Plan Review Details - Permit 03030352
Plan Review Stops For Permit 03030352
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-26 Cont ID  
Sent By shernand Date 2003-05-08 Time 13:05 Rev Time 1.00
Received By sthyng Date 2003-04-26 Time 15:37 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-14 Cont ID  
Sent By kstevens Date 2003-04-26 Time 13:24 Rev Time 5.00
Received By sthyng Date 2003-04-07 Time 20:16 Sent To  
Notes
2003-04-07 00:00:00**********CORRECTIONS************
  
 1.)BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY.THE ACTUAL SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.THIS
 CAN BE DONE AFTER THE PLANS HAVE BEEN
 APPROVED BUT BEFORE THE PERMIT CAN BE
 ISSUED.
  
 2.)PLANS MUST COMPLY WITH FBC 3407.1.2
 IN REGARDS TO ADDITIONS OF GREATER THAN
 25%.
  
 3.)ENERGY CALCS AND MANUAL J REQUIRED
 FOR ADDITIONS PER FBC 13-101.2.2.
  
 4.)CITY AMENDMENTS TO THE FBC, REVISED
 TABLE 2306.1, FASTENING SCHEDULE FOR
 ROOF SHEATHING IS ATTACHED.PLEASE
 REVISE.
  
 5.)FIREBLOCKING IS REQUIRED PER FBC
 705.3.1.1.
  
 6.)PLEASE CLARIFY AS TO WHETHER THIS
 IS A HAND FRAMED ROOF OR IF YOU WILL BE
 USING ENGINEERED TRUSSES.
  
 7.)PROVIDE A GABLE END BRACING DETAIL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-01-05 Cont ID  
Sent By dpalmer Date 2004-01-05 Time 14:40 Rev Time 0.50
Received By dpalmer Date 2004-01-05 Time 14:38 Sent To  
Notes
2004-01-05 00:00:00REDLINED # OF CONDUCTORS
 REDLINED EQUIPMENT GRND.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-05-06 Cont ID  
Sent By csiegber Date 2003-12-23 Time 15:28 Rev Time 0.50
Received By dpalmer Date 2003-05-06 Time 17:54 Sent To B
Notes
2003-05-06 00:00:00REDLINED EQUIPMENT GROUNDING CONDUCTOR
 FROM MAIN DISC TO PANEL. 250-122

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-05-05 Time 14:29 Rev Time 1.00
Received By dpalmer Date 2003-04-30 Time 15:25 Sent To  
Notes
2003-04-30 00:00:00************ UNSAT ******************
  
 PLEASE NOTE, NOW PLANS ARE BEING
 SUBMITTED SHOWING NEW RISER AS MENTIONED
 ON PREVIOUS PLANS. THE FOLLOWING ARE
 COMMENTS FOR NEW ELECTRICAL PLAN
 SUBMITTED.
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM,
 PANELS, AND LOAD CALCUALTIONS. SOME
 SHOWN AS 100A AND OTHER AT 150A.
 PLEASE SHOW SERVICE/ PANEL(S) LOCATION
 ON PLANS.PLEASE NOTE, NOT MORE THAN 8'
 OF UNPROTECTED CONDUCTOR ARE PERMITTED
 INSIDE HOUSE .230-70/LOCAL AMENDMENTS
  
 2)NOTE: PLEASE REMOVE EQUIPMENT GROUND-
 -ING CONDUCTOR BETWEEN METER AND MAIN
 250-24
  
 3)NOTE: PLEASE CLARIFY AND SHOW NEW
 AND EXISTING LOAD CALCULATIONS COMBINE
 AS REQ`D IN ART 220/ 215-5. NEC
  
 4)NOTE: PLEASE CLARIFY NEW AND EXSITING
 HEAT FOR AHU`S. SHOWS 10KW AND 7.5KW.
  
 5)NOTE: PLEASE SEE MISSING RECEPT PER
 210-52 IN MASTER BEDROOM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE SEE ATTACHED LETTER FOR PLANS
 PER FS 553.80(2)(B)

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-04-25 Cont ID  
Sent By shernand Date 2003-04-28 Time 11:34 Rev Time 0.25
Received By dpalmer Date 2003-04-25 Time 09:50 Sent To  
Notes
2003-04-25 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SEE THAT NO NEW E-SHEETS
 WERE SUBMITTED IN NEW SETS TO ADDRESS
 FIRST REVIEW COMMENTS.
  
