Plan Review Details - Permit 03031048
Plan Review Stops For Permit 03031048
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-09-30 Cont ID  
Sent By csiegber Date 2003-10-06 Time 14:23 Rev Time 1.00
Received By rmcdouga Date 2003-09-30 Time 16:43 Sent To  
Notes
2003-09-30 00:00:00PLANS RESTAMPED EXCEPT FOR SHEET A7
 WHICH HAS ELECTRICAL REVISIONS.9-30-03

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-24 Cont ID  
Sent By csiegber Date 2003-09-25 Time 15:04 Rev Time 3.00
Received By rmcdouga Date 2003-04-24 Time 08:26 Sent To  
Notes
2003-04-24 00:00:00BUILDING PROVISO
  
 1) SUBMIT A SOIL BORING TEST REPORT AS
 REQUIRED BY FBC 1804.2.2 PRIOR TO
 POURING THE FOUNDATION.
  
 2) SUBMIT A SIGNED,SEALED AND DATED
 LETTER FROM THE DESIGNER OF RECORD OF
 THE STRUCTURE TO ACCOMPANY THE SITE
 SPECIFIC ENGINEERING FOR THE SINGLE AND
 DOUBLE OUTSWING GLAZED DOORS, APPROVING
 THEM FOR USE IN THE STRUCTURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-09 Cont ID  
Sent By dpalmer Date 2003-04-23 Time 16:41 Rev Time 4.00
Received By rmcdouga Date 2003-04-09 Time 13:43 Sent To  
Notes
2003-04-09 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE A SOIL BORING TEST REPORT AS
 REQUIRED BY FBC 1804.1.1.
  
 4) REVISE GENERAL NOTE #1 ON C1. THE
 CONSTRUCTION IS TYPE VI.
  
 5) INDICATE THE INTERNAL PRESSURE
 COEFFICENT ON C1 WITH THE DESIGN
 CRITERIA. SEE FBC 1606.1.7.
  
 6) THE NOTE ON THE BOLLARD ON A2 REFERS
 TO DETAIL #54. THERE IS NO DETAIL #54 ON
 THE PLANS.
  
 7) THE PLANS HAVE TWO SHEETS MARKED A4
 AND NO SHEET A5.
  
 8) INDICATE ON THE PLANS THAT THE WALL
 BETWEEN THE GARAGE AND THE CONDITIONED
 SPACE IS INSULATED AND THE DOOR IN THIS
 WALL IS SOLID CORE AS REQUIRED BY FBC
 CHAPTER 13.
  
 9) THE DETAILS LOCATED ON A4 AND THEIR
 ID TAGS ARE LABELED INCORRECTLY AS A3.
  
 10) THE WINDLOAD SCHEDULE ON A3 LISTS A
 SH36 WINDOW AT THE DEN AND THE PLANS
 SHOW TWO SH26 WINDOWS MULLED TOGETHER.
  
 11) THE SLIDING GLASS DOOR AND DOOR
 DETAILS ON THE SECOND A4 SHEET SPECIFIES
 1X4 OR 2X4 BUCKS. IF 1X BUCKS ARE USED
 THE DOOR ASSEMBLY IS REQUIRED TO BE
 ANCHORED THROUGH THE BUCK AND INTO THE
 STRUCTURAL SUBSTRATE BY FBC 1707.4.4.2.
 THE 2X BUCKS ARE REQUIRED TO EXTEND
 BEYOND THE INTERIOR FACE OF THE DOOR
 FRAME. PLEASE REVISE THESE DETAILS.
  
 12) PROVIDE THE MANUFACTURER'S SPECS.
 AND UL LISTING INFORMATION FOR THE ONE
 HOUR FIRE RATED GLASS BLOCK.
  
 13) THE OPENING SIZE SHOWN ON THE PLANS
 FOR THE GLASS BLOCK EXCEEDS THE MAXIMUM
 OPENING SIZE ALLOWED BY THE PRODUCT
 APPROVAL.
  
 14) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - DOUBLE OUTSWING GLAZED DOORS WITH
 SIDELITES
 - SINGLE OUTSWING GLAZED DOOR
  
 15) THE OVAL WINDOW IN THE WALL AT A
 FORTY-FIVE DEGREE ANGLE TO THE ZERO LOT
 LINE VIOLATES TABLE 600. NO OPENINGS ARE
 ALLOWED IN WALL WITHIN 3 FEET OF THE
 PROPERTY LINE. THE PORTION OF REAR WALL
 THAT IS OVER TWENTY TO THIRTY FEET FROM
 PROPERTY LINE IS LIMITED TO 60% OF WALL
 AREA ALLOWED AS OPENINGS. THIS IS
 EXCEEDED BY THIS PLAN. PLEASE CORRECT.
  
 16) THE PRODUCT APPROVAL FOR THE STORM
 PANELS FROM SBCCI HAS BEEN REPLACED BY
 REPORT # 2229A. GENERAL NOTE 6 ON SHEET
 ONE OF THE DRAWINGS REQUIRES THE
 ORIGINAL SIGNATURE, DATE AND EMBOSSED
 SEAL ON EACH PERMIT COPY OF THIS REPORT.
  
