Plan Review Details - Permit 03031040
Plan Review Stops For Permit 03031040
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-05-07 Cont ID  
Sent By shernand Date 2003-05-09 Time 16:20 Rev Time 2.00
Received By rmcdouga Date 2003-05-07 Time 10:34 Sent To  
Notes
2003-05-07 00:00:00BUILDING PROVISO
  
 1) PROVIDE A SOIL BORING TEST REPORT PER
 1804.1.1, PRIOR TO POURING FOUNDATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-08 Cont ID  
Sent By pkrauss Date 2003-05-06 Time 11:44 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-04-08 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE A SOIL BORING TEST REPORT AS
 REQUIRED BY FBC 1804.1.1.
  
 4) REVISE GENERAL NOTE #1 ON C1. THE
 CONSTRUCTION IS TYPE VI.
  
 5) INDICATE THE INTERNAL PRESSURE
 COEFFICENT ON C1 WITH THE DESIGN
 CRITERIA. SEE FBC 1606.1.7.
  
 6) THE NOTE FOR THE BOLLARD ON A2 REFERS
 TO DETAIL #54. THERE IS NO DETAIL #54
 ON THE PLANS.
  
 7) THE PLANS HAVE TWO SHEETS MARKED A4
 AND NO SHEET MARKED A5.
  
 8) INDICATE ON THE PLANS THAT THE WALL
 BETWEEN THE GARAGE AND CONDITIONED SPACE
 IS INSULATED AND THE DOOR IN THIS WALL
 IS SOLID CORE AS REQUIRED BY FBC CHAPTER
 13.
  
 9) THE DETAILS AND THE ID. TAGS FOR THEM
 LOCATED ON SHEET A4 ARE INCORRECTLY
 MARKED AS A3.
  
 10) THE WINDLOAD SCHEDULE ON A3 LISTS
 A SH36 WINDOW AT THE DEN AND THE PLANS
 SHOW (2) SH26 WINDOWS.
  
 11) THE DETAIL FOR THE SLIDING GLASS
 DOOR AND THE HEAD/JAMB DOOR DETAIL ON
 SECOND SHEET A4 SPECIFIES 1X4 OR 2X4
 BUCKS. IF A 1X BUCK IS USED THE DOOR
 ASSEMBLY IS REQUIRED TO BE ANCHORED
 THROUGH THE BUCK AND INTO THE STRUCTURAL
 SUBSTRATE BY FBC 1707.4.4.2. THE 2X BUCK
 IS REQUIRED TO EXTEND BEYOND THE
 INTERIOR FACE OF THE DOOR FRAME. PLEASE
 REVISE THESE DETAILS.
  
 12) PROVIDE THE MANUFACTURER'S SPECS. &
 UL LISTING INFORMATION FOR THE ONE HOUR
 FIRE RATED GLASS BLOCK.
  
 13) THE OPENING SIZE INDICATED ON THE
 PLANS FOR THE GLASS BLOCK EXCEEDS THE
 MAXIMUM OPENING SIZE ALLOWED BY THE
 PRODUCT APPROVAL.
  
 14) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR SINGLE OUTSWING GLAZED
 DOOR.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-12-17 Cont ID  
Sent By btrobaug Date 2003-12-17 Time 14:52 Rev Time 0.50
Received By btrobaug Date 2003-12-17 Time 14:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-05-29 Cont ID  
Sent By csiegber Date 2003-12-12 Time 12:09 Rev Time 0.33
Received By btrobaug Date 2003-05-29 Time 18:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-29 Cont ID  
Sent By shernand Date 2003-05-29 Time 16:29 Rev Time 0.50
Received By btrobaug Date 2003-04-29 Time 11:00 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-27 Cont ID  
Sent By sthyng Date 2003-04-28 Time 12:58 Rev Time 0.50
Received By btrobaug Date 2003-03-27 Time 07:23 Sent To B
Notes
2003-04-07 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CHANGES TO THE
 PLAN FOR CODE COMPLIANCE.
  
 1} THE #4 GROUNDING CONDUCTOR ELECTRODE
 CONDUCTOR IS INCORRECT FOR THE 400 AMP S
 ERVICE SHOWN.
  
 2} PLEASE SHOW PANEL "B" LOCATION ON PLA
 N AND SUBMIT A PANEL SCHEDULE FOR SAME.
  
 3} THE LAUNDRY CIRCUIT NAAEDS TO COMPLY
 WITH 220-16(B) IN THE LOED CALCS.
  
 4} THE SMOKE DETECTOR CANNOT BE LOCATED
 IN THE KITCHEN,MUST COMPLY WITH 8-1.4.2,
 NFPA-72.
  
 5} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-12-12 Cont ID  
Sent By csiegber Date 2003-12-12 Time 12:09 Rev Time 0.00
Received By csiegber Date 2003-12-12 Time 12:08 Sent To E
Notes
2003-12-12 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-05-29 Cont ID  
Sent By shernand Date 2003-05-29 Time 16:28 Rev Time 0.00
Received By shernand Date 2003-05-29 Time 16:28 Sent To E
Notes
2003-05-29 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-09 Cont ID  
Sent By shernand Date 2003-05-09 Time 16:20 Rev Time 0.00
Received By shernand Date 2003-05-09 Time 16:20 Sent To B
Notes
2003-05-09 00:00:00RM DESK. SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-28 Cont ID  
Sent By sthyng Date 2003-04-28 Time 12:58 Rev Time 0.00
Received By sthyng Date 2003-04-28 Time 12:58 Sent To E
Notes
2003-04-28 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-14 Cont ID  
Sent By sthyng Date 2003-03-14 Time 13:48 Rev Time 0.00
Received By sthyng Date 2003-03-14 Time 13:48 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-05-06 Cont ID  
Sent By pkrauss Date 2003-05-06 Time 11:44 Rev Time 0.30
Received By pkrauss Date 2003-05-06 Time 11:27 Sent To B
Notes
2003-05-06 00:00:00MECH PERMIT 03031149

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-04-03 Cont ID  
Sent By btrobaug Date 2003-04-29 Time 11:21 Rev Time 0.50
Received By rregueir Date 2003-04-03 Time 18:09 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-03-31 Cont ID  
Sent By jleech Date 2003-03-31 Time 17:21 Rev Time 0.33
Received By jleech Date 2003-03-31 Time 17:21 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-17 Cont ID  
Sent By sthyng Date 2003-03-14 Time 13:49 Rev Time 0.00
Received By sgraham Date   Time   Sent To E
Notes
***NONE***