-02 |
Time |
07:23 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-10-02 |
Time |
07:23 |
Sent To |
|
|
| Notes |
| 2003-10-02 00:00:00 | 1) POST INDICATOR VALVE CUT SHEET | | | PROVIDED WITH PLANS. | | | | | | 2) DOCUMENTATION PROVIDED WITH | | | REGARDS TO MAIN EXIT WITH PLANS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2003-08-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-08-14 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-08-14 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2003-08-14 00:00:00 | 1) A 15 FOOT OPENING IS SHOWN ON | | | NORTHSHORE DRIVE. A 20 FOOT OPENING | | | IS REQUIRED FOR FIRE AND PARAMEDICAL | | | EQUIPMENT. | | | | | | 2) POST INDICATOR VALVES ARE REQUIRED. | | | | | | 3) ELECTRONIC SWITCHES ARE REQUIRED | | | ON THE BACKFLOW DEVICE. | | | | | | 4) SHEET S-7 FIRE HYDRANT LOCATION | | | IS IN A DIFFERENT LOCATION THAN | | | PREVIOUS DRAWING. | | | | | | 5) A KNOX-BOX WILL BE REQUIRED. | | | | | | 6) SHEET A-2 NEAR CLASSROOM # 7 IS | | | MISSING AN EXTERIOR DOOR. | | | | | | 7) IS THE FDC PLANNED TO BE INSTALLED | | | NEAR THE FENCED PLAY AREA. | | | | | | 8) PLEASE INDICATE LOCATION OF MAIN | | | ENTRY AND EGRESS DOORS. PLEASE | | | DEMONSTRATE THAT 50 PERCENT OF THE | | | TOTAL OCCUPANT LOAD CAN EXIT VIA | | | THE MAIN ENTRY OR EGRESS DOORS. | | | | | | 9) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE HOOD, DUCT, AND SUPPRESSION | | | SYSTEM. | | | | | | 10) TEN INCH TREADS APPEAR TO BE PRESENT | | | ON THE STAGE. TEN INCH TREADS DO NOT | | | MEET CODE REQUIREMENTS. | | | | | | 11) BUILDING ADDRESS REQUIRED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2003-06-03 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-06-03 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-06-03 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2003-06-03 00:00:00 | 1) PROVIDE FIRE PROTECTION PLAN WITH | | | FLOW DATA FOR FIRE SPRINKLER SYSTEM. | | | | | | 2) PLAN ONLY SHOW EMERGENCY LIGHTING IN | | | GYMNASIUM. | | | | | | 3) A KNOX-BOX ENTRY SYSTEM WILL BE | | | REQUIRED. | | | | | | 4) PLEASE SEE OTHER PROFESSIONAL REVIEW | | | COMMENTS. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT 8497 | | | 805-6722 OR 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-04-17 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-04-17 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-04-17 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2003-04-17 00:00:00 | 1) PLEASE PROVIDE FIRE PROTECTION AND | | | LIFE SAFETY PLAN INDICATING OCCUPANT | | | LOADS AND TRAVEL DISTANCES TO EXITS. | | | | | | 2) WHAT IS THE CLASSIFICATION OF THE | | | INTERIOR FINISHES. | | | | | | 3) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR THE INSTALLATION OF FIRE SPRINKLER | | | SYSTEM. | | | | | | 4) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR THE KITCHEN HOOD AND SUPPRESSION | | | SYSTEM. | | | | | | 5) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR THE FIRE ALARM SYSTEM. | | | | | | 6) A KNOX-BOX ENTRY SYSTEM WILL BE | | | REQUIRED. | | | | | | 7) FIRE DEPARTMENT ACCESS REQUIRES A 20 | | | FEET WIDE (MIN) DRIVEWAY FOR ENTRY. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT 8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2004-07-26 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-26 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-26 |
