| 2003-03-26 00:00:00 | **********CORRECTIONS************ |
| | |
| | PLEASE NOTE FBC 3401.7.1 AND 3401.7.2 |
| | |
| | 1.)IMPACT FEES WERE FOR 386 SQUARE |
| | FEET, CABANA ONLY.IMPACT FEES MUST |
| | BE PAID ON THE NEW HOUSE ADDITION. |
| | THE ACTUAL PERMIT PLANS MUST BE STAMPED |
| | BY THAT OFFICE, AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.PLEASE CALL 561-233-5025 |
| | FOR MORE INFORMATION. |
| | |
| | 2.)AREA TABULATION IS NOT CORRECT. |
| | PLEASE REVISE.AREA OF THE BAY WINDOW |
| | SHOULD ALSO BE INCLUDED.IF THE PATIO |
| | WAS PREVIOUSLY INDOOR AIR CONDITIONED |
| | SPACE, THIS REDUCTION SHOULD ALSO BE |
| | REFLECTED IN THE AREA TABULATIONS. |
| | IMPACT FEES WILL BE PAID ON ADDITIONAL |
| | LIVING AREA INCREASE. |
| | |
| | 3.)SEPARATE ENERGY CALCS REQUIRED FOR |
| | THE CABANA. |
| | |
| | 4.)PER FBC 104.2.1.1, PROVIDE ROOF |
| | FLASHING REQUIREMENTS & WIND RESISTANCE |
| | RATINGS THAT ARE REQUIRED TO BE |
| | INSTALLED. |
| | |
| | 5.)A 2X4 SKYLIGHT IS SHOWN HIGHLIGHTED |
| | ON SHEET A1.IF THIS IS A PROPOSED |
| | SKYLIGHT, SUBMIT PRODUCT APPROVALS.IF |
| | THIS IS EXISTING, INDICATE ON THE PLAN. |
| | |
| | 6.)PROVIDE PRODUCT APPROVALS FOR |
| | THE MULLS FOR WINDOW 8 AND FOR THE |
| | 45 DEGREE BAY MULLS. |
| | |
| | 7.)PROVIDE PRODUCT APPROVALS FOR |
| | THE EXTERIOR DOORS. |
| | |
| | 8.)PROVIDE PRODUCT APPROVALS FOR |
| | THE CASEMENT WINDOWS #12. |
| | |
| | 9.)PLEASE DATE THE ARCHITECTURAL |
| | SEAL AS PER FLORIDA STATUTE 61G1-16.003. |
| | |
| | 10.) FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 11.)ONE ACCESSIBLE BATHROOM REQUIRED |
| | FOR ALL RESIDENCES PER FBC 11-11 (1). |
| | |
| | 12.)1403.1.6 IN ORDER TO PROVIDE FOR |
| | INSPECTION FOR TERMITE INFESTATION, |
| | CLEARANCE BETWEEN EXTERIOR WALL COVER- |
| | INGS AND FINAL EARTH GRADE ON THE |
| | EXTERIOR OF A BUILDING SHALL NOT BE LESS |
| | THAN 6 INCHES.PLEASE REVISE WALL |
| | SECTION. |
| | |
| | 13.)PER FBC 1814.3.3, DAMPPROOFING |
| | IS REQUIRED FOR CONCRETE SLABS.PLEASE |
| | REVISE THE WALL SECTION (TYPICAL |
| | CONCRETE SLAB) ON SHEET A8. |
| | |
| | 14.)EXISTING BEDROOM WINDOWS ARE |
| | REQUIRED TO BE EGRESS WINDOWS (FBC1005.4 |
| | AND FBC 3401.7.1.2).PLEASE GIVE |
| | BEDROOM WINDOW INFORMATION; DIMENSIONS, |
| | TYPE, AND DISTANCE FROM FLOOR. |
| | |
| | 15.)ON WALL SECTIONS AND DETAILS, |
| | TWO COURSES OF LINTEL BLOCK W/STEEL IS |
| | DESCRIBED BUT ONLY ONE IS SHOWN.PLEASE |
| | REVISE IN ALL SECTIONS TO MAKE THE TEXT |
| | MATCH THE GRAPHIC. |
| | |
| | 16.)ATTIC ACCESS IS REQUIRED IN THE |
| | CABANA.GIVE SIZE AND LOCATION. |
| | |
| | 17.)ATTIC ACCESS IS REQUIRED IN THE |
| | ADDITION.GIVE SIZE AND LOCATION. |
| | |
| | 18.)ATTIC ACCESS REQUIRES INSULATION. |
| | ALSO, THE DETAIL TEXT REFERS TO A LADDER |
