Plan Review Details - Permit 03022362
Plan Review Stops For Permit 03022362
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-05-21 Cont ID  
Sent By jwitmer Date 2003-05-21 Time 16:51 Rev Time 0.50
Received By jwitmer Date 2003-05-21 Time 16:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-25 Cont ID  
Sent By shernand Date 2003-05-21 Time 14:21 Rev Time 1.15
Received By jwitmer Date 2003-04-25 Time 08:01 Sent To  
Notes
2003-04-25 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 03022362
 ADDRESS: 334 HUNTER ST
 CONT: O/B ANDERSON, GEORGE
 TELL # (561) 585-1301
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 ACTION : APPROVED
  
 ***************PROVISO*****************
  
 1) PLANS INDICATED THAT GLAZED OPENINGS
 ARE TO BE IMPACT RESISTANT( NEW OPENING)
 THE PRODUCT APPROVAL REPORTS SUBMITTED
 ARE NON-IMPACT RATED. STORM SHUTTERS
 WILL BE REQUIRED FOR THESE NEW OPENINGS.
 PROVIDE PRODUCT TESTING REPORT(2 COPIES)
 TO THIS OFFICE BEFORE ROUGH BUCK
 INSPECTION. HIGHLIGHT CONNECTION DETAILS
 TO BE USED. FASTENERS & SPACING.
 FL BLDG CODE 3401.7.2.4.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-31 Cont ID  
Sent By btrobaug Date 2003-04-17 Time 12:12 Rev Time 1.25
Received By jwitmer Date 2003-03-31 Time 16:20 Sent To  
Notes
2003-03-31 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03022362
 ADD: 334 HUNTER ST
 CONT: O/B ANDERSON GEORGE
 TEL: (561)585-1301
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) SHEET 3.1 GENERAL NOTES (1) PLANS
 INDICATE THAT THE WORK SHALL COMPLY WITH
 THE STANDAERD BUILDING CODE. WE ARE
 CURRENTLY USING THE 2001 FLORIDA BUILD-
 ING CODE.
  
 2) NOTE 12 INDICATES THE USE OF DEAD
 BOLTS FOR EXTERIOR DOORS. 1012.7 DOUBLE
 CYLINDER DEAD BOLTS ARE PROHIBITED ON
 REQUIRED MEANS OF EGRESS DOORS.
  
 3) MISSING PRODUCT TESTING REPORTS FOR
 THE EXTERIOR DOORS 001 & 003. THE CITY
 ACCEPTS S.B.C.C.I. REPORTS OR DADE
 COUNTY PRODUCT ACCEPTANCE REPORTS.
  
 4) SHEET 4.1 INDICATES THE BEAM 8"X22"
 BEING CUT DOWN TO 8"X12". WHEN CUTTING
 THE BEAM IN HALF WHAT STEEL WILL REPLACE
 THE BOTTOM TENSION STEEL?
  
 5) SHEET 3.1 INDICATES A NEW (3) 2X12
 WOOD BEAM TO SIT ON THE EXISTING TIE
 BEAM (EXTERIOR WALL). SHEET 4.1 DETAIL
 (3) INDICATES THAT IT SITS ON TOP OF THE
 TIE BEAM. HOW DOES THE DROP CEILING AT
 7'-6" ATTACH TO THIS NEW BEAM? SEE
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-17 Cont ID  
Sent By shernand Date 2003-05-21 Time 14:20 Rev Time 0.50
Received By btrobaug Date 2003-04-17 Time 12:11 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-04 Cont ID  
Sent By shernand Date 2003-04-16 Time 10:50 Rev Time 0.33
Received By dpalmer Date 2003-03-04 Time 07:12 Sent To P
Notes
2003-03-04 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE SEE RISER DIAGRAM, PLEASE
 SEE CONDUCTORS LEAVING BOTTON OF PANEL
 AND GOING TO?? 3-#1'S ETC??
  
 2)NOTE: PLEASE SEE CONDUCTORS SHOWN ON
 PANEL SCHEDULE AS FEEDERS, PLEASE SEE
 250-24, AN EQUIPMENT GROUND IS ONLY
 INSTALLED AFTER THE FIRST MEANS OF DISC.
  
 3)NOTE: PLEASE 210-52-C-3 FOR MISSING
 GFI ON PENINSULAR.
  
 4)NOTE: PLEASE SEE PANEL SCHEDULE, SHOWS
 ONLY ONE EXTS SMALL APPLIANCE CIRCUIT.
 PLEASE SEE 210-11-C1
  
 5)NOTE: IF THIS IS A NEW SERVICE, PLEASE
 SUBMIT AIC RATING OF NEW MAIN, ALL
 MUST BE RATED FOR THE AVAILABLE FAULT
 CURRENT. 110-9.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-21 Cont ID  
Sent By shernand Date 2003-05-21 Time 14:20 Rev Time 0.00
Received By shernand Date 2003-05-21 Time 14:20 Sent To B
Notes
2003-05-21 00:00:00JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-16 Cont ID  
Sent By shernand Date 2003-04-16 Time 10:50 Rev Time 0.00
Received By shernand Date 2003-04-16 Time 10:50 Sent To E
Notes
2003-04-16 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-28 Cont ID  
Sent By btrobaug Date 2003-02-28 Time 15:19 Rev Time 0.00
Received By btrobaug Date 2003-02-28 Time 15:19 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-03-13 Cont ID  
Sent By kstevens Date 2003-03-12 Time 18:42 Rev Time 0.30
Received By pkrauss Date 2003-03-13 Time 08:46 Sent To B
Notes
2003-03-13 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PROVIDE ENERGY & MANUAL J
 CALCULATIONS SHOULD A NEW HVAC SYSTEM
 BE INSTALLED.PROVIDE A COMPLETED FORM
 600C SHOULD EXISITNG EQUIPMENT BE USED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-03-12 Cont ID  
Sent By dpalmer Date 2003-03-04 Time 07:12 Rev Time 0.25
Received By kstevens Date 2003-03-12 Time 18:41 Sent To M
Notes
2003-03-12 00:00:00NO PLUMBING PLANS SUBMITTED