Time |
11:22 |
Sent To |
E |
|
| Notes |
| 2004-07-26 00:00:00 | TO DP DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2004-07-26 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-26 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-26 |
Time |
11:06 |
Sent To |
B |
|
| Notes |
| 2004-07-26 00:00:00 | TO AL DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2004-06-30 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-30 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-30 |
Time |
15:23 |
Sent To |
B |
|
| Notes |
| 2004-06-30 00:00:00 | TO AL DESK/SUBMITTAL/LETTER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2004-05-27 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-27 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-05-27 |
Time |
13:54 |
Sent To |
M |
|
| Notes |
| 2004-05-27 00:00:00 | TO PK BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2004-05-18 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-18 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-05-18 |
Time |
15:28 |
Sent To |
B |
|
| Notes |
| 2004-05-18 00:00:00 | TO JW DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2004-04-20 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-20 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-04-20 |
Time |
12:41 |
Sent To |
M |
|
| Notes |
| 2004-04-20 00:00:00 | TO PK BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2003-12-29 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-29 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-12-29 |
Time |
16:38 |
Sent To |
B |
|
| Notes |
| 2003-12-29 00:00:00 | TO JW DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2003-09-26 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-23 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-26 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2003-09-23 00:00:00 | TO COMM BD #39 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-07-17 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-17 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-17 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2003-07-17 00:00:00 | COMM BOARD #29 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-05-05 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-05 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-05 |
Time |
12:30 |
Sent To |
|
|
| Notes |
| 2003-05-05 00:00:00 | COMM BOARD #13 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-04-18 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-18 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-18 |
Time |
09:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-03-14 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-14 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-14 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2003-03-14 00:00:00 | COMM BOARD #34 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2004-05-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-05-28 |
Time |
