Plan Review Details - Permit 03021865
Plan Review Stops For Permit 03021865
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-06-12 Cont ID  
Sent By rmcdouga Date 2003-06-12 Time 10:45 Rev Time 2.00
Received By rmcdouga Date 2003-06-12 Time 10:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-05-07 Cont ID  
Sent By rmcdouga Date 2003-05-06 Time 14:29 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-05-06 00:00:00BUILDING DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE ENERGY CALCULATIONS AS
 REQUIRED BY CHAPTER 13 OF THE FBC.
  
 4) PROVIDE AN ADDITIONAL COPY OF THE
 SURVEY.
  
 5) SUBMIT AN ADDITIONAL COPY OF THE
 PRODUCT APPROVAL FOR THE POMA BAHAMA
 SHUTTERS. PROVIDE A KEY PLAN AND
 INSTALLATION SCHEDULE FOR THE STORM
 PANELS. INDICATE THE TYPE OF STORM PANEL
 THAT WILL BE INSTALLED AT EACH OPENING.
  
 6) SHEET A1 INDICATE THAT ALL WINDOWS
 ARE SINGLE HUNG (SH),HOWEVER, NO
 PRODUCT APPROVALS FOR SINGLE HUNG
 WINDOWS WERE SUBMITTED. THE PRODUCT
 APPROVALS THAT WERE SUBMITTED ARE FOR
 HORIZONTAL SLIDING WINDOWS (HS) AND
 CASEMENT WINDOWS (CSMT).
  
 7) ITEM #10 ON PREVIOUS REVIEW WAS NOT
 ADDRESSED. IDENTIFY ON THE PLANS THE
 EXISTING ROOMS THAT ARE ADJACENT TO THE
 ADDITION.
  
 8) INDICATE ON THE PLANS THAT THE WIRE
 MESH IN THE SLAB IS REQUIRED TO BE
 SUPPORTED ON APPROVED MATERIALS AT A
 MAXIMUM OF 3 FEET O.C. PER FBC 1909.3.
  
 9) THE FOOTER SPECS ON A1 SPECIFY THREE
 #5 REINFORCING BARS IN THE FOOTER AND
 THE WALL SECTION ON A2 SPECIFIES TWO
 #5 BARS. PLEASE CLARIFY.
  
 10) THE WALL SECTION ON A2 SPECIFIES
 MTSM 20 TRUSS CONNECTORS AT THE NEW TIE
 BEAM AND THE ROOF FRAMING PLAN ON A1
 CALLS FOR HETAL 20 CONNECTORS AT THE
 NEW BEAM AND MSTM 20 CONNECTORS AT THE
 EXISTING TIE BEAM. THE HETAL 20 CAN BE
 INSTALLED INTO THE CONCRETE WHEN THE
 NEW BEAM IS POURED AND THE MSTM 20 CAN
 BE USED AT THE EXISTING BEAM. PLEASE
 CORRECT.
  
 11) THE 2003 SIMPSON CATALOG REQUIRES
 THE MSTM 20 TO BE ATTACHED TO THE
 EXISTING TIE BEAM WITH (4) 1/4"X 2-1/4"
 TITEN SCREWS AND (10) 10D NAILS INTO THE
 WOOD ROOF JOIST. PLEASE CORRECT.
  
 12) CHANGE THE TRUSS CONNECTOR SPECIFIED
 ON A1 FOR THE ROOF JOIST TO EXISTING
 BEAM FROM A TS-18 TO THE MSTM 20.
  
 13) THE ENGINEER'S TITLE BLOCK IS
 MISSING ON SHEET A1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-31 Cont ID  
Sent By sgraham Date 2003-05-06 Time 09:40 Rev Time 4.00
Received By rmcdouga Date 2003-03-31 Time 13:34 Sent To  
Notes
2003-03-31 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE ENERGY CALCULATIONS AS
 AS REQUIRED BY CHAPTER 13 OF THE FBC.
  
 4) PROVIDE TWO COPIES OF A RECENT
 SURVEY.
  
 5) LARGE MISSILE IMPACT PROTECTION IS
 REQUIRED FOR ALL NEW GLAZED OPENINGS.
 PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 6) THE WALL SECTION ON A2 SPECIFIES R-19
 BLOWN INSULATION. THIS WILL NOT BE
 POSSIBLE WITH A SINGLE ASSEMBLY ROOF/
 CEILING SYSTEM AS SHOWN.
  
 7) THE SIMPSON TS-18 SPECIFIED ON A2 IS
 A WOOD TO WOOD CONNECTOR. PLEASE REVISE
 TO A WOOD TO MASONRY CONNECTOR SUCH AS A
 MTSM 20. SPECIFY THE FASTENERS AS LISTED
 IN THE 2003 CATALOG.
  
 8) THE PLANS LIST 3636SH WINDOWS. PLEASE
 CLARIFY. ARE THESE H36 SINGLE HUNG
 WINDOWS AS THEY APPEAR TO BE ON THE
 ELEVATIONS? PROVIDE PRODUCT APPROVAL FOR
 THE WINDOWS AS SHOWN ON PLANS THAT WILL
 BE INSTALLED.
  
 9) SPECIFY ON THE DRAWINGS WEATHER THE
 DOOR AT THE REAR OF THE EXISTING
 STRUCTURE IS EXISTING OR NOT. IF IT IS
 NEW PROVIDE PRODUCT APPROVALS.
  
 10) THE NEW ADDITION CAN NOT BLOCK ANY
 EXISTING BED ROOM EGRESS WINDOWS OR BATH
 ROOM WINDOWS (UNLESS MECHANICAL VENT IS
 INSTALLED). IDENTIFY ON PLANS THE EXIST-
 ING ROOMS ADJACENT TO THE ADDITION.
  
 11)THE WIRE MESH IN THE SLAB IS REQUIRED
 TO BE SUPPORTED ON APPROVED MATERIALS AT
 MAX. OF 3 FEET O.C. PER FBC 1909.3.
 INDICATE ON THE PLANS.
  
 12) THE NEGATIVE WINDLOAD PRESSURES ARE
 INDICATED ON THE PLANS WITH POSITIVE
 SIGNS. PLEASE PLACE NEGATIVE SIGNS IN
 FRONT OF THE NEGATIVE PRESSURES ON A2.
  
 13) INDICATE ON THE WALL SECTION THAT
 THE FOOTING IS REQUIRED TO BE A MINIMUM
 OF 12" BELOW GRADE AND THE FINISH FLOOR
 ELEVATION IS REQUIRED TO BE A MINIMUM OF
 4" ABOVE FINISH GRADE. FBC 1804.1.3 AND
 CITY AMENDMENTS TO FBC 1804.1.7
  
 14) THE PLANS ARE REQUIRED TO HAVE A
 TITLE BLOCK WITH THE ENGINEER'S NAME,
 ADDRESS AND NUMBER. 61G15-23.002
  
 15) ADDITIONAL PERMITS WILL BE REQUIRED
 FOR ROOFING AND OTHER TRADES WITH
 ADDITIONAL FEES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-03-17 Cont ID  
Sent By sthyng Date 2003-03-13 Time 15:50 Rev Time 0.50
Received By btrobaug Date 2003-03-17 Time 13:23 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-23 Cont ID  
Sent By shernand Date 2003-04-23 Time 16:21 Rev Time 0.00
Received By shernand Date 2003-04-23 Time 16:21 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-13 Cont ID  
Sent By sthyng Date 2003-03-13 Time 15:45 Rev Time 0.00
Received By sthyng Date 2003-03-13 Time 15:45 Sent To E
Notes
2003-03-13 00:00:00OK TO GO THROUGH REVIEW PER SHIRLEY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-25 Cont ID  
Sent By dpalmer Date 2003-02-25 Time 09:13 Rev Time 0.00
Received By dpalmer Date 2003-02-25 Time 09:13 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-03-19 Cont ID  
Sent By kstevens Date 2003-03-18 Time 09:14 Rev Time 0.20
Received By pkrauss Date 2003-03-19 Time 06:39 Sent To B
Notes
2003-03-19 00:00:00NO MECHANICAL PLANS SUBMITTED - NO
 MECHANICAL WORK INDICATED ON PLAN.
 PROVIDE A COMPLETED FORM 600C WITH
 MECHANICAL PERMIT APPLICATION SHOULD
 ANY MECHANICAL WORK BE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-06-25 Cont ID  
Sent By kstevens Date 2003-06-25 Time 16:26 Rev Time 0.25
Received By kstevens Date 2003-06-25 Time 16:26 Sent To  
Notes
2003-06-25 00:00:00MISSED RISER AT TIME OF REVIEW KSTEVENS

Review Stop P PLUMBING
Rev No 2 Status N Date 2003-05-07 Cont ID  
Sent By rmcdouga Date 2003-05-07 Time 09:41 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-06-12 00:00:00NO PLANS SUBMITTED

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-03-18 Cont ID  
Sent By btrobaug Date 2003-03-17 Time 13:50 Rev Time 0.25
Received By kstevens Date 2003-03-18 Time 09:14 Sent To M
Notes
2003-03-18 00:00:00NO PLUMBING PLANS SUBMITTED

Review Stop Z ZONING
Rev No 2 Status P Date 2003-05-06 Cont ID  
Sent By sgraham Date 2003-05-06 Time 09:40 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-03-13 Cont ID  
Sent By shernand Date 2003-04-23 Time 16:21 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-03-13 00:00:00DENIED, MUST PROVIDE A COMPLETE FLOOR
 PLAN SHOWING EXISTING KITCHEN REMOVED