Plan Review Details - Permit 03030747
Plan Review Stops For Permit 03030747
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2003-06-30 Cont ID  
Sent By btrobaug Date 2003-06-30 Time 14:04 Rev Time 0.50
Received By sthyng Date 2003-06-30 Time 09:44 Sent To E
Notes
2003-06-30 00:00:00REVISION - TOP ATTACHMENT, STEEL COLUMN
 TO EXISTING BEAM

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2003-06-17 Cont ID  
Sent By shernand Date 2003-06-27 Time 16:32 Rev Time 1.00
Received By sthyng Date 2003-06-16 Time 14:47 Sent To  
Notes
2003-06-17 00:00:00******CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)CORRECTIONS MADE IN INK ON A SEALED
 PLAN SHOULD BE INITIALED BY THE
 ENGINEER.
  
 2.)REGARDING THE TOP PLATE DETAIL
 2-A2, IS THE 8X8 PLATE ATTACHED TO THE
 STEEL CHANNEL AND 1/4" PLATE?

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-05-23 Cont ID  
Sent By sthyng Date 2003-05-23 Time 10:45 Rev Time 1.00
Received By sthyng Date 2003-05-23 Time 10:45 Sent To  
Notes
2003-05-23 00:00:00ELIMINATED CARPORT; OK PER SHERRY
 PILAND

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-05-22 Cont ID  
Sent By sthyng Date 2003-05-22 Time 15:45 Rev Time 0.00
Received By sthyng Date 2003-05-22 Time 15:45 Sent To  
Notes
2003-05-22 00:00:00OK TO ISSUE AFTER PAYMENT OF IMPACT
 FEES AND NOC

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-05-07 Cont ID  
Sent By btrobaug Date 2003-05-22 Time 13:48 Rev Time 2.00
Received By sthyng Date 2003-05-07 Time 17:29 Sent To P
Notes
2003-05-07 00:00:00**********CORRECTIONS************
  
 1.)REFER TO #1 ON PREVIOUS CORRECTION
 LIST; ENERGY CALCS SHALL INCLUDE ENTIRE
 HOUSE AS PER DEFINITION OF "RENOVATION"
 IN THE ENERGY CODE.
  
 2.)BEFORE A PERMIT TO CONSTRUCT CAN
 BE ISSUED, PLANS MUST BE TAKEN TO PALM
 BEACH COUNTY FOR IMPACT FEES 233-5025.
  
 3.)FILE A NOTICE OF COMMENCEMENT WITH
 THE CLERK OF COURTS.
  
 4.)REFER TO #5 ON PREVIOUS CORRECTION
 LIST; A 34 WINDOW DOES NOT MEET THE
 EMERGENCY EGRESS REQUIREMENTS FBC1005.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-09 Cont ID  
Sent By btrobaug Date 2003-05-06 Time 09:53 Rev Time 8.00
Received By sthyng Date 2003-04-07 Time 16:16 Sent To  
Notes
2003-04-07 00:00:00**********CORRECTIONS************
  
 1.)ENERGY CALCS REQUIRED PER FBC
 13-101.2.2 AND 13-101.2.3.ENERGY CALCS
 SHALL INCLUDE ENTIRE HOUSE AS PER
 DEFINITION OF "RENOVATION" IN THE ENERGY
 CODE.
  
 2.)ON THE WALL SCHEDULE, SHEET A2,
 STUCCO OVER METAL PLASTER BASE TO BE
 NOMINAL THICKNESS OF 7/8" PER
 FBC 2504.2.1 AND ASTM C926.ALSO
 SPECIFY THE WALL SHEATHING ATTACHMENT.
  
 3.)ADDITIONAL FEES DUE.THIS CAN BE
 PAID WHEN THE PERMIT IS ISSUED.
  
 4.)BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE ACTUAL PERMIT PLANS
 MUST BE STAMPED BY THAT OFFICE, AND A
 COPY OF THE PAID RECEIPT ATTACHED TO
 THE PERMIT APPLICATION.PLEASE CALL
 (561) 233-5025 FOR MORE INFORMATION.
 THIS CAN BE DONE AFTER PLAN REVIEW BUT
 MUST BE DONE BEFORE THE PERMIT CAN BE
 ISSUED.
  