14:26 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2004-05-28 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2004-05-28 00:00:00 | PROVISO: | | | 1.ADDITIONAL PERMITS REQUIRED FOR HOOD | | | AND FIRE SUPPRESSION PER 2001 FBC(M) | | | 506.1. | | | | | | 2.PLEASE NOTE, DUCTS PENETRATING A | | | WALL WITH A FIRE RESISTANCE RATING SHALL | | | HAVE A FIRE DAMPER OR COMPLY WITH THE | | | EXCEPTION PER 2001 FBC(M) 607.1.2 AND | | | 607.1.3. | | | | | | 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | IN NORMALLY OCCUPIED AREAS PER NFPA 90A | | | 6.4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
F |
Date |
2004-05-04 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-27 |
Time |
13:54 |
Rev Time |
1.20 |
| Received By |
pkrauss |
Date |
2004-05-04 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2004-05-04 00:00:00 | DENIED: | | | FUTURE PLAN SUBMITTALS SHALL BE LISTED | | | AS REVISIONS & NOT SUBMITTALS. | | | | | | 1.REVISION SUBMITTED IS NOT DONE BY | | | THE ENGINEER OF RECORD. PLEASE PROVIDE | | | LETTER BY THE ENGINEER OF RECORD OR | | | OWNER INIDCATING THE RELEASE OF SAID | | | PLANS. | | | | | | 2.DUCT SMOKE DETECTORS REQUIRED IN | | | UNITS THAT HAVE THE DESIGN CAPACITY | | | GREATER THAN 2,000 CFM.PLEASE | | | INDICATE DUCT SMOKE DETECTORS ON THE | | | PLAN. | | | | | | 3.ORIGINAL PLANS SUBMITTED INDICATE | | | CORRIDORS HAVING A 1 HR FIRE RESISTANCE | | | RATING.NO FIRE DAMPERS ARE INDICATED | | | ON THE NEW/REVISED PLAN.PLEASE CLARIFY | | | | | | 4.NEW ENGINEER SHALL COMPLY WITH FS | | | 471.025 & THE FAC 61G15-23.002.PROVIDE | | | TITLE BLOCK, INDIACATE LICENSE NUMBER AS | | | WELL AS DATE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2003-10-03 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-20 |
Time |
12:41 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2003-10-03 |
Time |
07:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2003-07-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-07-29 |
Time |
07:32 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2003-07-29 |
Time |
07:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2003-05-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-05-23 |
Time |
10:56 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2003-05-23 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2003-05-23 00:00:00 | AS PER MEETING W/DON CLAY, NO CHEMICALS | | | TO BE STORED IN STORAGE ROOMS, DOORS | | | WILL BE LOUVERED. | | | | | | AHU IN CORRIDOR DO NOT PENETRATE A RATED | | | CEILING.FIRE DAMPERS ADDED TO OTHER | | | AREAS. | | | | | | HOOD & FIRE SUPPRESSION PERMITS TO BE | | | APPLIED FOR SEPARATELY & PLANS SUBMITTED | | | AT THE TIME OF APPLICATION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2003-05-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-05-13 |
Time |
15:30 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2003-05-13 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2003-05-13 00:00:00 | DENIED: | | | | | | COMMENTS NOT ADDRESSED FROM FIRST REVIEW | | | PLEASE PROVIDE RESPONSE TO COMMENTS. | | | SEE COMMENTS FROM PREVIOUS REVIEW | | | ATTACHED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-04-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-04-10 |
Time |
13:00 |
Rev Time |
3.00 |
| Received By |
pkrauss |
Date |
2003-04-10 |
Time |
12:28 |
Sent To |
|
|
| Notes |