 17) THE OPENING SIZES ON THE STORM PANEL
 SCHEDULE DO NOT CORRESPOND TO THE SIZES
 ON THE PLANS FOR SEVERAL OF THE OPENINGS
 THE MAXIMUM ALLOWABLE SPANS FOR THE
 PANELS ARE EXCEEDED FOR SEVERAL OF THE
 OPENINGS LISTED IN THE SCHEDULE BASED ON
 THE NEGATIVE PRESSURES THAT ARE GIVEN.
 SEE TABLE 1 AND 2 ON THE PRODUCT
 APPROVAL DRAWINGS. PLEASE CORRECT.
  
 18) THE ORIGINAL SIGNATURES OF THE
 PERSONS CERTIFYING CODE COMPLIANCE WITH
 THE FLORIDA ENERGY CODE IS REQUIRED ON
 THE ENERGY CALCULATION FORMS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-12-11 Cont ID  
Sent By dpalmer Date 2003-12-11 Time 08:37 Rev Time 0.33
Received By dpalmer Date 2003-12-11 Time 08:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-12-03 Cont ID  
Sent By csiegber Date 2003-12-10 Time 15:45 Rev Time 0.33
Received By dpalmer Date 2003-12-03 Time 07:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-23 Cont ID  
Sent By csiegber Date 2003-11-26 Time 15:49 Rev Time 0.25
Received By dpalmer Date 2003-04-23 Time 16:41 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-28 Cont ID  
Sent By shernand Date 2003-04-18 Time 16:17 Rev Time 0.25
Received By dpalmer Date 2003-03-28 Time 06:47 Sent To P
Notes
2003-03-28 00:00:00************ UNSAT ******************
  
 1)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250-66, PLEASE SEE MIN
 SEC`S PER 310-15
  
 2)NOTE: SD NOT PERMITTED IN KITCHEN,
 NFPA-72 8-1.4.2
  
 3)NOTE: PLEASE SHOW MIN SIZE FOR WASHER
 CIRCUIT 220-16B. SHOWN AS 1.0
  
 4)NOTE: PLEASE SHOW AND INDENTIFY
 LOCATION OF PANELS.
  
 PLEASE VERIFY SIZE OF SERVICE WITH
 CONTRACTOR. SHOWN AS 400A`S W/ 152A`S??
 THIS IS JUST A NOTE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-12-10 Cont ID  
Sent By csiegber Date 2003-12-10 Time 15:45 Rev Time 0.00
Received By csiegber Date 2003-12-10 Time 15:45 Sent To E
Notes
2003-12-10 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-11-26 Cont ID  
Sent By csiegber Date 2003-11-26 Time 15:49 Rev Time 0.00
Received By csiegber Date 2003-11-26 Time 15:49 Sent To E
Notes
2003-11-26 00:00:00TO BT DESK/REV
 TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-10-06 Cont ID  
Sent By csiegber Date 2003-10-06 Time 14:23 Rev Time 0.00
Received By csiegber Date 2003-10-06 Time 14:23 Sent To B
Notes
2003-10-06 00:00:00TO RM DESK/RESTAMP CORRECTIONS MADE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-09-25 Cont ID  
Sent By csiegber Date 2003-09-25 Time 15:03 Rev Time 0.00
Received By csiegber Date 2003-09-25 Time 15:03 Sent To B
Notes
2003-09-25 00:00:00TO RM/RE-STAMP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-29 Cont ID  
Sent By shernand Date 2003-04-29 Time 15:06 Rev Time 0.00
Received By shernand Date 2003-04-29 Time 15:06 Sent To M
Notes
2003-04-29 00:00:00PK DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-18 Cont ID  
Sent By shernand Date 2003-04-18 Time 16:16 Rev Time 0.00
Received By shernand Date 2003-04-18 Time 16:16 Sent To E
Notes
2003-04-18 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-14 Cont ID  
Sent By sthyng Date 2003-03-14 Time 10:04 Rev Time 0.00
Received By sthyng Date 2003-03-14 Time 10:04 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-04-30 Cont ID  
Sent By pkrauss Date 2003-04-30 Time 11:05 Rev Time 0.30
Received By pkrauss Date 2003-04-30 Time 11:04 Sent To  
Notes
2003-04-30 00:00:00MECH REVISION PERMIT 03031126

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-04-24 Cont ID  
Sent By shernand Date 2003-04-29 Time 15:07 Rev Time 0.35
Received By pkrauss Date 2003-04-24 Time 08:33 Sent To  
Notes
2003-04-24 00:00:00MECHANICAL PERMIT 03031126
 PROVISO ON PLAN

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-04-03 Cont ID  
Sent By jleech Date 2003-03-31 Time 18:54 Rev Time 0.50
Received By rregueir Date 2003-04-03 Time 19:04 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-03-31 Cont ID  
Sent By dpalmer Date 2003-03-28 Time 06:47 Rev Time 0.50
Received By jleech Date 2003-03-31 Time 18:53 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2003-04-25 Cont ID  
Sent By rmcdouga Date 2003-04-24 Time 09:36 Rev Time 0.00
Received By tjonseck Date   Time   Sent To  
Notes
2003-04-24 00:00:00PERMIT NOT TO BE PRINTED UNTIL COUNTY
 IMPACT FEES ARE PAID AND NOC SUBMITTED.

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-17 Cont ID  
Sent By sthyng Date 2003-03-14 Time 10:18 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***