 5.)BEDROOM WINDOWS ARE TO COMPLY WITH
 EGRESS REQUIREMENTS AS PER FBC 1005.4:
 PROVIDE EMERGENCY EGRESS WINDOWS IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGTH OF 24" AND NET CLEAR
 OPENING WIDTH OF 20" AND A NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH
 SHALL NOT BE MORE THAN 44 " ABOVE THE
 FINISH FLOOR.
 PLEASE INDICATE BEDROOM EGRESS WINDOWS,
 EITHER ON THE FLOOR PLAN OR ON A WINDOW
 SCHEDULE, GIVING WINDOW SIZES.
  
 6.)NOTE #10, CONCRETE NOTES, SHEET C1
 PER FBC 1814.3.3, DAMPPROOFING IS
 REQUIRED TO BE A MINIMUM OF 6 MIL.
  
 7.)ITEM #13, ELECTRICAL NOTES REFERS
 TO DOOR CHIMES (POOL) AND SMOKE
 DETECTORS, BUT ARE NOT SHOWN ON THE
 ELECTRICAL PLAN.SMOKE DETECTORS ARE
 REQUIRED.
  
 8.)THE PRODUCT APPROVALS FOR THE
 FOLLOWING ITEMS ARE EXPIRED:
 FRENCH DOOR
 ROOF TILE
 HURRICANE SHUTTERS
 PLEASE SUBMIT 2 CURRENT COPIES OF EACH.
  
 9.)PLEASE SUPPLY PRODUCT APPROVALS FOR
 THE FOLLOWING ITEMS, 2 COPIES EACH:
 CASEMENT WINDOWS
 MULLIONS
  
 NOTE - PLEASE CHECK THAT THE PRODUCT
 APPROVALS FOR THE CASEMENT WINDOWS
 ARE FOR AN ARCHED WINDOW, NOT ONLY FOR
 A RECTANGULAR ONE.
  
 10.)PLEASE GIVE DIMENSIONS OF
 INDIVIDUAL WINDOWS IN UNITS D AND E.
  
 11.) SECOND FLOOR BEDROOM EGRESS WINDOWS
 ARE REQUIRED TO BE EITHER IMPACT GLASS
 OR TO HAVE HURRICANE SHUTTERS WHICH CAN
 BE REMOVED FROM THE INSIDE.
  
 12.)A HOT WATER HEATER IS NOT SHOWN
 ON THE PROPOSED FLOOR PLANS.PLEASE
 REVISE.
  
 13.)PROVIDE A ROOF SHEATHING NAILING
 SCHEDULE.PLEASE NOTE CITY AMENDMENT
 REVISED TABLE 2306.1.
  
 14.)ANY CHANGES MADE TO A PLAN SEALED
 BY AN ARCHITECT OR ENGINEER MUST BE
 INITIALED BY THE INDIVIDUAL WHO SEALED
 THE PLAN.
  
 15.) 1503.4 ROOF DRAINS UNLESS ROOFS ARE
 SLOPED TO DRAIN OVER THE ROOF EDGE, ROOF
 DRAINS SHALL BE INSTALLED AT THE LOWEST
 POINT OF THE ROOF. WHERE REQUIRED FOR
 ROOF DRAINAGE,SCUPPERS SHALL BE LOCATED
 AS DETERMINED BY THE ROOF SLOPE AND CON-
 TRIBUTING ROOF AREA.
  
 16.) 1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 17.) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 18.) 1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7.
 NOTE:ALTHOUGH A ROOF MOUNTED UNIT IS
 NOT SHOWN ON THE PLAN, THIS NOTE IS
 MADE TO ASSIST THE DESIGNER IF THIS IS
 THE LOCATION OF THE EXISTING OR PROPOSED
 UNIT.IF THE UNIT IS OR WILL BE LOCATED
 AT ANOTHER LOCATION, DISREGARD THIS
 COMMENT.
  