| | BUT IS NOT SHOWN.PLEASE REVISE THE |
| | DETAIL. |
| | |
| | 19.)IF THE FIREPLACE IS NOT FACTORY- |
| | BUILT, PLEASE PROVIDE A DETAIL.IF IT |
| | IS FACTORY BUILT, PLEASE COMPLY WITH |
| | NOTES 20 THROUGH 24. |
| | |
| | 20.) 2804.4.1 FACTORY-BUILT CHIMNEYS |
| | FACTORY BUILT CHIMNEYS SHALL BE LISTED |
| | AND SHALL BE INSTALLED IN ACCORDANCE |
| | WITH THE CONDITIONS OF THE LISTING, AND |
| | MANUFACTURER'S INSTRUCTION. |
| | |
| | 21.) 2804.4.4. FACTORY-BUILT CHIMNEYS |
| | FOR USE WITH CLOSED COMBUSTION WOOD |
| | BURNING APPLIANCES SHALL COMPLY WITH |
| | THE TYPE HT REQUIREMENT UL 103. |
| | |
| | 22.) CHIMNEYS FOR THE USE WITH FACTORY- |
| | BUILT FIREPLACES SHALL MEET THE |
| | REQUIREMENTS OF UL 127. |
| | |
| | 23.) 2806.1.2 FACTORY BUILT FIREPLACES |
| | SHALL BE TESTED IN ACCORDANCE WITH AND |
| | MEET THE REQUIREMENTS OF UL 127. |
| | |
| | 24.) 2810 FRESH AIR INTAKES, FRESH AIR |
| | INTAKESSHALL BE SCREENED WITH A CORRO- |
| | SION RESITANT MATERIAL NOT LARGER THAN |
| | 1/2 INCH MESH. FRESH AIR INTAKES SHALL |
| | NOT BE TAKEN FROM A LOCATION CLOSER THAN |
| | 10 FT FROM ANY CHIMNEY OR VENT OUTLET OR |
| | SANITARY SEWER VENT OUTLET, UNLESS SUCH |
| | VENT IS NOT LESS THAN 24" ABOVE THE |
| | FRESH AIR VENT. FRESH AIR INTAKE VENTS |
| | LOCATED ON THE ROOFS WILL BE PROPERLY |
| | MARKED WITH A UNIVERSAL MARKING, |
| | ***"INTAKE"***, PERMANETLY ATTACHED. |
| | SEE 705.1.1.4 FOR FIRE PROTECTION. |
| | |
| | 25.)PLEASE PROVIDE ADDITIONAL |
| | INFORMATION IN REGARDS TO THE METHOD |
| | OF SHORING. |
| | |
| | 26.)PLEASE PROVIDE INFORMATION IN |
| | REGARDS TO THE SIDING MATERIAL. |
| | |
| | 27.) PROVIDE STORM PANEL INFORMATION W/ |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. |
| | FBC 1606.1.4. |
| | |
| | 28.)FIRESTOP REQUIRED.PLEASE REVISE |
| | WALL SECTION DETAILS. |
| | |
| | 29.)PROVIDE A DETAIL FOR THE BAY |
| | WINDOW. |
| | |
| | 30.)PROVIDE STRUCTURAL INFORMATION |
| | ON THE EXISTING PATIO WALLS.ARE THERE |
| | EXISTING COLUMNS?PROVIDE STRUCTURAL |
| | CALCULATIONS AND A DETAIL FOR THE |
| | PROPOSED PORCH TIE BEAM, INCLUDING |
| | THE CANTALEVERED SECTION OVER THE BAY |
| | WINDOW. |
| | |
| | 31.)FOR FOUNDATION DETAIL 1/A3, GIVE |
| | ALL DIMENSIONS. |
| | |
| | 32.)FOR DETAIL 2/A3, GIVE CONNECTION |
| | INFORMATION AT THE TOP OF THE POST. |
| | |
| | 33.)PROVIDE ADDITIONAL INFORMATION IN |
| | REGARDS TO UPLIFT AND CALCULATED LOADS. |
| | |
| | 34.)PROVIDE LOADING INFORMATION FOR |
| | THE TRUSSES. |
| | |
| | 35.)THE POOL IS TO COMPLY WITH FBC |
| | 424.2.17.1.INDICATE COMPLIANCE ON |
| | THE PLAN, EITHER AS EXISTING OR |
| | PROPOSED. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | SAMANTHA THYNG |
| | 561-659-8096, EXTENSION 8340, OR |
| | 561-805-6724 |