Plan Review Details - Permit 03030314
Plan Review Stops For Permit 03030314
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-03-11 Cont ID  
Sent By hpiskura Date 2003-03-11 Time 10:40 Rev Time 0.00
Received By hpiskura Date 2003-03-11 Time 10:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-03-30 Cont ID  
Sent By btrobaug Date 2004-03-30 Time 13:40 Rev Time 0.75
Received By btrobaug Date 2004-03-30 Time 13:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-21 Cont ID  
Sent By csiegber Date 2004-03-25 Time 11:34 Rev Time 0.50
Received By dpalmer Date 2003-03-21 Time 10:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-07 Cont ID  
Sent By dpalmer Date 2003-03-07 Time 06:06 Rev Time 0.33
Received By dpalmer Date 2003-03-07 Time 06:06 Sent To  
Notes
2003-03-07 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE CLARIFY CONDUCTOR SIZE
 FROM ELEVATOR DISC, W/ 40A OCP AND #10?
  
 2)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 INFORMATION REQ`D FOR ENGINEER OF
 RECORD IN TITLE BLOCK.
  
 3)NOTE: PLEASE SUBMIT AIC RATING FOR ALL
 NEW EQUIPMENT. IT IS NOTED THAT AIC
 RATING WERE SUBMITTED FOR PANEL.
 110-9
  
 4)NOTE: PLEASE SUBMIT WIRE SIZE FROM
 MDP TO NEW DISC #5.
  
 5)NOTE: PLEASE PROVIDE LOAD FOR ELEVATOR
 COMBINED WITH LOAD ON PANEL..
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-03-21 Cont ID  
Sent By mcarsill Date 2003-03-21 Time 13:03 Rev Time 0.00
Received By mcarsill Date 2003-03-21 Time 13:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-03-06 Cont ID  
Sent By mcarsill Date 2003-03-06 Time 12:36 Rev Time 0.00
Received By mcarsill Date 2003-03-06 Time 12:36 Sent To  
Notes
2003-03-06 00:00:001) PERMANENT SIGNS ARE REQUIRED ON
 EVERY LEVEL " IN FIRE EMERGENCY, DO
 NOT USE ELEVATOR. USE EXIT STAIRS
  
 2) PLEASE INDICATE IF THE NEW ELEVATOR
 HAS AN EMERGENCY EXIT.
  
 3) PLEASE INDICATE TOTAL TRAVEL DISTANCE
 OF NEW ELEVATOR.
  
 4) WHERE ARE THE OPERATING CONTROLS FOR
 THE NEW ELEVATOR.
  
 5) INTERIOR FINISH OF NEW ELEVATOR IS
 TO BE NON-COMBUSTIBLE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-25 Cont ID  
Sent By csiegber Date 2004-03-25 Time 11:34 Rev Time 0.00
Received By csiegber Date 2004-03-25 Time 11:34 Sent To E
Notes
2004-03-25 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-21 Cont ID  
Sent By sthyng Date 2003-03-21 Time 09:29 Rev Time 0.00
Received By sthyng Date 2003-03-21 Time 09:29 Sent To  
Notes
2003-03-21 00:00:00COMM BOARD #20

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-03-06 Cont ID  
Sent By pkrauss Date 2003-03-06 Time 15:08 Rev Time 0.35
Received By pkrauss Date 2003-03-06 Time 15:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2003-03-11 Cont ID  
Sent By hpiskura Date 2003-03-11 Time 10:41 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy