| 2003-04-03 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) INDICATE THE LOCATION AND SIZE OF THE |
| | ATTIC ACCESS TO THE AREA ABOVE THE |
| | MASTER BEDROOM. |
| | |
| | 3) THE ROOF SHEATHING NAIL SPACING GIVEN |
| | ON SHEET GN1 IS INCORRECT. SEE CITY OF |
| | WPB AMENDMENTS TO THE FBC TABLE 2306.1. |
| | |
| | 4) THE EXTERIOR STUCCO SOFFIT SPECS. #7 |
| | ON A5 STATES THAT METAL LATH IS TO BE |
| | ATTACHED NOT MORE THAN 6" APART. ASTM C |
| | 1063 REQUIRES 3/8" RIB METAL LATH TO BE |
| | ATTACHED AT EVERY RIB (4"O.C.). PLEASE |
| | REVISE. |
| | |
| | 5) THE GIRDER AT THE SECOND FLOOR ABOVE |
| | BEDROOM #2 WITH AN UPLIFT OF 5455# AND |
| | BEARING ON THE (3) 2X6 HAS THE WRONG |
| | CONNECTOR SPECIFIED. SEE SHEET 3S. THE |
| | DETAIL THAT IS SPECIFIED SHOWS A USP |
| | USC 53 ATTACHED TO A MASONRY WALL. |
| | NOTE: SOME HOLDOWN STRAPS MAY NOT WORK |
| | AT THIS LOCATION DUE TO PROXIMITY TO THE |
| | CORNER. |
| | |
| | 6) THE TRUSS/GIRDER CONNECTION DETAIL ON |
| | S3 SHOWS A 2X4 WALL. THE PLANS SHOW A |
| | 2X6 WALL. PLEASE CORRECT. |
| | |
| | 7) SPECIFY THE SPECIAL ROOF SHEATHING |
| | NAILING REQUIREMENTS REQUIRED BY CITY OF |
| | WPB AMENDMENTS TO FBC TABLE 2306.1. |
| | INDICATE THE FASTENER TYPES, SPACINGS |
| | AND ZONES ON THE PLANS. |
| | |
| | 8) SPECIFY THE LENGTH OR EMBED DEPTH OF |
| | THE 1/2" DIA. EXPANSION ANCHORS AT THE |
| | WD. FRAME TO CONCRETE ATTACHMENT DETAIL |
| | ON A6. |
| | |
| | 9) THE OWNER/AGENT IS REQUIRED TO SIGN |
| | THE ENERGY CALC. FORM. |
| | |
| | 10) THE OPENING SIZES LISTED ON THE |
| | STORM PANEL SCHEDULE DO NOT MATCH THE |
| | WINDOW SIZES ON THE PLANS FOR NUMBERS 1, |
| | 12, 15, 16, 18 AND 19. THE GLAZED FRENCH |
| | DOOR AT THE MASTER BEDROOM IS NOT SHOWN |
| | ON THE KEY PLAN OR SCHEDULE. THE SHUTTER |
| | WIDTH, HEIGHT AND SPAN ARE NOT GIVEN FOR |
| | OPENING #1. PLEASE CORRECT. |
| | |
| | 11) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - DOUBLE GARAGE DOOR |
| | - SINGLE HUNG WINDOWS |
| | - GLAZED FRENCH DOOR AT MASTER BEDROOM |
| | |
| | 12) PROVIDE A SOIL BORING TEST REPORT AS |
| | REQUIRED BY FBC 1804.2.2. |
| | |
| | NOTE: PLEASE RETURN ALL OLD SHEETS OF |
| | DRAWINGS WHEN RESUBMITTING PLANS. |