Plan Review Details - Permit 03022270
Plan Review Stops For Permit 03022270
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-17 Cont ID  
Sent By lsmith Date 2003-04-17 Time 14:14 Rev Time 0.30
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-13 Cont ID  
Sent By btrobaug Date 2003-04-14 Time 12:55 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2003-03-13 00:00:00***************FAILED**************
 1. PLANS MUST COMPLY WITH FBC 2001
 CHAPTER 424 FOR RESIDENTIAL POOLS.
 2. EQUIPMENT ANCHORINGMETHOD MUST BE
 SHOWN ON PLANS.
 3. METHOD OF PROTECTING OPENINGS FROM
 HOUSE TO POOL MUST BE SHOWN ON PLANS.
 4. NEED COPY OF CONTRACT TO VARIFY VALUE
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 8394

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-04-17 Cont ID  
Sent By btrobaug Date 2003-04-17 Time 14:26 Rev Time 0.33
Received By btrobaug Date 2003-04-17 Time 14:23 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-04-14 Cont ID  
Sent By btrobaug Date 2003-04-14 Time 12:55 Rev Time 0.33
Received By btrobaug Date 2003-04-14 Time 12:52 Sent To B
Notes
2003-04-14 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOTE: PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY ARCH/ OR
 ENGINEER ARE REQ`D PER 61G15-23.002 FOR
 ENGINEER AND 61G1-16.004 FOR ARCH.
 SHALL HAVE A TITLE BLOCK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-03-13 Cont ID  
Sent By kstevens Date 2003-04-14 Time 12:22 Rev Time 0.33
Received By btrobaug Date 2003-03-13 Time 11:46 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-03 Time 15:21 Rev Time 0.00
Received By shernand Date 2003-04-03 Time 15:21 Sent To B
Notes
2003-04-03 00:00:00MISC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-28 Cont ID  
Sent By btrobaug Date 2003-02-28 Time 15:57 Rev Time 0.00
Received By btrobaug Date 2003-02-28 Time 15:57 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-04-17 Cont ID  
Sent By btrobaug Date 2003-04-17 Time 14:26 Rev Time 0.50
Received By kstevens Date 2003-04-17 Time 14:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-04-14 Cont ID  
Sent By kstevens Date 2003-04-14 Time 12:12 Rev Time 0.50
Received By kstevens Date 2003-04-14 Time 12:12 Sent To E
Notes
2003-04-14 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) F.S. 61G15-23.002 TITLE BLOCK REQUI-
 RED. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND NUMBER ON EACH
 SHEET. A TITLE BLOCK ON EACH SHEET CON-
 TAINING THE PRINTED NAME, ADDRESS, AND
 ENGINEER OR ENGINEERING BUSINESS WILL
 SATISFY THIS REQUIREMENT.
 2) PIPING DIAGRAM SHOWS TWO PUMPS AND
 SPA MAIN DRAINS. NO SPA IS INDICATED ON
 POOL LAYOUT. PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-03-12 Cont ID  
Sent By sgraham Date 2003-03-11 Time 11:51 Rev Time 0.50
Received By kstevens Date 2003-03-12 Time 18:13 Sent To E
Notes
2003-03-12 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) SECTION 104.2.1 TWO OR MORE COPIES OF
 SPECIFICATIONS, AND OF DRAWINGS DRAWN TO
 SCALE WITH SUFFICIENT CLARITY AND DETAIL
 TO INDICATE THE NATURE AND CHARACTER OF
 THE WORK SHALL ACCOMPANY THE APPLICATION
 FOR THE PERMIT. PLANS ARE NOT CLEAR AND
 UNREADABLE. PLEASE RESUBMIT.
 B) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS. (ADD TO NOTES)
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92, AND NSPI-5. (ADD TO
 NOTES)
 3) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 4) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 5) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 6) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. (DETAIL)
 7) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 8) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 9) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 10) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 11) ATMOSPHERIC VENT DETAIL SAYS TEE BUT
 SHOWS TWO 90'S PLEASE CLAIRFY.
 12) PIPING SCHEMATIC DOES NOT SHOW THE
 VACUUM LINE, WATER FALL PLANTER LINE, OR
 VALVES REQUIRED BY SECTION 424.2.8.2.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2003-03-11 Cont ID  
Sent By btrobaug Date 2003-02-28 Time 15:57 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***