| 2003-04-10 00:00:00 | PLEASE CLARIFY THE FOLLOWING INFORMATION | | | | | | 1.PLEASE INDICATE WHAT WILL BE STORED | | | IN THE STORAGE ROOMS SHOWN ON PLAN SHEET | | | A-1. | | | | | | 2.PLAN SHEET A-1 INDICATES TWO STORAGE | | | ROOMS.THE MECHANICAL PLAN DOES NOT | | | INDICATE ANY TYPE OF VENTILATION.WILL | | | THIS BE ACCOMPLISHED BY NATURAL MEANS | | | OR MECHANICALLY?PLAN DOES NOT SHOW ANY | | | LOUVERED DOORS OR LOUVERS.SEE 2001 | | | FBC(M) 404. | | | | | | 3.PLAN SHEET M-2 NOTE H, AHU CEILING | | | MOUNT IN FIRE RATED ENCLOUSURE.FIRE | | | DAMPER NOT INDICATED ON PLAN SHEET M-1 | | | OR IN THE NOTES.PLEASE NOTE, ENCLOSURE | | | SHALL BE LARGE ENOUGH TO ACCESS FOR | | | SERVICE AND MAINTENANCE. | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPPRESSION & WALK-IN COOLERS. | | | PLEASE PROVIDE PLANS WITH PERMIT | | | APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2003-10-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-10-02 |
Time |
08:33 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-10-02 |
Time |
08:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2003-07-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-07-28 |
Time |
11:44 |
Rev Time |
4.50 |
| Received By |
kstevens |
Date |
2003-07-26 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2003-07-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | FBC-2001 AMENDMENTS, CHAPTER | | | ONE, ADMINISTRATION | | | CODE. | | | | | | 1) FROM PREVIOUS REVIEW: COMMENT NUMBERS | | | TO STAY THE SAME FOR CLAIRTY. | | | (2) SUBMIT CALCULATIONS FOR MINIMUM FIX- | | | TURES. NO INFORMATION IS GIVEN FOR THE | | | GYMNASIUM AREA. WHERE ARE THE FACILITIES | | | FOR THE GYM? WILL THE PATRONS BE ABLE TO | | | USE THE FACILITIES IN THE SCHOOL AREA? | | | POTTY PARITY PER SECTION 403.1.1 INDICA- | | | TES THAT RESTROOM WHICH ARE OPEN TO THE | | | PUBLIC MUST HAVE A RATIO OF 3 TO 2 WATER | | | CLOSETS PROVIDED FOR WOMEN AS THE COM- | | | BINED TOTAL OF WATER CLOSETS AND URNALS | | | PROVIDED FOR MEN. | | | 3) CALCULATIONS FOR PRIMARY AND SECOND- | | | ARY ROOF DRAINS. ROOF AREAS "I" & "J" | | | DO NOT SHOW THE ROOF AREA OF THE GYM | | | THAT DRAINS ONTO THESE AREAS. ALSO NO | | | MENTION OF VERTICAL WALLS IS SHOWN IN | | | CALCULATIONS PROVIDED FOR ANY AREAS. | | | SECTIONS 1106 & 1107 AND ALL SUBSECTIONS | | | *COVER SHEET INDICATES 31 3" ROOF DRAINS | | | BUT THERE ARE ONLY 26 3" ROOF DRAINS AND | | | 6 2" ROOF DRAINS. PLEASE CLAIRFY. | | | 4) PLEASE SUBMIT A DETAIL FOR THE SCUPP- | | | ERS. SHOW HEIGHT AND WIDTH FOR OPENING | | | AND INDICATE HEIGHT OFF ROOF TO FLOW | | | LINE PER SECTION 1511.6.4.3 OF THE BLDG. | | | CODE. | | | 6) PLEASE PROVIDE A DETAIL FOR EACH | | | TOILET ROOM. SHOW CLEAR FLOOR SPACE, | | | TURNING CIRCLE 11-4.16.2, HEIGHT 4.16.3, | | | GRAB BARS 4.16.4, FLUSH CONTROLS 4.16.5. | | | SHOW CLEAR FLOOR SPACE 11-4.19.3, HEIGHT | | | & CLEARANCES 4.19.2, EXPOSED PIPES AND | | | SURFACES 4.19.4, AND FAUCETS 4.19.5 | | | 7) DETAILS FOR TOILET ROOM BETWEEN CLASS | | | ROOMS 1 & 2, AND 12 & 13 REQUIRED. SEE | | | ABOVE COMMENT. | | | 8) YOU MUST COMPLETE A WAIVER FOR THE | | | USE OF CHILDREN'S FIXTURES IN THE SCHOOL | | | THE ACCESSIBILITY STANDARD IS ONLY A | | | GUIDLINE AND HAS NOT BEEN ADOPTED BY THE | | | DEPT. OF JUSTICE. THE WAIVER SHALL BE | | | SUBMITTED TO DTATE OF FLA. DEPT. OF COMM | | | AFFAIRS. PLEASE SUBMIT CUT SHEETS FOR | | | CHILDRENS FIXTURES. | | | 9) SHT P-1 PLEASE PROVIDE DETAILS FOR | | | TEACHERS LOUNGE SINK. SHOW COMPLIANCE | | | WITH SECTION 11-4.24 AND ALL SUBSECTIONS | | | 13) TOILET ROOM FOR PRESIDENT SHALL BE | | | ADAPTABLE - DETAILS REQUIRED - CLEAR | | | FLOOR SPACE, TURNING CIRCLE, AND SHOW | | | BACKING FOR GRAB BARS AND INDICATE THE | | | HEIGHT AND WIDTH OF BACKING. 