| Plan Review Stops For Permit 03022159 |
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-06-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-06-02 |
Time |
08:55 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-06-02 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2003-06-02 00:00:00 | REVISION OK - MOVE BBQ LINE TO OUTSIDE | | | SECTION - REMOVE AND CAP TEE INSIDE. | | | | | | | | | FIELD INSPECTOR TO VERIFY BTU'S FOR EACH | | | APPLIANCE. | | | DRYER ROOM IS A CONFINED SPACE. | | | OPENINGS REQUIRED PER SECTION 304.3.1 0R | | | SECTION 304.3.2. 1,100 CU.FT. REQUIRED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2003-03-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-03-07 |
Time |
14:09 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-03-07 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2003-03-07 00:00:00 | | | | | | | | | | FIELD INSPECTOR TO VERIFY BTU'S FOR EACH | | | APPLIANCE. | | | | | | DRYER ROOM IS A CONFINED SPACE - 1,100 | | | CUBIC FEET REQUIRED - 575 CUBIC FEET | | | PROVIDED - OPENINGS REQUIRED BY SECTION | | | 304.3.1 OR 304.3.2 TO BE INSTALLED. |
|
|
|