Plan Review Details - Permit 03030664
Plan Review Stops For Permit 03030664
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-03-13 Cont ID  
Sent By hpiskura Date 2003-03-13 Time 13:28 Rev Time 0.00
Received By hpiskura Date 2003-03-13 Time 09:32 Sent To  
Notes
2003-03-13 00:00:00PLANS DATED 12/4/02

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-23 Cont ID  
Sent By dpalmer Date 2003-04-23 Time 19:28 Rev Time 0.33
Received By dpalmer Date 2003-04-23 Time 19:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-18 Cont ID  
Sent By dpalmer Date 2003-03-18 Time 18:34 Rev Time 1.00
Received By dpalmer Date 2003-03-18 Time 18:34 Sent To  
Notes
2003-03-18 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE CORRELATE PANEL SCHEDULES
 AND RISER DIAGRAM.
 SOME PANELS SCH SUBMITTED AND NOTHING
 SHOWN ON RISER? NEED TO SUBMIT PANEL
 SCHEDULE FOR EXISTING PANELS FEEDING NEW
 PLEASE OCP SHOWN IN NOTES, 2P-50A FOR
 63A LOAD??
 LOAD CALCS SHOW "1LC1" AND RISER SHOWS
 "1CL1", ??
  
 2)NOTE: PLEASE NOTE ON PLANS, PANELS
 IN NURSE STORAGE AREA TO BE KEPT CLEAR
 AT ALL TIMES, COMBUSTABLES ETC 110-26
  
 PLEASE SEE FIRE REVIEW COMMENTS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2003-03-11 Cont ID  
Sent By mamini Date 2003-03-11 Time 14:55 Rev Time 0.00
Received By mamini Date 2003-03-11 Time 14:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-04-03 Cont ID  
Sent By mcarsill Date 2003-04-03 Time 14:51 Rev Time 0.00
Received By mcarsill Date 2003-04-03 Time 14:51 Sent To  
Notes
2003-04-03 00:00:001) ALL EXIT ACCESS AND EXITS SHALL
 REMAIN CLEAR AT ALL TIMES.
  
 2) TRASH AND DEBRIS SHALL BE REMOVED
 FROM THE FACILITY DAILY.
  
 3) RENOVATIONS SHALL NOT INTERFERE WITH
 ANY EXISTING REQUIRED FIRE PROTECTION
 DEVICES.
  
 4) ALL DEMOLITION, CONSTRUCTION, AND
 RENOVATION ACTIVITIES TO COMPLY WITH
 NFPA 241.
  
 5) NO NON FIRE RATED VISQUEEN SHALL BE
 HUNG FROM THE CEILING. ONLY APPROVED
 RATED MATERIALS SHALL BE USED.
  
 6) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-16 Cont ID  
Sent By shernand Date 2003-04-16 Time 16:08 Rev Time 0.00
Received By shernand Date 2003-04-16 Time 16:07 Sent To  
Notes
2003-04-16 00:00:00COMM BOARD #15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-11 Cont ID  
Sent By sthyng Date 2003-03-11 Time 14:24 Rev Time 0.00
Received By sthyng Date 2003-03-11 Time 14:24 Sent To  
Notes
2003-03-11 00:00:00COMM BOARD #31

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-05-03 Cont ID  
Sent By pkrauss Date 2003-05-03 Time 09:13 Rev Time 0.45
Received By pkrauss Date 2003-05-03 Time 09:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2003-04-08 Cont ID  
Sent By jleech Date 2003-04-26 Time 12:38 Rev Time 0.15
Received By pkrauss Date 2003-04-08 Time 08:36 Sent To  
Notes
2003-04-08 00:00:00AS PER PHONE CALL PER MIKE LINDEN (JLSD)
 FIRE/SMOKE DAMPERS ARE EXISTING.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-04-08 Cont ID  
Sent By pkrauss Date 2003-03-26 Time 10:36 Rev Time 0.00
Received By pkrauss Date 2003-03-19 Time 15:05 Sent To  
Notes
2003-03-26 00:00:00PLEASE CLARIFY THE FOLLOWING INFORMATION
  
 PLAN SHEETS M-3 THROUGH M-6, INDICATE
 DUCTS INTO SHAFT.SOME OF THE DUCTS
 INDICATE FIRE/SMOKE DAMPERS & A FEW DO
 NOT.IT WOULD SEEM THAT ALL DUCTS
 PENETRATING THIS SHAFT WOULD REQUIRE
 FIRE/SMOKE DAMPERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date 2003-04-26 Cont ID  
Sent By jleech Date 2003-04-26 Time 12:38 Rev Time 0.75
Received By jleech Date 2003-04-26 Time 12:38 Sent To M
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2003-04-07 Cont ID  
Sent By jleech Date 2003-04-07 Time 18:44 Rev Time 2.50
Received By jleech Date 2003-04-07 Time 18:44 Sent To  
Notes
2003-04-07 00:00:00MED GAS VALVES AND ALARM PANEL LOCATION
 DOES NOT COMPLY WITH NFPA 99C SECTION
 4.3.1.2.2 (C) AREA ALARMS. NOTE 2 PANELS
 SHALL BE LOCATED AT THE NURSES STATION
 OR OTHER LOCATION THAT WILL PROVIDE FOR
 SURVEILLANCE. NURSERY STORAGE ROOM DOES
 NOT MEET THESE REQUIREMENTS.
 MED-GAS REVIEW BY
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-03-27 Cont ID  
Sent By kstevens Date 2003-03-27 Time 17:49 Rev Time 2.00
Received By kstevens Date 2003-03-27 Time 17:49 Sent To  
Notes
2003-03-27 00:00:00PASSED PLUMBING ONLY - SEPARATE MED GAS
 PERMIT REQUIRED -