 19.)PER FBC 1606.1.7, THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 THERE ARE TWO PARTS TO THIS PLAN; THE
 RENOVATION OF THE EXISTING BUILDING AND
 THE PROPOSED CARPORT.SOME OF THE ABOVE
 INFORMATION IS ON THE PLAN, BUT ALL FIVE
 ITEMS IN REGARDS TO THE TWO PARTS OF
 THIS JOB ARE NOT ON THE PLAN.PLEASE
 REVISE.
  
 20.)AWNING WINDOWS ARE INDICATED ON
 THE PLAN.IF THEY ARE TO BE CASEMENT,
 CHANGE THE PLAN.IF THEY ARE TO BE
 AWNING, PROVIDE PRODUCT APPROVALS.
  
 21.)THE 2 1/4" RING SHANK NAILS
 ON THE WALL SECTION (SHEET D1) DO NOT
 MEET THE SHEATHING NAILING REQUIREMENTS.
 PLEASE REVISE.
  
 22.)PER FBC 2103.1, ENGINEERED MASONRY
 SHALL CONFORM TO THE REQUIREMENTS OF
 CHAPTERS 1 THROUGH 3 OF ACI 530. LATERAL
 TIES REQUIRED IN COLUMNS (ACI 5.9.1.6).
  
 23.)PLEASE NOTE:IN REGARDS TO THE
 FUTURE POOL, AS PER NEC 680-22(6),
 FIXED METAL PARTS THAT ARE WITHIN 5 FT
 HORIZONTAL OF THE INSIDE WALL OF THE
 POOL ARE REQUIRED TO BE BONDED.YOU
 MAY WISH TO MAKE PROVISIONS TO HAVE
 THE STEEL FOR THE CARPORT FOUNDATION
 BONDED DURING CONSTRUCTION OF THE
 CARPORT, BEFORE CONCRETE IS POURED.
 THIS IS OPTIONAL AND NOT REQUIRED AT
 THIS TIME.
  
 24.)PLEASE NOTE:
 FBC 1803.1.3 EXCAVATION FOR ANY PURPOSE
 SHALL NOT EXTEND WITHIN 1 FT OF THE
 ANGLE OF REPOSE OR NATURAL SLOPE OF THE
 SOIL UNDER ANY FOOTING OR FOUNDATION,
 UNLESS SUCH FOOTING OR FOUNDATION IS
 FIRST PROPERLY UNDERPINNED OR PROTECTED
 AGAINST SETTLEMENT.
 TO ACCOMODATE THE FUTURE POOL, YOU MAY
 WISH TO ADDRESS THIS ISSUE AT THIS TIME.
 THIS ITEM IS NOT REQUIRED TO BE
 ADDRESSED AT THIS TIME.
  
 25.)AS PER FBC TABLE 600, NOTE (I),
 THE FIRE RESISTANCE REQUIREMENTS FOR
 EXTERIOR WALLS WITH 5 FEET OR LESS
 HORIZONTAL SEPARATION SHALL BE BASED
 UPON BOTH INTERIOR AND EXTERIOR FIRE
 PARTITIONS.IN REGARDS TO THE INFILL
 WOOD FRAME WALL DETAIL FOR THE WEST
 EXTERIOR WALL, EITHER PROVIDE FIRE
 RESISTANCE CALCULATIONS (USING FBC
 CHAPTER 7) OR CHANGE THAT DETAIL TO
 A BLOCK INFILL.
  
 26.)BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE ACTUAL PERMIT PLANS
 MUST BE STAMPED BY THAT OFFICE, AND A
 COPY OF THE PAID RECEIPT ATTACHED TO
 THE PERMIT APPLICATION.PLEASE CALL
 (561) 233-5025 FOR MORE INFORMATION.
 THIS CAN BE DONE AFTER THE PLANS HAVE
 BEEN APPROVED BUT BEFORE THE PERMIT CAN
 BE ISSUED, OR CAN BE DONE NOW.WHEN
 IMPACT FEES ARE PAID, HAVE THEM STAMP
 PAGE A1 WHICH HAS THE ZONING & HISTORIC
 APPROVALS ON THEM.
  
