Review Stop P PLUMBING
Rev No 2 Status P Date 2003-06-02 Cont ID  
Sent By kstevens Date 2003-06-02 Time 08:55 Rev Time 0.50
Received By kstevens Date 2003-06-02 Time 08:55 Sent To  
Notes
2003-06-02 00:00:00REVISION OK - MOVE BBQ LINE TO OUTSIDE
 SECTION - REMOVE AND CAP TEE INSIDE.
  
  
 FIELD INSPECTOR TO VERIFY BTU'S FOR EACH
 APPLIANCE.
 DRYER ROOM IS A CONFINED SPACE.
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2. 1,100 CU.FT. REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-03-07 Cont ID  
Sent By kstevens Date 2003-03-07 Time 14:09 Rev Time 1.00
Received By kstevens Date 2003-03-07 Time 14:09 Sent To  
Notes
2003-03-07 00:00:00 
  
  
 FIELD INSPECTOR TO VERIFY BTU'S FOR EACH
 APPLIANCE.
  
 DRYER ROOM IS A CONFINED SPACE - 1,100
 CUBIC FEET REQUIRED - 575 CUBIC FEET
 PROVIDED - OPENINGS REQUIRED BY SECTION
 304.3.1 OR 304.3.2 TO BE INSTALLED.