Plan Review Details - Permit 03022292
Plan Review Stops For Permit 03022292
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-30 Cont ID  
Sent By rbrown Date 2003-04-30 Time 16:43 Rev Time 0.00
Received By rbrown Date 2003-04-30 Time 16:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-04 Cont ID  
Sent By dpalmer Date 2003-04-24 Time 15:23 Rev Time 0.00
Received By rbrown Date 2003-04-04 Time 10:41 Sent To  
Notes
2003-04-03 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 MODEL B REVERSE
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) BOUNDARY LINE SURVEY.THE DRAWING
 SHALL BE AMENDED TO SHOW THE EGRESS
 EASEMENT REQUIRED ON THE ADJACENT LOT
 (LOT 3), TO ALLOW SAFE SECONDARY EGRESS
 FROM BEDROOM 2 (VIA THE ATRIUM) OF THE
 HOME ON LOT 4.
  
 2) BOUNDARY LINE SURVEY. IF THE ADJACENT
 LOT 5 REQUIRES AN EASEMENT ON LOT 4, FOR
 SECONDARY EGRESS FROM BEDROOMS, THEN THE
 EGRESS EASEMENT MUST BE SHOWN ON THE
 SURVEY DRAWING FOR THIS LOT AND THAT OF
 LOT 5
  
 3) SHEET S-1, ROOF FRAMING PLAN.NO
 TRUSS ANCHORS ARE SPECIFIED ALONG THE
 FAMILY ROOM WALL.
  
 4) SHEET S-1, ROOF FRAMING PLAN.ADD A
 KEY, FOR THE TRUSS ANCHOR REFERENCE
 ANNOTATION, TO CONFIRM IF1MEANS
 CONNECTOR MARK 1, AND IF 'U' IS THE
 DESIGN UPLIFT CAPACITY REQUIRED.WHAT
 IS THE VALUE STATED AS 'R', IS IT THE
 REQUIRED LATERAL LOAD CAPACITY (EITHER
 F1 OR F2)?
  
 5) SHEET S-2, CONNECTOR SCHEDULE.AMEND
 THE SCHEDULE TO INCLUDE THE UPLIFT AND
 THE LATERAL LOAD CAPACITY FOR THE
 SELECTED ANCHORS AND LUMBER GRADE.
  
 6) FBC TABLE 600THE GLASS BLOCK WINDOW
 IS ON THE PROPERTY LINE.AMEND THE
 PLANS TO SHOW THE REQUIREMENT FOR A ONE-
 HOUR FIRE-RATED ASSEMBLY.
  
 7) SHEET S3, PLYWOOD NAILING DETAIL.
 AMEND '10/32 CDX PLYWOOD' TO READ
 '19/32 CDX PLYWOOD'.
  
 8) PROVISO - ROOF TILE PRODUCT APPROVAL
 NOA# 99-1012.02 HAS EXPIRED.SUBMIT A
 CURRENT PRODUCT APPROVAL.
  
 9) PROVISO - OUTSWING STEEL DOUBLE DOOR
 PRODUCT APPROVAL NOA# 99-0311.03 HAS
 EXPIRED.SUBMIT A CURRENT PRODUCT
 APPROVAL.
  
 10) PROVISO - ALUMINUM SLIDING GLASS DOO
 PRODUCT APPROVAL NOA# 98-1228.01 HAS
 EXPIRED.SUBMIT A CURRENT PRODUCT
 APPROVAL.
  
 11) PROVISO - ALUMINUM TUBE MULLION
 PRODUCT APPROVAL NOA# 99-0310.01 HAS
 EXPIRED.SUBMIT A CURRENT PRODUCT
 APPROVAL.
  
 12) PROVISO - SINGLE HUNG WINDOW PRODUCT
 APPROVAL NOA# 98-1222.02 HAS EXPIRED.
 SUBMIT A VALID PRODUCT APPROVAL.
  
