| 2003-03-07 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING AND |
| | RESUBMIT FOR REVIEW. |
| | |
| | 1} RISER DIAGRAM OF THE NEW SERVICE. |
| | |
| | 2} LOCATION OF NEW SERVICE, DON'T KNOW |
| | WHERE THE "UTILITY"ROOM OR BUILDING IS. |
| | |
| | 3} PLEASE RESUBMIT DRAWINGS WITH MORE |
| | CLARITY REGARDING THE SCOPE OF WORK |
| | WITH ALL ROOMS IN PLACE ON ONE SHEET |
| | FOR ELECTRICAL. |
| | |
| | 4} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 5} PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECT--ED PER 210-8-A-6. |
| | INCLUDES KITCHEN ISLANDS. |
| | |
| | 6} PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG. |
| | |
| | 7} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | IN THE VICINITY OF BEDROOMS AND CLOSE |
| | PROXIMITY OF STAIRWAYS. 2-5.2.1.3 |
| | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| | |
| | 8} PLEASE NOTE FRONT AND REAR |
| | RECEPTS REQ`D PER 210-52E |
| | |
| | 9} PLEASE LIST THE REQ`D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | |
| | 10} PLEASE SUBMIT LOAD CALCAULATION |
| | -S.PER 220,215-5. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/659-8096 EXT. 8392 |