Plan Review Details - Permit 03030336
Plan Review Stops For Permit 03030336
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-03-13 Cont ID  
Sent By hpiskura Date 2003-03-13 Time 09:14 Rev Time 0.00
Received By hpiskura Date 2003-03-13 Time 09:11 Sent To  
Notes
2003-03-13 00:00:00PROVSIO:
 PROVIDE A TEST REPORT FOR THE NEW DOOR'S
 WINDLOAD CAPACITY.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-08 Cont ID  
Sent By dpalmer Date 2003-04-08 Time 13:24 Rev Time 0.50
Received By dpalmer Date 2003-04-08 Time 13:24 Sent To  
Notes
2003-04-08 00:00:00NOTES REDLINED ON PLANS FOR OCP OF
 AHU/HEAT. PER 424-3B

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-14 Cont ID  
Sent By shernand Date 2003-04-02 Time 15:48 Rev Time 1.00
Received By dpalmer Date 2003-03-14 Time 15:06 Sent To  
Notes
2003-03-14 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SHOW WIRE SIZES ON PANEL
 SCHEDULE FOR ALL BRANCH CIRCUITS.
  
 2)NOTE: PLEASE LIST THE REQ`D SIGN
 CIRCUIT PER 600-5
  
 3)NOTE: PLEASE CIRCUIT EM/EXT LTS PER
 700-12E.
  
 4)NOTE: PLEASE SIZE OCP FOR AHU HEAT
 PER 424-3B
  
 5)NOTE: PLEASE SHOW SIZE OF TAPPED
 CONDUCTORS FROM GUTTER TO METER AND
 METER TO MAIN DISC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-03-28 Cont ID  
Sent By mcarsill Date 2003-03-28 Time 15:54 Rev Time 0.00
Received By mcarsill Date 2003-03-28 Time 15:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-02 Cont ID  
Sent By shernand Date 2003-04-02 Time 15:48 Rev Time 0.00
Received By shernand Date 2003-04-02 Time 15:47 Sent To E
Notes
2003-04-02 00:00:00DPALMER DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-06 Cont ID  
Sent By dpalmer Date 2003-03-06 Time 09:27 Rev Time 0.00
Received By dpalmer Date 2003-03-06 Time 09:27 Sent To  
Notes
2003-03-06 00:00:00TO COMM BOARD #26

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-03-31 Cont ID  
Sent By pkrauss Date 2003-03-26 Time 09:30 Rev Time 0.00
Received By pkrauss Date 2003-03-26 Time 09:29 Sent To  
Notes
2003-03-26 00:00:00APPROVED 3-17-03