Plan Review Details - Permit 03030453
Plan Review Stops For Permit 03030453
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-05-16 Cont ID  
Sent By hpiskura Date 2003-05-16 Time 11:48 Rev Time 0.00
Received By hpiskura Date 2003-05-16 Time 11:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-05-06 Cont ID  
Sent By pkrauss Date 2003-05-15 Time 14:18 Rev Time 0.00
Received By hpiskura Date 2003-05-06 Time 13:42 Sent To  
Notes
2003-05-06 00:00:00SHEET S-11 IS MISSING FROM THE PLANS
 AND SHEET A-3.01 IS NOT INCLUDED ON THE
 TITLE SHEET.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-04-15 Cont ID  
Sent By hpiskura Date 2003-04-15 Time 16:27 Rev Time 0.00
Received By hpiskura Date 2003-04-15 Time 16:27 Sent To  
Notes
2003-04-15 00:00:00THE ENERGY CODE CALCULATIONS HAVE THE
 WRONG COUNTY AND JURISDICTION NUMBER.
 PLEASE REVISE TO CITY OF WEST PALM
 BEACH, 604700.
  
 SHEETS S3 AND S4 ARE ILLEGIBLE.PLEASE
 REVISE AS NECESSARY.
  
 SHEET A3.01 IS STRUCK FROM THE TITLE
 SHEET BUT INCLUDED IN THE PLANS. PLEASE
 CORRECT AS NEEDED.
  
 SHEET S11 IS MISSING FROM THESE SETS. IT
 IS IN THE SIX UNIT PLANS.PLEASE
 CORRECT AS NECESSARY.
  
 TWO SHEETS LABELED M1 ARE NOT INCLUDED
 ON THE TITLE SHEET.PLEASE REVISE AND
 COLLATE AS NECESSARY.
  
 A 1 1/2" SLAB DEPRESSION IS REQUIRED FOR
 THE EXTERIOR MASONRY WALLS.SEE FBC
 2111.1.9 AS AMENDED BY THE CITY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-12 Cont ID  
Sent By hpiskura Date 2003-03-12 Time 15:56 Rev Time 0.00
Received By hpiskura Date 2003-03-12 Time 15:56 Sent To  
Notes
2003-03-12 00:00:00SEE NOTES ON COMPANION REVIEW #03030456

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-04-11 Cont ID  
Sent By dpalmer Date 2003-04-11 Time 15:05 Rev Time 1.00
Received By dpalmer Date 2003-04-11 Time 15:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-04-09 Cont ID  
Sent By dpalmer Date 2003-04-09 Time 09:27 Rev Time 1.00
Received By dpalmer Date 2003-04-09 Time 09:27 Sent To  
Notes
2003-04-09 00:00:00********* UNSAT ***************
  
 1)NOTE: PLEASE SEE PLANS, RISER SHOWS
 A MAIN DISC NEXT TO METER AND PLANS DO
 NOT SHOW ANY MAIN? PLEASE SHOW.
  
 2)NOTE: PLEASE SEE LOAD SHOWN FOR WATER
 HEATER ON PANEL SCHEDULE AND ON LOAD
 CALCS> PLEASE CORRELATE.
 PLEASE ALSO SEE RANGE. IF THESE ARE
 INDIVIDUAL UNITS THEN LOAD CALCS MUST BE
 FIGURED THAT WAY.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-18 Cont ID  
Sent By dpalmer Date 2003-03-18 Time 15:14 Rev Time 0.50
Received By dpalmer Date 2003-03-18 Time 15:14 Sent To  
Notes
2003-03-18 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE NOTE, PLANS ARE NOT
 COMPLETE FOR REVIEW. RISER DIAGRAM ETC
 215-5/110-9
  
 2)NOTE: PLEASE SEE LOAD ON PANEL
 SCHEDULE AND LOAD CALCS FOR WH, PLEASE
 CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-04-16 Cont ID  
Sent By nmccray Date 2003-04-16 Time 16:00 Rev Time 0.00
Received By nmccray Date 2003-04-16 Time 16:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-03-21 Cont ID  
Sent By mcarsill Date 2003-03-21 Time 13:16 Rev Time 0.00
Received By mcarsill Date 2003-03-21 Time 13:16 Sent To  
Notes
2003-03-21 00:00:001) PLEASE CLEARLY SHOW DEMISING WALLS
 BETWEEN UNITS.
  
 2) NO ELEVATION DRAWINGS PROVIDED FOR
 BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-05-15 Cont ID  
Sent By shernand Date 2003-05-15 Time 12:55 Rev Time 0.00
Received By shernand Date 2003-05-15 Time 12:55 Sent To M
Notes
2003-05-15 00:00:00PK DESK, WILL GIVE TO HP.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 14:26 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 14:26 Sent To  
Notes
2003-05-05 00:00:00COMM BOARD #20

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-04-22 Cont ID  
Sent By shernand Date 2003-04-22 Time 15:02 Rev Time 0.00
Received By shernand Date 2003-04-22 Time 15:02 Sent To Z
Notes
2003-04-22 00:00:00REMOVED FROM BOARD. SENT TO SHIRLEY FOR
 REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-03 Time 15:58 Rev Time 0.00
Received By shernand Date 2003-04-03 Time 15:58 Sent To  
Notes
2003-04-03 00:00:00COMM BOARD #44

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-11 Cont ID  
Sent By dpalmer Date 2003-03-11 Time 08:16 Rev Time 0.00
Received By dpalmer Date 2003-03-11 Time 08:16 Sent To  
Notes
2003-03-11 00:00:00TO COMM BOARD #8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-06 Cont ID  
Sent By dpalmer Date 2003-03-06 Time 13:37 Rev Time 0.00
Received By dpalmer Date 2003-03-06 Time 13:37 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-05-15 Cont ID  
Sent By pkrauss Date 2003-05-15 Time 14:17 Rev Time 0.40
Received By pkrauss Date 2003-05-15 Time 13:44 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2003-05-06 Cont ID  
Sent By shernand Date 2003-05-15 Time 13:01 Rev Time 0.35
Received By pkrauss Date 2003-05-06 Time 12:33 Sent To  
Notes
2003-05-06 00:00:00DENIED:PLANS M-201 & M-202
 COMMENTS NOT ADDRESSED FROM 1ST AND 2ND
 REVIEW.
 PROVIDE OUTSIDE AIR CALCS AS PER 2001
 FBC(M) 402.2 FOR NATURAL VENTILATION OR
 TABLE 403.3 FOR MECHANICAL.PLEASE
 PROVIDE CALCULATIONS ON PLAN.
  
 PLEASE NOTE PLAN SHEET M-204 AHU
 MOUNTING DETAIL, DETAIL INDICATES 3"
 CLEARANCE FOR DUCT CONNECTION.2001
 FBC(M) 603.1.3, A MIN OF 4" CLEARANCE
 IS REQUIRED.
  
 PLANS BY ARS DATED 4/29/03 ARE OKAY
 WITH THE EXCEPTION OF OUTSIDE AIR CALCS.
  
 PLEASE REMOVE MECHANICAL PLANS THAT WILL
 NOT BE USED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-04-21 Cont ID  
Sent By hmoser Date 2003-04-21 Time 17:40 Rev Time 0.50
Received By hmoser Date 2003-04-21 Time 17:40 Sent To  
Notes
2003-04-21 00:00:00PLAN DENIED
 NEED FRESHAIR CALCULATIONS.SAME AS LAST
 REVIEW.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-03-19 Cont ID  
Sent By pkrauss Date 2003-03-19 Time 13:28 Rev Time 0.45
Received By pkrauss Date 2003-03-19 Time 13:28 Sent To  
Notes
2003-03-19 00:00:002001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-05-13 Cont ID  
Sent By kstevens Date 2003-05-13 Time 13:05 Rev Time 0.50
Received By kstevens Date 2003-05-13 Time 13:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-04-12 Cont ID  
Sent By kstevens Date 2003-04-12 Time 15:46 Rev Time 0.50
Received By kstevens Date 2003-04-12 Time 15:51 Sent To  
Notes
2003-04-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA-98 DESIGN MANUAL
  
 1) COMMENTS FROM PREVIOUS REVIEW NOT
 ADDRESSED.
  
 A) SHT A3.02 OPTIONAL BATHROOMS UNITS
 B & B(REV), W/C SHALL BE 18" OFF WALL
 AND NOT THE SHOWER. TOILETS POSITIONED
 BESIDE A WALL OFFER THE HIGHEST DEGREE
 OF SAFE USE SINCE A GRAB BAR CAN BE
 MOUNTED TO THE SIDE OF THE TOILET. P-6.5
 (THIS IS ALSO THE CASE FOR UNITS IN THE
 FLOOR PLAN)
 B) SHT A3.03 THE CLEAR FLOOR SPACE DIME-
 NTIONS ARE TO BE APPLIED OR SUPERIMPOSED
 OVER A PLAN DURING THE DESIGN PROCESS TO
 DETERMINE OF SPACE REQUIREMENTS AT
 TOILETS ARE BEING MET. P-7.43 - THIS IS
 NOT SHOWN ON "C" OR "C"(REV) UNITS.
 ******** WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-03-22 Cont ID  
Sent By kstevens Date 2003-03-22 Time 06:08 Rev Time 0.50
Received By kstevens Date 2003-03-22 Time 06:08 Sent To  
Notes
2003-03-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA-98 (AMEND.) DESIGN MANUAL
  
 1) SHT A3.02 OPTIONAL BATHROOMS UNITS
 B & B(REV), W/C SHALL BE 18" OFF WALL
 AND NOT THE SHOWER. TOILETS POSITIONED
 BESIDE A WALL OFFER THE HIGHEST DEGREE
 OF SAFE USE SINCE A GRAB BAR CAN BE
 MOUNTED TO THE SIDE OF THE TOILET. P-6.5
 2) SHT A3.03 THE CLEAR FLOOR SPACE DIME-
 NTIONS ARE TO BE APPLIED OR SUPERIMPOSED
 OVER A PLAN DURING THE DESIGN PROCESS TO
 DETERMINE IF SPACE REQUIREMENTS AT
 TOILETS ARE BEING MET. P-7.43 - NOT
 SHOWN ON "C" OR "C"(REV) UNITS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2003-05-16 Cont ID  
Sent By shernand Date 2003-04-22 Time 15:02 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***