11-4.22 | | | A) NEW COMMENT... PLANS INDICATE 1/8" | | | PER FOOT ON SHEET A-1 BUT MEASURMENTS DO | | | NOT REFLECT THIS SCALE. PLEASE CLAIRFY | | | B) ALL RED LINE CORRECTIONS SHALL BE IN- | | | ITALED AND DATED BY ARCHITECT/ENGINEER | | | OF RECORD. | | | *********WHEN RESUBMITTING PLANS******** | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2003-06-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-06-04 |
Time |
10:31 |
Rev Time |
5.00 |
| Received By |
kstevens |
Date |
2003-06-03 |
Time |
18:06 |
Sent To |
|
|
| Notes |
| 2003-06-04 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | FBC-2001 ADMIN. CODE, CHAPTER | | | ONE & AMENDMENTS. | | | | | | 1) PLANS SHALL BE ROUTED TO THE PALM | | | BEACH HEALTH UNIT DIVISION OF ENVIRON- | | | MENTAL HEALTH, 901 EVERNIA ST. WPB | | | (561) 355-3018. PLANS SHALL BE STAMPED | | | PRIOR TO RESUBMITTING. FBC-2001 101.4.7 | | | 2) SUBMIT CALCULATIONS FOR MINIMUM FIX- | | | TURES PER TABLE 1003.1 (BLDG CODE), AND | | | TABLE 403.1 (PLMG. CODE). SHOW SQUARE | | | FOOTAGE FOR EACH OCCUPANCY AND REQUIRED | | | FIXTURES FOR EACH. | | | 3) SUBMIT CALCULATIONS FOR PRIMARY AND | | | SECONDARY ROOF DRAINS. SHOW 1/2 AREA OF | | | ALL VERTICAL WALLS, INCLUDING PARAPETS. | | | SHOW ALL AREAS OF ROOFS THAT DRAIN ON TO | | | THE ROOF FROM ABOVE. (GYM ROOF) SECTIONS | | | 1106, 1107, AND ALL SUBSECTIONS. | | | *COVER SHEET INDICATES 31 3" ROOF DRAINS | | | BUT THERE ARE ONLY 26 3" ROOF DRAINS AND | | | 6 2" ROOF DRAINS. PLEASE CLAIRFY. - IN- | | | DICATE SQUARE FOOTAGE BEING DRAINED BY | | | EACH ROOF DRAIN. | | | 4) PLEASE SUBMIT A DETAIL FOR THE SCUPP- | | | ERS. SHOW HEIGHT AND WIDTH FOR OPENING | | | AND INDICATE HEIGHT OFF ROOF TO FLOW | | | LINE PER SECTION 1511.6.4.3 OF THE BLDG | | | CODE. | | | 5) PLEASE SUBMIT A STORM RISER DIAGRAM, | | | SHOWING ALL PIPE SIZES AND INDICATE | | | WHERE THEY TERMINATE. | | | 6) ALL PUBLIC AND COMMON AREA TOILET | | | ROOMS SHALL COMPLY WITH 11-4.22 AND ALL | | | SUBSECTIONS. PLEASE PROVIDE A DETAIL FOR | | | EACH TOILET ROOM. SHOW TURNING CIRCLE & | | | CLEAR FLOOR SPACE. (SEE FIGS. 3,28,29 & | | | 32). SECTION 11-4.1.3(11) | | | 7) PLEASE SUBMIT A DETAIL FOR TOILET | | | ROOM BETWEEN CLASSROOMS #1 & #2 AND FOR | | | TOILET ROOM BETWEEN CLASSROOMS #12 & #13 | | | SHOW ALL DIMENTIONS FOR TOILET ROOMS. | | | TOILET ROOMS SHALL COMPLY WITH 11-4.22 | | | 8) YOU MUST COMPLETE A WAIVER FOR THE | | | USE OF CHILDREN'S FIXTURES IN THE SCHOOL | | | THE ACCESSIBILITY STANDARD IS ONLY A | | | GUIDLINE AND HAS NOT BEEN ADOPTED BY THE | | | DEPT. OF JUSTICE. THE WAIVER SHALL BE | | | SUBMITTED TO STATE OF FLA. DEPT. OF COMM | | | AFFAIRS. (PLEASE SUBMIT CUT SHEETS FOR | | | CHILDRENS FIXTURES, | | | 9) SHT P-1 PLEASE PROVIDE DETAIL FOR | | | TEACHERS LOUNGE SINK. SHOW COMPLIANCE | | | WITH SECTION 11-4.24 AND ALL SUBSECTIONS | | | 10) SHT P-5 SHUT OFF VALVES REQUIRED FOR | | | ALL WALL HYDRANTS. SECTION 606.2(2) | | | PLEASE SHOW ON WATER RISER DIAGRAM. | | | 11) SHT P-5 WATER HEATERS, PRV