 27.)IN REGARDS TO THE 8X16 BEAM AT THE
 DINING ROOM ON SHEET A1, IS THIS
 EXISTING OR PROPOSED?IF THIS IS NEW,
 PROVIDE A DETAIL AS TO HOW THIS WILL
 BE STRAPPED.
  
 28.)PLEASE PROVIDE A DETAIL FOR THE
 GIRDER AT THE DINING ROOM AND
 INFORMATION AS TO HOW THIS WILL TIE
 INTO THE EXISTING COLUMNS.
  
 29.)PLEASE CLARIFY - IT APPEARS THAT
 THERE IS AN EXISTING 8" COLUMN IN THE
 KITCHEN THAT IS TO REMAIN.IF THIS IS
 TO BE A NEW COLUMN, PROVIDE A DETAIL. IF
 THIS IS EXISTING, INDICATE ON PLAN.
  
 30.)HOW IS THE STEEL COLUMN TO BE
 ATTACHED AT THE TOP?IF THE DETAIL IS
 THE SAME AT THE TOP PLATE AS THE BOTTOM,
 IT APPEARS THAT THE DETAIL WILL NOT
 WORK DUE TO THE DISTANCE OF THE BOLTS
 TO THE EDGE OF THE BEAM.EITHER PROVIDE
 INFORMATION AS TO HOW THAT DETAIL WILL
 WORK AT THE TOP OF THE COLUMN, OR
 PROVIDE AN ATTACHMENT DETAIL FOR THE
 TOP.
  
 31.)PLEASE GIVE INFORMATION IN
 REGARDS TO THE LANDINGS SHOWN ON THE
 FRONT ELEVATIONS.GIVE HEIGHT FROM
 GRADE TO TOP OF LANDING, HEIGHT FROM
 TOP OF LANDING TO FINISHED FLOOR, AND
 WIDTH AND LENGTH.
  
 32.)A SEPARATE PERMIT IS REQUIRED
 FOR THE DRIVEWAY APPROACH.AN APPROVED
 PLAN IS AVAILABLE FROM THE CITY.
  
 33.)ADDITIONAL FEES DUE.THIS MAY
 BE PAID WHEN THE PERMIT IS ISSUED.
  
 34.)PLEASE GIVE INFORMATION ABOUT
 THE GIRDER AT THE DINING ROOM, INCLUDING
 ATTACHMENT DETAILS.
  
 35.)THE AREA CALCULATIONS ARE NOT
 CORRECT.THEY SHOULD INCLUDE ROOFED
 AREAS ONLY.THE CARPORT IS NOT ON THE
 AREA CALCULATIONS AND AN OVERALL
 DIMENSION IS NOT GIVEN FOR THE ROOFED
 AREA OF THE CARPORT.PLEASE REVISE.
  
 36.)PLEASE PROVIDE A SURVEY, IF
 AVAILABLE.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS
 NECESSARY.THIS WILL HELP TO EXPEDITE
 THE PROCESSING OF YOUR PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724 FAX 561-543-2692
 EMAIL [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-03-02 Cont ID  
Sent By btrobaug Date 2004-03-02 Time 08:31 Rev Time 0.50
Received By btrobaug Date 2004-03-02 Time 08:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-06-30 Cont ID  
Sent By csiegber Date 2004-02-26 Time 12:46 Rev Time 0.50
Received By btrobaug Date 2003-06-30 Time 13:44 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-05-22 Cont ID  
Sent By sthyng Date 2003-06-30 Time 09:46 Rev Time 0.50
Received By btrobaug Date 2003-05-22 Time 13:04 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-05-06 Cont ID  
Sent By shernand Date 2003-05-22 Time 10:05 Rev Time 0.75
Received By btrobaug Date 2003-05-06 Time 09:32 Sent To B
Notes
2003-05-06 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 TO THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} THE NOTE ON SHEET "A2" INDICATES
 THERE WILL BE WORK DONE ON THE
 SERVICE.PLEASE PROVIDE AIC RATINGS PER
 110-9 & 110-10.ALSO CORRECTED PANEL
 SCHEDULES,LOAD CALC'S.,AND RISER DIAGRAM
  
 2} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 3} THE SMALL APPLIANCE CIRCUITS ON THE
 LOAD CALCULATION (2@ 1500 VA) AND THE
 PANEL SCHEDULE (3@ 1500 VA) DO NOT
 CORRESPOND,PLEASE CORRECT SAME.
  
