Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-22 Cont ID  
Sent By sthyng Date 2003-04-22 Time 17:08 Rev Time 2.00
Received By sthyng Date 2003-04-22 Time 17:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-22 Time 16:40 Rev Time 3.00
Received By sthyng Date   Time   Sent To  
Notes
2003-04-02 00:00:00**********CORRECTIONS************
  
 1.) BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE ACTUAL PERMIT PLANS
 MUST BE STAMPED BY THAT OFFICE, AND A
 COPY OF THE PAID RECEIPT ATTACHED TO
 THE PERMIT APPLICATION.PLEASE CALL
 (561) 233-5025 FOR MORE INFORMATION.
  
 2.)PER FBC 104.3.1.1, MINIMUM PLAN
 REVIEW CRITERIA, PROVIDE A ROOF FRAMING
 PLAN. ELEVATIONS CONFLICT WITH SECTIONS.
  
 3.)PLEASE PROVIDE AREA CALCULATIONS
 OF EXISTING HOUSE AND ADDITION AREA.
  
 4.)2304.3.4 WOOD JOIST SHALL HAVE 18"
 CLEARANCE FROM THE BOTTOM OF JOIST TO
 EARTH OR ELSE BE PRESSURE TREATED WOOD.
  
 5.)1403.1.6 IN ORDER TO PROVIDE FOR
 INSPECTION FOR TERMITE INFESTATION,
 CLEARANCE BETWEEN EXTERIOR WALL COVER-
 INGS AND FINAL EARTH GRADE ON THE
 EXTERIOR OF A BUILDING SHALL NOT BE LESS
 THAN 6 INCHES.
  
 6.)PROVIDE ENERGY CALCS FOR ADDITION
 AREA.
  
 7.)FBC 905.2, SMOKE DETECTOR REQUIRED.
  
 8.)PROVIDE LEGIBLE PRODUCT APPROVALS
 FOR THE FOLLOWING ITEMS:
 A.)HURRICANE SHUTTERS (CAN'T READ)
 B.)FRENCH DOORS (CAN'T READ)
 C.)WINDOW
 D.)LAP SIDING
  
 9.) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
  
  
  
  
  
  
  
  
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-09-02 Cont ID  
Sent By btrobaug Date 2003-09-02 Time 12:41 Rev Time 0.50
Received By btrobaug Date 2003-09-02 Time 11:40 Sent To  
Notes
2003-09-02 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOTE: PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED, DATED
 AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 IF THERE ARE ANY QEUSTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-03-11 Cont ID  
Sent By dbaxter Date 2003-08-28 Time 13:17 Rev Time 0.50
Received By btrobaug Date 2003-03-11 Time 17:29 Sent To B
Notes
2003-03-11 00:00:00RES IN BOX./WRT

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-28 Cont ID  
Sent By dbaxter Date 2003-08-28 Time 13:17 Rev Time 0.00
Received By dbaxter Date 2003-08-28 Time 13:17 Sent To E
Notes
2003-08-28 00:00:00TO BTROBAUGH DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-22 Cont ID  
Sent By shernand Date 2003-04-22 Time 16:40 Rev Time 0.00
Received By shernand Date 2003-04-22 Time 16:40 Sent To B
Notes
2003-04-22 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-11 Cont ID  
Sent By sthyng Date 2003-03-11 Time 14:07 Rev Time 0.00
Received By sthyng Date 2003-03-11 Time 14:06 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-05 Cont ID  
Sent By sgraham Date 2003-03-11 Time 12:20 Rev Time 0.00
Received By dpalmer Date 2003-03-05 Time 10:28 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-11 Cont ID  
Sent By dpalmer Date 2003-03-05 Time 10:28 Rev Time 0.00
Received By sgraham Date   Time   Sent To I