DISCHARGE | | | LINE SHALL NOT HAVE ANY TRAPPED SECTIONS | | | SECTION 504.7.1 - WATER RISER STILL IN- | | | DICATES THAT THE LINES WILL BE TRAPPED. | | | PLEASE SHOW DETAIL FOR T/P LINES SHOWING | | | HOW THEY WILL BE PIPED TO COMPLY WITH | | | CODE REFERENCE. ALSO INDICATE THAT | | | THERMAL EXPANSION CONTROL PER 607.3.2 | | | IS BEING ADDRESSED. SUBMIT DETAIL. | | | 12) RPZ BACKFLOW REQUIRED ON WATER SERV. | | | PLEASE INDICATE ON WATER RISER DIAGRAM | | | SHT P-5. SECTION 608.13.2 & UTILITY ORD. | | | 13) TOILET ROOM IN PRESIDENTS SHALL BE | | | EITHER ACCESSIBLE (11-4.22) OR ADAPTABLE | | | PLEASE INDICATE ON PLANS. IF ADAPTABLE, | | | DETAIL REQUIRED SHOWING 5' TURNING | | | CIRCLE AND BACKING AS REQUIRED IN SEC. | | | 11-4.22 | | | 14) SHT A-1 PLEASE INDICATE HOW THE | | | TOILET IN THE ISOLATION ROOM WILL BE | | | ACCESSIBLE. | | | 15) PLEASE SHOW ALL CLEANOUTS REQUIRED | | | BY SECTIONS 708.3.1, 708.3.3, & 708.3.5 | | | ON THE SANITARY RISER DIAGRAM. | | | ********WHEN RESUBMITTING PLANS********* | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-04-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-04-12 |
Time |
05:56 |
Rev Time |
2.25 |
| Received By |
kstevens |
Date |
2003-04-11 |
Time |
18:56 |
Sent To |
|
|
| Notes |
| 2003-04-12 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) PLANS SHALL BE ROUTED TO THE PALM | | | BEACH HEALTH UNIT DEVISION OF ENVIRON- | | | MENTAL HEALTH, 901 EVERNIA ST. WPB | | | (561) 355-3018 | | | 2) GREASE TRAP SHALL BE SIZED BY RODNEY | | | COMPO, ENVIRONMENTAL COMPLIANCE, UTILITY | | | ORD #2938-96. (561) 837-4074 | | | 3) SUBMIT CALCULATIONS FOR MINIMUM FIX- | | | TURES PER TABLE 1003.1 (BLDG. CODE) AND | | | TABLE 403.1 (PLUMBING CODE) | | | 4) SUBMIT CALCULATIONS FOR PRIMARY AND | | | SECONDARY ROOF DRAINS. SHOW 1/2 AREA OF | | | ALL VERTICAL WALLS INCLUDING PARAPETS. | | | SHOW AREAS OF ROOFS THAT DRAIN ON TO | | | ROOF FROM ABOVE. SHOW LOCATION OF | | | SECONDARY DRAINS OR SCUPPERS. SUPPLY A | | | DETAIL OF SCUPPERS (IF USED). SECTIONS | | | 1106, 1107, (PLUMBING) AND SECTIONS | | | 1503.4 & 1503.4.2, (BLDG). | | | 5) SHT A-27 PLEASE PROVIDE DETAILS THAT | | | SHOW CENTER OF W/C TO WALL (18" REQD), | | | HEIGHT OF W/C OFF FINISHED FLOOR (17" TO | | | 19" REQD), CLEAR FLOOR SPACE FOR ALL | | | HDCP FIXTURES, 5' TURNING CIRCLE ECT. | | | 6) SHT P-1 PLEASE PROVIDE DETAIL FOR | | | TEACHERS LOUNGE SINK. SHOW COMPLIANCE | | | WITH 11-4.24 AND ALL SUBSECTIONS. | | | 7) SHT P-3 JANITOR SINK SHALL BE ON THE | | | GREASE WASTE SYSTEM. (NOT SHOWN) | | | 8) SHT P-5 SHUT OFF VALVES REQUIRED FOR | | | ALL WALL HYDRANTS. SEC 606.2(2) | | | 9) SHT P-5 WATER HAMMER ARRESTORS ARE | | | REQUIRED FOR QUICK CLOSING VALVES. SEC | | | 604.9. (ICE MAKER, DISHWASHER, WASH | | | MACHINE IF PROVIDED). | | | 10) SHT P-5 WATER HEATERS, PRV LINE | | | SHALL NOT HAVE ANY TRAPPED SECTIONS. SEC | | | 504.7.1. ALSO THERMAL EXPANSION CONTROL | | | REQUIRED AT WATER HEATER. 607.3.2 | | | 11) RPZ BACKFLOW REQUIRED ON WATER | | | SERVICE. | | | ********WHEN RESUBMITTING PLANS******** | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2003-05-20 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2003-05-20 |
Time |
12:40 |
Rev Time |
1.00 |
| Received By |
mmclean |
Date |
|
Time |
|
Sent To |
E |
|
| Notes |
|
|