 PLEASE ADDRESS ORIG COMMENT AND INSERT
 NEW SHEETS FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-02 Cont ID  
Sent By shernand Date 2003-04-18 Time 16:05 Rev Time 0.75
Received By dpalmer Date 2003-04-02 Time 18:09 Sent To P
Notes
2003-04-02 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT ONE SET OF LOAD
 CALCULATIONS FOR NEW AND EXISTING.
  
 2)NOTE: PLEASE SEE NOTES, #11 MENTIONS
 NEW 150A SERVICE AND NO RISER DIAGRAM
 WAS SUBMITTED? PLEASE SUBMIT, SEC`S
 CONDUITS, AIC RATING FOR NEW MAIN/PANELS
 ETC. ETC. 215-5/110-9
  
 3)NOTE: PLEASE CLARIFY NEW OR EXSITING
 WATER HEATER AND LOAD? NOT SHOWN ON
 EXISTING OR NEW LOAD CALCS?
  
 4)NOTE: PLEASE RECONFIURE LOAD CALCS
 TO MEET NEC 220.
  
 5)NOTE: PLEASE SEE MISSING RECEPT PER
 210-52 ON WALL OUTSIDE BEDROOM. SITTING
 ROOM?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-12-23 Cont ID  
Sent By csiegber Date 2003-12-23 Time 15:28 Rev Time 0.00
Received By csiegber Date 2003-12-23 Time 15:28 Sent To E
Notes
2003-12-23 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-16 Time 12:26 Rev Time 0.00
Received By csiegber Date 2003-12-16 Time 12:26 Sent To E
Notes
2003-12-16 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-05-08 Cont ID  
Sent By shernand Date 2003-05-08 Time 13:05 Rev Time 0.00
Received By shernand Date 2003-05-08 Time 13:05 Sent To B
Notes
2003-05-08 00:00:00STHYNG. RETURNED W/ PAID IMPACT FEES.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 14:29 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 14:29 Sent To E
Notes
2003-05-05 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-04-28 Cont ID  
Sent By shernand Date 2003-04-28 Time 11:34 Rev Time 0.00
Received By shernand Date 2003-04-28 Time 11:34 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-18 Cont ID  
Sent By shernand Date 2003-04-18 Time 16:04 Rev Time 0.00
Received By shernand Date 2003-04-18 Time 16:04 Sent To E
Notes
2003-04-18 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-24 Time 12:58 Rev Time 0.00
Received By sthyng Date 2003-03-24 Time 12:58 Sent To E
Notes
2003-03-24 00:00:00TO ELEC IN BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-06 Cont ID  
Sent By sgraham Date 2003-03-24 Time 12:44 Rev Time 0.00
Received By dpalmer Date 2003-03-06 Time 12:56 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-04-28 Cont ID  
Sent By hmoser Date 2003-04-28 Time 07:49 Rev Time 0.25
Received By hmoser Date 2003-04-28 Time 07:48 Sent To  
Notes
2003-04-28 00:00:00SUBMIT PLANS,MANUAL(J) WITH APPLICATION

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-04-26 Cont ID  
Sent By sthyng Date 2003-04-26 Time 15:48 Rev Time 0.25
Received By hmoser Date 2003-04-26 Time 12:49 Sent To P
Notes
2003-04-26 00:00:00PLAN DENIED
 NO A/C PLANS,OR ENERGY CALCULATIONS
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-04-07 Cont ID  
Sent By kstevens Date 2003-04-03 Time 17:15 Rev Time 0.50
Received By hmoser Date 2003-04-07 Time 17:27 Sent To B
Notes
2003-04-07 00:00:00MECHANICAL CONTRACTOR NEEDS PLANS,MANUAL
 (J) ENERGY CALCULATIONS FOR PERMIT
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8221

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-04-26 Cont ID  
Sent By kstevens Date 2003-04-26 Time 13:24 Rev Time 0.25
Received By kstevens Date 2003-04-26 Time 13:23 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-04-03 Cont ID  
Sent By hmoser Date 2003-04-26 Time 12:50 Rev Time 0.25
Received By kstevens Date 2003-04-03 Time 17:14 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-24 Cont ID  
Sent By dpalmer Date 2003-03-06 Time 12:56 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved