| 2003-04-03 00:00:00 | **********CORRECTIONS************ |
| | |
| | 1.)BEFORE A PERMIT TO CONSTRUCT MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION.THIS CAN BE DONE AT TIME |
| | OF ISSUANCE, AFTER THE PLANS HAVE BEEN |
| | APPROVED BUT BEFORE THE PERMIT IS |
| | PRINTED. |
| | |
| | 2.)PROVIDE SOILS REPORT SHOWING |
| | BEARING CAPACITY.THIS MAY BE SUBMITTED |
| | LATER (AFTER PERMIT ISSUANCE). |
| | |
| | 3.)FILE A NOTICE OF COMMENCEMENT WITH |
| | THE CLERK'S OFFICE.BRING A RECORDED |
| | CERTIFIED COPY TO THIS OFFICE.THIS |
| | MUST BE DONE BEFORE THE PERMIT CAN BE |
| | PICKED UP. |
| | |
| | 4.)PER FBC 1814.3.3, DAMPPROOFING |
| | IS REQUIRED TO BE .006.PLEASE REVISE |
| | NOTES #1. |
| | |
| | 5.) HURRICANE PROTECTION REQUIRED FOR |
| | WINDOWS.ANY OF THE FOLLOWING OPTIONS |
| | WOULD BE ACCEPTABLE: |
| | |
| | A.) SUBMIT TWO COPIES OF PRODUCT |
| | APPROVALS FOR SHUTTERS, OR |
| | B.) WINDOWS TO BE IMPACT GLASS, |
| | CHANGE PLAN AND SUBMIT PRODUCT |
| | APPROVALS, OR |
| | C.) INDICATE ON PLAN THAT SHUTTERS |
| | ARE REQUIRED, BUT A PERMIT |
| | CAN BE APPLIED FOR LATER. |
| | |
| | 6.) FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 7.)PROVIDE WINDOW SIZES FOR THE |
| | WINDOWS IN THE ADDITION. |
| | |
| | 8.)2001 FL BLD CODE, 1005.4: |
| | PROVIDE EMERGENCY EGRESS WINDOWS IN |
| | SLEEPING ROOMS WITH A MINIMUM NET CLEAR |
| | OPENING HEIGTH OF 24" AND NET CLEAR |
| | OPENING WIDTH OF 20" AND A NET CLEAR |
| | OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR |
| | OPENINGS ARE PERMITTED TO HAVE A NET |
| | CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH |
| | SHALL NOT BE MORE THAN 44 " ABOVE THE |
| | FINISH FLOOR.PLEASE HAVE THE BEDROOM |
| | EGRESS WINDOW INDICATED ON THE PLAN. |
| | |
| | 9.)WHEN CHANGES ARE MADE TO A SEALED |
| | DRAWING, THEY ARE TO BE MADE BY THE |
| | ARCHITECT OR ENGINEER ONLY, AND THOSE |
| | CHANGES SHOULD BE INITIALED.THE CHANGE |
| | IN INK (NOT INITIALED) FOR THE WOOD |
| | DOOR TO BE A METAL DOOR SHOULD BE |
| | INITIALED, AND THE FLOOR PLAN CHANGED |
| | AS WELL. |
| | |
| | 10.)FIREBLOCKING REQUIRED PER FBC |
| | 2305.1.PLEASE REVISE WALL SECTION. |
| | |
| | 11.)WALL SECTION MUST SPECIFY WHICH |
| | HURRICANE STRAPS ARE TO BE USED, EITHER |
| | BY NAMING A BRAND AND TYPE OF STRAP TO |
| | BE USED, OR BY SPECIFYING UPLIFT |
| | REQUIREMENTS FOR THE STRAP. |
| | |
| | 12.)FOOTER DEPTH REQUIRED TO BE |
| | 16" MIN. PER CITY AMENDMENTS TO THE FBC |
| | 1804.1.7. |
| | |
| | 13.)PROVIDE A SHEATHING NAILING |
| | SCHEDULE.PLEASE NOTE CITY AMENDMENTS |
| | 2306.1 REVISED TABLE. |
| | |
| | 14.)THE FLOOR PLAN SHOWS A SINGLE |
| | WINDOW OF 6'2, BUT THE PRODUCT APPROVALS |
| | SUBMITTED SHOWS A MAX WIDTH OF 52". |
| | IF THIS IS TO BE TWO WINDOWS MULLED |
| | TOGETER, CHANGE THE PLAN TO INDICATE |
| | THIS AND PROVIDE PRODUCT APPROVALS FOR |
| | THE MULLIONS.IF THIS IS TO BE ONE |
| | WINDOW, PROVIDE PRODUCT APPROVALS FOR |
| | THE WINDOW YOU PLAN TO INSTALL IN THIS |
| | LOCATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |