Plan Review Details - Permit 03031042
Plan Review Stops For Permit 03031042
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-22 Cont ID  
Sent By rmcdouga Date 2003-04-22 Time 11:07 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-04-22 00:00:00BUILDING PROVISO
  
 1) SUBMIT A SOIL BORING TEST REPORT AS
 REQUIRED BY FBC 1804.2.2 PRIOR TO
 POURING THE FOUNDATION.
  
 2) SUBMIT A REVISED KEY PLAN AND
 INSTALLATION SCHEDULE FOR THE STORM
 PANELS. THE (2) SH 26 WINDOWS AT THE
 DINING ROOM ARE NOT LISTED AND THE
 WRONG DIMENSIONS ARE GIVEN FOR ONE OF
 THE SH 25 WINDOWS IN THE FAMILY ROOM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-07 Cont ID  
Sent By alange Date 2003-04-21 Time 17:23 Rev Time 5.00
Received By rmcdouga Date 2003-04-04 Time 16:33 Sent To  
Notes
2003-04-04 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3)PROVIDE A SOIL BORING TEST AS REQUIRED
 BY FBC 1804.2.2.
  
 4) GENERAL NOTE #1 ON C1 LISTS THE WRONG
 CONSTRUCTION TYPE. SHOULD BE TYPE VI.
  
 5) INDICATE THE INTERNAL PRESSURE
 COEFFICENT PER FBC 1606.1.7.
  
 6) SPECIFY ON THE PLANS THAT THE SPACING
 OF THE INTERMEDIATE RAILS FOR THE
 BALCONY GUARDRAIL SHALL REJECT THE
 PASSAGE OF A 4" SPHERE AND THE BOTTOM
 RAIL SHALL REJECT A 2" SPHERE.
  
 7)SPECIFY ON THE PLANS THAT FIREBLOCKING
 IS REQUIRED AT THE CONCEALED SPACES
 BETWEEN THE STAIR STRINGERS AT THE TOP
 AND BOTTOM OF THE RUNS. FBC 2305.1.4.
  
 8) THE VALUES IN TRUSS CONNECTION
 SCHEDULE ARE INCORRECT. DOUBLING THE
 STRAPS DOES NOT DOUBLE THE LOAD VALUES.
 SEE THE ATTACHED COPIES FROM 2003 USP
 CATALOG.
  
 9) PROVIDE MANUFACTURER'S SPECIFICATIONS
 AND UL LISTING INFORMATION FOR THE ONE
 HOUR FIRE RATED WECK GLASS BLOCK.
  
 10) SUBMIT PRODUCT APPRVALS FOR THE 16'
 WIDE GARAGE DOOR.
  
 11) THE SIZE OF THE GLASS BLOCK OPENING
 IN THE WINDOW SCHEDULE ON SHEET A2 DOES
 NOT CORRESPOND TO THE SIZE LISTED ON THE
 PLANS. PLEASE CORRECT.
  
 12) THE KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS ARE
 MISSING TWO (2) OF THE OPENINGS ON THE
 FIRST FLOOR. (THE DINING ROOM WINDOWS &
 A WINDOW ON THE LEFT ELEVATION) THE
 WRONG SIZES ARE GIVEN FOR THE WINDOWS ON
 THE LEFT ELEVATION. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-02-12 Cont ID  
Sent By dpalmer Date 2004-02-12 Time 11:53 Rev Time 0.33
Received By dpalmer Date 2004-02-12 Time 11:53 Sent To  
Notes
2004-02-12 00:00:00** REDLINED MISSING EQUIPMENT GROUNDING
 CONDUCTORS. 250.122

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-21 Cont ID  
Sent By csiegber Date 2004-02-11 Time 14:09 Rev Time 0.50
Received By dpalmer Date 2003-04-21 Time 15:51 Sent To P
Notes
2003-04-21 00:00:00*****NOTE ****
  
 GROUNDING ELECTRODE CONDUCTOR STILL
 SHOWN AS WRONG SIZE. NEEDS TO BE #2
 PER 250-66

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-28 Cont ID  
Sent By shernand Date 2003-04-17 Time 14:10 Rev Time 0.33
Received By dpalmer Date 2003-03-28 Time 06:08 Sent To P
Notes
2003-03-28 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE SEE SD IN KITCHEN, NOT
 PERMITTED UNDER NFPA-71 8-1.4.2
 PLEASE ALSO SEE TWO SD`S SHOWN IN MASTER
 BEDROOM. TWO CAN BE INSTALLED,HOWEVER
 ANOTHER ONE WOULD NEED TO BE OUTSIDE.
  
 2)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250-66, SIZE FROM SEC`S
 UNDER 310-15 FOR 400A SERVICE.
  
 3)NOTE: PLEASE CORRELATE PANELS AND
 RISER DIAGRAM. SHOWN AS 200A PANELS
 ON RISER AND 150A ON SCHEDULES??
  
 4)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING COND. BETWEEN MAIN DSIC AND
 PANEL B. SIZE PER 250-122.
  
 5)NOTE: PLEASE ADD RECEPT ALONG KITCHEN
 COUNTERSPACE PER 210-52C-1
  
 6)NOTE: PLEASE SEE WASHER KW, SIZE PER
 MIN 220-16B.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]
  
 7)NOTE: PLEASE LIST MISSING REQ`D BATH
 CIRCUIT(S) PER 210-52D/210-11C-3

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 14:09 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 14:09 Sent To E
Notes
2004-02-11 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-17 Cont ID  
Sent By shernand Date 2003-04-17 Time 14:10 Rev Time 0.00
Received By shernand Date 2003-04-17 Time 14:10 Sent To E
Notes
2003-04-17 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-14 Cont ID  
Sent By sthyng Date 2003-03-14 Time 10:20 Rev Time 0.00
Received By sthyng Date 2003-03-14 Time 10:20 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-03-31 Cont ID  
Sent By jleech Date 2003-03-31 Time 17:23 Rev Time 0.33
Received By rregueir Date 2003-03-31 Time 20:15 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-04-21 Cont ID  
Sent By alange Date 2003-04-21 Time 17:22 Rev Time 0.33
Received By alange Date 2003-04-21 Time 17:22 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-03-31 Cont ID  
Sent By dpalmer Date 2003-04-21 Time 15:52 Rev Time 0.33
Received By jleech Date 2003-03-31 Time 17:22 Sent To M
Notes
2003-03-31 00:00:00DENIED;
 PAGE A-1. RISER DIAGRAM NOT TO CODE.
 SEC. 909.1. WET VENTSFOR BATHROOMS
 ARE PERMITTED TO VENT ONLY BATHROOM
 FIXTURES. THE WASHING MACHINE AND
 LAUNDRY TUB ARE REQUIRED TO DISCHARGE
 DOWN STREAM OF THE BATHROOM GROUP.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8369

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2003-04-25 Cont ID  
Sent By rmcdouga Date 2003-04-22 Time 12:36 Rev Time 0.00
Received By tjonseck Date 2003-04-22 Time 12:36 Sent To  
Notes
2003-04-22 00:00:00PERMIT NOT TO BE PRINTED UNTIL IMPACT
 FEES ARE PAID AND NOC SUBMITTED.

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-17 Cont ID  
Sent By sthyng Date 2003-03-14 Time 10:20 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***