 13) SHEET S-4.ONE OF THE PLAN SETS HAS
 TWO DIFFERENT SHEETS NUMBERED S-4, ONE
 OF WHICH IS NOT SIGNED AND SEALED.
 REMOVE THE ONE WHICH IS NOT APPLICABLE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-09-02 Cont ID  
Sent By dpalmer Date 2003-09-02 Time 12:46 Rev Time 0.25
Received By dpalmer Date 2003-09-02 Time 12:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-24 Cont ID  
Sent By bstaples Date 2003-08-19 Time 08:48 Rev Time 0.25
Received By dpalmer Date 2003-04-24 Time 15:23 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-13 Cont ID  
Sent By shernand Date 2003-04-17 Time 16:39 Rev Time 0.75
Received By dpalmer Date 2003-03-13 Time 06:22 Sent To P
Notes
2003-03-13 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE SET PLANS/SHEET SO PAGE
 CAN BE OPENED UP TO SEE LOAD CALCULATION
 -S.
  
 2)NOTE: PLEASE SIZE SEC PER 310-15.
  
 3)NOTE: UPON SIZING SEC, PLEASE SIZE
 GROUNDING ELECTRODE CONDUCTOR PER 250-66
  
 4)NOTE: PLEASE SEE SERVICE AMP/LOAD
 SHOWN @ 144? PLEASE SEE PANEL A/B LOADS.
  
 5)NOTE: PLEASE LIST THE REQ`D BATH
 CIRCUIT(S) PER 210-52D/210-11-C-3
  
 6)NOTE: PLEASE SEE NOTE AT BOTTOM OF
 LOAD CALCS, NOTE MENTIONS SERVICE TO BE
 SIZED PER 220-17.PLEASE REMOVE, APPLIES
 TO APPLIANCES
  
 7)NOTE: PLEASE SEE SCALE ON PLAN, SHOWS
 1/4" =1'??
  
 8)NOTE: PLEASE SEE FEEDER SIZE FOR
 PANEL "A", 150ABRKR W/ 2/0`S, THIS IS
 PERMITTED, HOWEVER IF SHOWN ON PLAN,
 THEN IT MUST BE INSTALLED. PLEASE VERIFY
 WITH CONTRACTOR.
  
 9)NOTE: PLEASE CORRELATE LOADS SHOWN ON
 PANEL "B" AND LOAD CALCUALTIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-19 Cont ID  
Sent By bstaples Date 2003-08-19 Time 08:48 Rev Time 0.00
Received By bstaples Date 2003-08-19 Time 08:48 Sent To E
Notes
2003-08-19 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-17 Cont ID  
Sent By shernand Date 2003-04-17 Time 16:39 Rev Time 0.00
Received By shernand Date 2003-04-17 Time 16:39 Sent To E
Notes
2003-04-17 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-28 Cont ID  
Sent By btrobaug Date 2003-02-28 Time 16:26 Rev Time 0.00
Received By btrobaug Date 2003-02-28 Time 16:26 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-22 Cont ID  
Sent By hmoser Date 2003-03-22 Time 09:45 Rev Time 0.25
Received By hmoser Date 2003-03-22 Time 09:45 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-03-17 Cont ID  
Sent By jleech Date 2003-03-15 Time 12:32 Rev Time 0.33
Received By rregueir Date 2003-03-17 Time 19:17 Sent To B
Notes
2003-03-17 00:00:00MECH PLAN REVIEW: FALIED
 PLAN IS NOT LEGIBLE AS SUBMITTED.
 UNABLE TO READ DUCT SIZES, GRILL SIZES
 OR EQUIPMENT LISTING.
 SUBMIT CLEARER AND/OR LARGER COPIES.
 RONALD J REGUEIRO 659-8096 X8512

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-03-15 Cont ID  
Sent By dpalmer Date 2003-03-13 Time 06:40 Rev Time 0.33
Received By jleech Date 2003-03-15 Time 12:32 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-04 Cont ID  
Sent By btrobaug Date 2003-02-28 Time 16:26 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***