Plan Review Details - Permit 03021545
Plan Review Stops For Permit 03021545
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-16 Cont ID  
Sent By hpiskura Date 2003-04-16 Time 08:23 Rev Time 0.00
Received By hpiskura Date 2003-04-16 Time 07:28 Sent To  
Notes
2003-04-16 00:00:00PLANS DATED 3/26/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-03-11 Cont ID  
Sent By hpiskura Date 2003-03-11 Time 08:46 Rev Time 0.00
Received By hpiskura Date 2003-03-11 Time 08:00 Sent To  
Notes
2003-03-11 00:00:00PLANS DATED 2/7/03

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-02-26 Cont ID  
Sent By dpalmer Date 2003-02-26 Time 09:02 Rev Time 0.75
Received By dpalmer Date 2003-02-26 Time 09:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-04-04 Cont ID  
Sent By mcarsill Date 2003-04-04 Time 09:48 Rev Time 0.00
Received By mcarsill Date 2003-04-04 Time 09:48 Sent To  
Notes
2003-04-04 00:00:00APPROVED PROVISO:
  
 NO ELECTRICAL DRAWINGS PROVIDED. ALL
 REQUIRED ELECTRICAL EQUIPMENT TO WIT
 EXIT SIGNS AND EMERGENCY LIGHTS, AND
 FIRE ALARM EQUIPMENT SHALL BE PROVIDED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-03-07 Cont ID  
Sent By mcarsill Date 2003-03-07 Time 13:56 Rev Time 0.00
Received By mcarsill Date 2003-03-07 Time 13:55 Sent To  
Notes
2003-03-07 00:00:001) ALL WORK IS TO BE DONE IN ACCORDANCE
 WITH NFPA 241, THE STANDARD FOR
 BUILDINGS UNDER CONSTRUCTION, DEMOLITION
 AND RENOVATION.
  
 2) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 3) PLEASE CLEARLY ILLUSTRATE LOCATIONS
 OF FIRE ALARM EQUIPMENT.
  
 4) SEPARATE PLANS AND PERTMIT REQUIRED
 FOR FIRE SPRINKLER SYSTEM REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shernand Date 2003-04-23 Time 10:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-03 Time 13:03 Rev Time 0.00
Received By shernand Date 2003-04-03 Time 13:03 Sent To  
Notes
2003-04-03 00:00:00COMM BOARD #15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-21 Cont ID  
Sent By dpalmer Date 2003-02-21 Time 14:13 Rev Time 0.00
Received By dpalmer Date 2003-02-21 Time 14:13 Sent To  
Notes
2003-02-21 00:00:00TO COMM BOARD #16

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-04-16 Cont ID  
Sent By pkrauss Date 2003-04-16 Time 10:43 Rev Time 0.35
Received By pkrauss Date 2003-04-16 Time 10:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-03-11 Cont ID  
Sent By pkrauss Date 2003-03-04 Time 14:52 Rev Time 0.55
Received By pkrauss Date 2003-03-04 Time 14:51 Sent To  
Notes
2003-03-04 00:00:00PLEASE CLARIFY THE FOLLOWING INFORMATION
  
 1.EXISTING ATRIUM RETURN AIR DUCT
 THAT PENETRATES "TENANT SEPARATION"
 WALLS DO NOT INDICATE FIRE DAMPERS.
 CLARIFY IF THE FIRE DAMPERS ARE EXISTING
 OR IS THIS A PART OF AN EVAC SYSTEM...
 PLEASE CLARIFY.
 2.HP5 DOES NOT INDICATE A DUCT SMOKE
 DETECTOR.CLARIFY IF EXISTING, IT WILL
 BE REQUIRED IF THERE IS NOT ONE ALREADY
 INSTALLED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-04-12 Cont ID  
Sent By kstevens Date 2003-04-12 Time 15:16 Rev Time 0.50
Received By kstevens Date 2003-04-12 Time 15:15 Sent To  
Notes
2003-04-12 00:00:00PASSED/PROVISO
  
 MANUFACTURE INFORMATION FOR FILTER AND
 PUMP REQUIRED AT FINAL PLUMBING INSPECT-
 ION.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-03-11 Cont ID  
Sent By kstevens Date 2003-03-11 Time 12:52 Rev Time 1.00
Received By kstevens Date 2003-03-11 Time 12:51 Sent To  
Notes
2003-03-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) ALL PLUMBING APPLIANCES, POTABLE
 WATER COMPONENTS ECT SHALL BE LABELED BY
 AN APPROVED AGENCY. SECTION 303.4 - NSF
 APPROVAL FOR FILTER - LISTING FOR PUMP
 PLEASE PROVIDE MANUF. INFORMATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377