 4} THE DRYER ON THEPANEL SCHEDULE AND
 THE LOAD CALCS IS LISTED AT DIFFERENT
 VALUES. SEE 220-16(B).
  
 5} THE BATH UPSTAIRS NEEDS A RECEPTACLE
 PER 210-52(D).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-25 Cont ID  
Sent By shernand Date 2003-04-25 Time 11:18 Rev Time 0.75
Received By btrobaug Date 2003-03-25 Time 09:35 Sent To P
Notes
2003-03-25 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 0N THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT A PANEL SCHEDULE
 SH0WING COMPLIANCE WITH THE FOLLOWING
 APPLICABLE ARTICLES.
  
 A)210-11(C)(3),BATHS.
 B)210-12,BEDROOMS.
 C)220-16(A),SMALL APPLIANCE CIRCUITS.
 D)220-16(B),LAUNDRY.
  
 2} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 3} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 4} PLEASE INDICATE SIZE OF EXISTING
 SERVICE.SUBMIT RISER DIAGRAM AND LOAD
 CALCS IF SERVICE IS TO BE CHANGED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 805-6718

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-02-26 Cont ID  
Sent By csiegber Date 2004-02-26 Time 12:46 Rev Time 0.00
Received By csiegber Date 2004-02-26 Time 12:46 Sent To E
Notes
2004-02-26 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-06-27 Cont ID  
Sent By shernand Date 2003-06-27 Time 16:32 Rev Time 0.00
Received By shernand Date 2003-06-27 Time 16:32 Sent To B
Notes
2003-06-27 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-05-22 Cont ID  
Sent By shernand Date 2003-05-22 Time 10:05 Rev Time 0.00
Received By shernand Date 2003-05-22 Time 10:05 Sent To E
Notes
2003-05-22 00:00:00BT DESK, RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-25 Cont ID  
Sent By shernand Date 2003-04-25 Time 11:18 Rev Time 0.00
Received By shernand Date 2003-04-25 Time 11:18 Sent To E
Notes
2003-04-25 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-24 Time 13:10 Rev Time 0.00
Received By sthyng Date 2003-03-24 Time 13:10 Sent To E
Notes
2003-03-24 00:00:00TO ELEC IN BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-11 Cont ID  
Sent By sthyng Date 2003-03-11 Time 08:56 Rev Time 0.00
Received By sthyng Date 2003-03-11 Time 08:56 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-03-26 Cont ID  
Sent By kstevens Date 2003-03-25 Time 17:50 Rev Time 0.25
Received By pkrauss Date 2003-03-26 Time 12:37 Sent To B
Notes
2003-03-26 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
  
 PROVIDE INFORMATION ON HVAC (NEW OR
 EXISTING, MODEL, BTU'S OF AHU & SEER OF
 C.U.).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-05-10 Cont ID  
Sent By kstevens Date 2003-05-10 Time 12:34 Rev Time 0.50
Received By kstevens Date 2003-05-10 Time 12:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-03-25 Cont ID  
Sent By sthyng Date 2003-05-07 Time 18:54 Rev Time 0.50
Received By kstevens Date 2003-03-25 Time 17:50 Sent To M
Notes
2003-03-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN. THE KITCHEN SINK
 IS NOT SHOWN.
 2) WASH MACHINE SHALL HAVE A STANDPIPE,
 AND REQUIRES A CLEAN OUT 4' ABOVE THE
 FLOOR. (SEE RED LINES ON PLANS)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-11 Time 08:56 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***