Plan Review Details - Permit 03021815
Plan Review Stops For Permit 03021815
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-08-15 Cont ID  
Sent By hpiskura Date 2003-08-15 Time 11:20 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-08-15 00:00:00REVISIONS DATED 7/29/03 GA1

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-11 Cont ID  
Sent By hpiskura Date 2003-07-11 Time 14:36 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-07-11 00:00:00REVISIONS DATED 6/12/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-03-10 Cont ID  
Sent By hpiskura Date 2003-03-10 Time 13:00 Rev Time 0.00
Received By hpiskura Date 2003-03-10 Time 13:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-09-29 Cont ID  
Sent By dpalmer Date 2003-09-29 Time 17:39 Rev Time 0.50
Received By dpalmer Date 2003-09-29 Time 17:39 Sent To  
Notes
2003-09-29 00:00:00REDLINED SAME NOTES AS PREVIOUS REVIEW.
  
 700.12E
 210.63
 PLEASE ADDRESS BEFORE FINAL.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-08-11 Cont ID  
Sent By dpalmer Date 2003-08-11 Time 19:52 Rev Time 0.50
Received By dpalmer Date 2003-08-11 Time 19:48 Sent To  
Notes
2003-08-11 00:00:00********* NOTES REDLINED ************
  
 1)NOTE; PLEASE SEE 210.63 FOR RECEPT FOR
 A/C EQUIPMENT.
  
 2)NOTE; PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM AND EXT LTS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-14 Cont ID  
Sent By dpalmer Date 2003-07-14 Time 15:20 Rev Time 0.25
Received By dpalmer Date 2003-07-14 Time 15:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-02-27 Cont ID  
Sent By dpalmer Date 2003-02-27 Time 08:28 Rev Time 0.25
Received By dpalmer Date 2003-02-27 Time 08:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-10-03 Cont ID  
Sent By mcarsill Date 2003-10-03 Time 15:34 Rev Time 0.00
Received By mcarsill Date 2003-10-03 Time 15:34 Sent To  
Notes
2003-10-03 00:00:001) ENSURE THAT EMERGENCY LIGHTS AND
 EXIT SIGNS ARE PRESENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-07-17 Cont ID  
Sent By alange Date 2003-08-11 Time 08:25 Rev Time 0.00
Received By nmccray Date 2003-07-17 Time 14:42 Sent To  
Notes
2003-07-17 00:00:00REVISION 7-07-03

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-03-07 Cont ID  
Sent By mcarsill Date 2003-03-07 Time 10:38 Rev Time 0.00
Received By mcarsill Date 2003-03-07 Time 10:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-10-15 Cont ID  
Sent By csiegber Date 2003-10-15 Time 11:02 Rev Time 0.00
Received By csiegber Date 2003-10-15 Time 11:02 Sent To M
Notes
2003-10-15 00:00:00TO PK DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-09-29 Cont ID  
Sent By csiegber Date 2003-09-26 Time 15:50 Rev Time 0.00
Received By csiegber Date 2003-09-26 Time 15:50 Sent To  
Notes
2003-09-26 00:00:00TO COMM BD #30

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-08-11 Cont ID  
Sent By alange Date 2003-08-11 Time 08:24 Rev Time 0.00
Received By alange Date 2003-08-11 Time 08:23 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-30 Time 11:40 Rev Time 0.00
Received By alange Date 2003-07-30 Time 11:40 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-07 Time 16:50 Rev Time 0.00
Received By shernand Date 2003-07-07 Time 16:50 Sent To  
Notes
2003-07-07 00:00:00COMM BOARD #25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-31 Cont ID  
Sent By sthyng Date 2003-03-31 Time 16:10 Rev Time 0.00
Received By sthyng Date 2003-03-31 Time 16:10 Sent To P
Notes
2003-03-31 00:00:00TO PLUMBING IN BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-26 Cont ID  
Sent By dpalmer Date 2003-02-26 Time 11:24 Rev Time 0.00
Received By dpalmer Date 2003-02-26 Time 11:23 Sent To  
Notes
2003-02-26 00:00:00TO #7 COMM BOARD.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-10-16 Cont ID  
Sent By pkrauss Date 2003-10-16 Time 11:11 Rev Time 0.35
Received By pkrauss Date 2003-10-16 Time 11:11 Sent To  
Notes
2003-10-16 00:00:00PROVISO:
 1.MECHANICAL PERMIT REQUIRED.
  
