Plan Review Details - Permit 03031022
Plan Review Stops For Permit 03031022
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-15 Cont ID  
Sent By btrobaug Date 2003-04-10 Time 10:59 Rev Time 0.00
Received By sthyng Date 2003-04-09 Time 20:30 Sent To P
Notes
2003-04-09 00:00:00**********CORRECTIONS************
  
 1.) FBC 104.2:ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 2.)SOILS TEST REQUIRED.THIS MAY BE
 DONE LATER.
  
 3.)GENERAL NOTES REFER TO SOUTH
 FLORIDA BUILDING CODE.THIS SHOULD BE
 FLORIDA BUILDING CODE 2001.
  
 4.)IS THIS AREA GOING TO BE AIR
 CONDITIONED?IS THERE A HOT WATER
 HEATER IN THIS ROOM?PLEASE CLARIFY.
 ENERGY CALCS MAY BE REQUIRED.
  
 5.)THIS ROOM IS A BEDROOM AS PER FBC
 13-202.THIS CONFLICTS WITH THE
 DESIGNATION ON THE PLAN AS A GYM AND
 ZONING NOTE THAT THIS ROOM CANNOT BE
 USED AS A SLEEPING ROOM.
  
 6.)SEPARATE PERMIT REQUIRED
 (MECHANICAL).
  
 7.)FBC TABLE 600, NOTE I, FIRE
 RESISTANCE REQUIREMENTS FOR EXTERIOR
 WALLS WITH 5 FEET OR LESS SEPARATION
 SHALL BE BASED UPON BOTH INTERIOR AND
 EXTERIOR FIRE EXPOSURE.PLEASE GIVE
 CALCULATIONS FOR THE WALL FOR THE
 PROPOSED BUILDING.
  
 8.)FBC TABLE 600, HORIZONTAL
 SEPARATION OF LESS THAN 3' REQUIRE A 1HR
 PROTECTION AND 0% OPENINGS.
  
 9.) PROVIDE PRODUCT APPROVALS FOR THE
 FOLLOWING ITEMS:
 HURRICANE PROTECTION FOR WINDOWS
 WINDOW MULLIONS
 ASPHALT SHINGLES
  
 10.) PRODUCT APPROVALS WERE SUBMITTED
 FOR MODIFIED BITUMEN ROOF SYSTEM.
 PLEASE CLARIFY.
  
 11.)PROVIDE A ROOF FRAMING PLAN AND A
 GABLE END BRACING DETAIL.
  
 12.)CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC 1804.1.7: THE LOWEST BUILDING
 FLOOR ELEVATION AT THE PERIMETER OF A
 MONOLITHIC FOUNDATION AT HABITABLE AREAS
 SHALL BE A MINIMUM OF 4" ABOVE THE
 FINISH GRADE, AT THE BUILDING PERIMETER.
 FBC 1804.1.3: THE BOTTOM OF FOUNDATIONS
 SHALL EXTEND NO LESS THAN 12 INCHES
 BELOW FINISH GRADE.
  
 13.)PROVIDE ROOF SHEATHING ATTACHMENT
 SCHEDULE.
  
 14.)SPECIFY ATTACHMENTS ON THE WALL
 SECTION OR PROVIDE UPLIFT REQUIREMENTS.
  
 15.)FIRESTOPPING REQUIRED FBC 705.3.1,
 FBC 2305.1.
  
 16.)DOOR SCHEDULE SHOWS A WOOD DOOR
 FOR DOOR #1; PRODUCT APPROVAL SUBMITTED
 IS FOR METAL DOOR.PLEASE CLARIFY.
  
 17.)THE INFORMATION ON THE PLAN
 INDICATES THAT THE IMPACT PROTECTION
 WOULD BE IMPACT WINDOW, BUT THE PRODUCT
 APPROVALS SUBMITTED ARE FOR NON IMPACT.
 PLEASE CLARIFY.
  
 18.)PROVIDE A RECORDED NOTICE OF
 COMMENCEMENT RECORDED WITH THE CLERK OF
 COURTS BEFORE A PERMIT CAN BE ISSUED.
  
 19.)BEFORE A PERMIT TO CONSTRUCT CAN
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY.THE ACTUAL PERMIT
 PLANS MUST BE STAMPED BY THAT OFFICE
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.THIS
 MAY BE DONE AFTER THE PLANS HAVE BEEN
 APPROVED BY PLAN REVIEW BUT BEFORE THE
 PERMIT IS ISSUED.
  
 20.) ON THE WALL SECTION PROVIDE MORE
 STRUCTURAL INFORMATION - TYPE OF STRAPS
 OR UPLIFT REQUIREMENTS, STUD SPACING,
 ATTACHMENT OF STUDS TO TOP PLATE, BOLT
 LENGTH (EMBEDMENT), SHEATHING AND
 ATTACHMENT.
  
 21.) PLEASE CLARIFY AS TO HOW YOU WILL
 PREVENT WATER FROM GOING UNDER THE WALL
 (TYPICAL WALL SECTION).
  
 22.) WINDOW B APPEARS TO BE IN A
 HAZARDOUS LOCATION PER FBC 2405.2.1(2).
  
 23.) FBC 2309.6: ATTIC SPACES SHALL BE
 PROVIDED WITH AN INTERIOR ACCESS
 OPENING NOT LESS THAN 20X36 INCHES.
  
 24.) ADDITIONAL FEES DUE; MAY BE PAID
 WHEN PERMIT IS ISSUED.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IF YOU HAVE ANY QUESTIONS, CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724, [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-10 Cont ID  
Sent By sthyng Date 2003-04-09 Time 20:30 Rev Time 1.00
Received By btrobaug Date 2003-04-10 Time 10:28 Sent To B
Notes
2003-04-10 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 AND MAKE NECESARRY CHANES ON THE PLANS.
  
 1} INDICATE HOW THE NEW STRUCTURE IS BEI
 NG FED.SHOW THE LOCATION OF THE DISCONNE
 CT FOR COMPLIANCE WITH 225-31,32 & 250-3
 2.
  
 2} PROVIDE LOAD CALCULATIONS PER 215-5,
 ALSO GIVE SIZE OF EXISTING SERVICE.
  
 3} PROVIDE A PANEL SCHEDULE SHOWING COMP
 LIANCE WITH 210-11(C)(3) & 210-12.
  
 4} PLEASE SHOW A SMOKE DETECTOR TO COMPL
 Y WITH NFPA-72,8-1.4.1.6.2(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-13 Cont ID  
Sent By sgraham Date 2003-03-25 Time 16:37 Rev Time 0.00
Received By sthyng Date 2003-03-13 Time 13:30 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By kstevens Date 2003-04-11 Time 11:03 Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-04-11 Cont ID  
Sent By sthyng Date 2003-04-15 Time 15:06 Rev Time 0.25
Received By kstevens Date 2003-04-11 Time 10:53 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-25 Cont ID  
Sent By sthyng Date 2003-03-13 Time 13:30 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***