Plan Review Details - Permit 03030165
Plan Review Stops For Permit 03030165
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2003-04-17 00:00:00REVIEWED BY HP - SWAPPED OUT SHEETS
 FOR OWNER AFTER CORRECTIONS ADDED IN RED
 FOR FIRE - HP LOOKED AT THE CORRECTIONS
 AND SAID IT WAS OK -

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-03-24 Cont ID  
Sent By hpiskura Date 2003-03-24 Time 10:16 Rev Time 0.00
Received By hpiskura Date 2003-03-11 Time 11:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-07 Cont ID  
Sent By dpalmer Date 2003-04-07 Time 06:16 Rev Time 0.30
Received By dpalmer Date 2003-04-07 Time 06:16 Sent To  
Notes
2003-04-07 00:00:00ADDRESS IS STILL NOT CORRECT.
 3914 SOUTHERN IS NOT IN THE CITY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-10 Cont ID  
Sent By dpalmer Date 2003-03-10 Time 06:12 Rev Time 0.25
Received By dpalmer Date 2003-03-10 Time 06:12 Sent To  
Notes
2003-03-10 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE SEE FS/ FAC, 61G15-23.002
 471.025, TITLE BLCOK FOR ENGINEER OF
 RECORD SHALL BE ON ALL SHEETS.
  
 2)NOTE: PLEASE SEE 700-12E FOR CIRCUIT-
 ING OF EM / EXT LTS.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT, INCLUDING NEW MAINS.
 110-9/215-5
  
 4)NOTE: PLEASE SEE RISER DIAGRAM, IT IS
 NOTED THAT AN EQUIPMENT GROUNDING
 CONDUCTOR IS TO BE INSTALLED BETWEEN
 GUTTER AND MAIN DISC'S. PLEASE SHOW AN
 EQP, GRD IS ONLY INSTALLED AFTER FIRST
 MEANS OF DISC. PER 250-24 PLEASE CORRECT
  
 5)NOTE: PLEASE CLARIFY LOCATION OF NEW
 RECEPT, APPEARS TO BE SERVICE BAY AREA?
 PLEASE PROVIDE TYPE OF LOCATION ON PLAN
 PER ART 500. NEC.
  
 6)NOTE: PLEASE SHOW LOCATION OF SERVICE
 ON PLANS , INCLUDING LOCATIONS OF NEW
 AND EXISTING PANELS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-04-04 Cont ID  
Sent By mcarsill Date 2003-04-04 Time 11:04 Rev Time 0.00
Received By mcarsill Date 2003-04-04 Time 11:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-03-21 Cont ID  
Sent By mcarsill Date 2003-03-21 Time 15:10 Rev Time 0.00
Received By mcarsill Date 2003-03-21 Time 15:10 Sent To  
Notes
2003-03-21 00:00:001) DOOR # 9 SHALL BE AT LEAST 45 MINUTE
 FIRE RATED SINCE IT IS WITHIN A ONE
 HOUR FIRE WALL.
  
 2) SINCE NO SPRINKLERS ARE PRESENT,
 THE MECHANICAL AND STORAGE ROOM SHALL
 BE AT LEAST ONE HOUR FIRE RATED WITH
 PROPER OPENING PROTECTIVES.
  
 3) FUEL TANK WORK SHALL COMPLY WITH
 NFPA 30.
  
 4) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-04-15 Cont ID  
Sent By shernand Date 2003-04-15 Time 13:25 Rev Time 0.00
Received By shernand Date 2003-04-15 Time 13:25 Sent To P
Notes
2003-04-15 00:00:00KSTEVENS DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-08 Cont ID  
Sent By shernand Date 2003-04-08 Time 14:55 Rev Time 0.00
Received By shernand Date 2003-04-08 Time 14:55 Sent To  
Notes
2003-04-08 00:00:00KSTEVENS DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-04 Cont ID  
Sent By sthyng Date 2003-04-04 Time 09:56 Rev Time 0.00
Received By sthyng Date 2003-04-04 Time 09:56 Sent To  
Notes
2003-04-04 00:00:00TO COMM BOARD #57

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-06 Cont ID  
Sent By dpalmer Date 2003-03-06 Time 12:32 Rev Time 0.00
Received By dpalmer Date 2003-03-06 Time 12:32 Sent To  
Notes
2003-03-06 00:00:00TO COMM BOARD #27

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-03-17 Cont ID  
Sent By pkrauss Date 2003-03-17 Time 16:21 Rev Time 0.35
Received By pkrauss Date 2003-03-17 Time 16:21 Sent To  
Notes
2003-03-17 00:00:00AHU EXISTING - REPLACING SOME AC DROPS
 TO EXISTING GRILLES - ADD 1 R/A JUMPER

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-07-03 Cont ID  
Sent By kstevens Date 2003-07-03 Time 09:18 Rev Time 0.50
Received By kstevens Date 2003-07-03 Time 09:18 Sent To  
Notes
2003-07-03 00:00:00REVISION OK - SANITARY RISER DIAGRAM,
 WATER RISER DIAGARM, & PLUMBING FLOOR
 PLAN.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-06-16 Cont ID  
Sent By kstevens Date 2003-04-17 Time 12:54 Rev Time 0.75
Received By pschmitz Date 2003-04-17 Time 12:53 Sent To  
Notes
2003-04-17 00:00:00PROVISO
  
  
 LAV SHALL BE MINIMUM OF 15" TO CENTER
 OF WASTE OFF ANY WALL. 30" X 48"CLEAR
 FLOOR SPACE REQUIRED.
  
 NO PLUMBING PLANS SUBMITTED - NOT REQD.
 AS LAV MOVING IN SAME WALL ONLY PLUMBING
 WORK BEING DONE.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-16 Cont ID  
Sent By shernand Date 2003-04-15 Time 13:31 Rev Time 0.00
Received By pschmitz Date 2003-06-16 Time 09:20 Sent To  
Notes
2003-04-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT 3 LAV SHALL BE MINIMUM OF 15" OFF
 WALL TO CENTER. SEE HDCP DETAIL SHT 3
 2) 11-4.1.6(2) 20% OVER CONTRACT PRICE
 SHALL BE SPENT FOR ACCESSIBILITY ISSUES.
 WOMENS TOILET ROOM DOES NOT MEET HDCP
 CODE. PLEASE INDICATE HOW $12,000 WILL
 BE SPENT PER CHAPTER 11 DISPROPORTIONATE
 COST. IF NOT SPENT THEN THE WOMENS
 TOILET ROOM WILL HAVE TO COMPLY WITH
 11-4.22.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692