 2.EQUIPMENT STANDS ON THE ROOF SHALL
 COMPLY WITH 2001 FBC 1511.7, SEE
 ATTACHED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-10-15 Time 11:03 Rev Time 0.55
Received By pkrauss Date 2003-10-09 Time 10:41 Sent To  
Notes
2003-10-09 00:00:00DENIED:
 1.MECHANICAL PERMIT REQUIRED.PLANS
 ORIGINALLY SUBMITTED INDICATED
 MECHANICAL PLANS WOULD BE SUBMITTED
 WITH MECHANICAL PERMIT APPLCIATION
 SEPARATELY.
  
 2.PLANS INDICATE CONDENSATE WILL
 TERMINATE INTO OPEN FLOOR DRAIN? PLEASE
 SEE ATTACHED CITY CODE SECTION 90-125,
 PROHIBITIONS AND LIMITATIONS OF
 DISCHARGE.REVISE PLANS TO COMPLY.
  
 3.EQUIPMENT STANDS ON THE ROOF SHALL
 COMPLY WITH 2001 FBC 1511.7, SEE
 ATTACHED.
  
 4.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS AS PER 2001 FBC(M) TABLE
 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2003-08-12 Cont ID  
Sent By pkrauss Date 2003-08-12 Time 07:09 Rev Time 0.15
Received By pkrauss Date 2003-08-12 Time 07:08 Sent To  
Notes
2003-08-12 00:00:00MECHANICAL UNDER SEPARATE PERMIT (SEE
 COMMENTS DATED 8-7-03).

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-07-08 Cont ID  
Sent By pkrauss Date 2003-07-08 Time 10:51 Rev Time 0.25
Received By pkrauss Date 2003-07-08 Time 10:51 Sent To  
Notes
2003-07-08 00:00:00MECHANICAL BY OTHERS ON SEPARATE PERMIT
 PLAN SHEET GE-1 DUCT SMOKE DETECTOR
 IS TO BE INSTALLED IN THE SUPPLY AIR
 DUCT AS PER 2001 FBC(M) 606.2.1.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-03-03 Cont ID  
Sent By pkrauss Date 2003-03-03 Time 15:12 Rev Time 0.25
Received By pkrauss Date 2003-03-03 Time 15:10 Sent To  
Notes
2003-03-03 00:00:00NO MECHANICAL PLANS SUBMITTED.EXHAUST
 FANS INDICATED ON PLAN SHEET GE-2.

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-08-09 Cont ID  
Sent By kstevens Date 2003-08-09 Time 15:53 Rev Time 0.50
Received By kstevens Date 2003-08-09 Time 15:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-07-15 Cont ID  
Sent By alange Date 2003-07-30 Time 11:40 Rev Time 0.50
Received By kstevens Date 2003-07-15 Time 08:41 Sent To  
Notes
2003-07-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
  
 1) SHT GA-1 NEW BREAK AREA SINK SHALL
 COMPLY WITH 1104.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL SHOWING HEIGHT, KNEE
 CLEARANCE, DEPTH, CLEAR FLOOR SPACE, EX-
 POSEC PIPE PROTECTION, & FAUCETS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-04-02 Cont ID  
Sent By vmahle Date 2003-04-02 Time 12:07 Rev Time 0.75
Received By vmahle Date 2003-04-02 Time 12:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-03-20 Cont ID  
Sent By sthyng Date 2003-03-31 Time 16:10 Rev Time 0.75
Received By kstevens Date 2003-03-20 Time 10:36 Sent To  
Notes
2003-03-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHTGA-1 TOILET ROOM DETAILS, SHOW
 CLEAR FLOOR SPACE FOR LAVS. DOOR SHALL
 NOT OPEN INTO THE CLEAR FLOOR SPACE OF
 ANY FIXTURE. 114-22.2
 2) SHT GP-1 GENERAL PLUMBING NOTES #6 &
 WATER RISER DIAGRAM. AIR CHAMBERS ARE
 NOT APPROVED. PLEASE DELETE REFERENCE &
 REMOVE FROM RISER. 406.9 REQUIRES WATER
 HAMMER ARRESTORS ON QUICK CLOSING VALVES
 (WASH MACHINE, ICE MAKER, DISHWASHER).
 IF WATER HAMMER ARRESTORS ARE USED, THEY
 SHALL BE LOCATED NEAR THE FIXTURE NOT IN
 CEILING PER PDI-WH 201 & MANUF. INSTALL-
 ATION INSTRUCTIONS.
 3) ALL CAPPED/DEMO'ED PIPING SHALL BE
 INSPECTED PRIOR TO COVERING. (PLEASE
 ADD NOTE TO PLANS).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377